background image

5

1 - INTRODUCTION

 The 30XAS Aquaforce units are designed to cool water for the air 

conditioning of buildings and industrial processes.  

Prior to the initial start-up of the units, the people involved in the 

on-site installation, start-up, operation, and maintenance of this 

unit should be thoroughly familiar with these instructions and the 

specific project data for the installation site.

The 30XAS liquid chillers are designed to provide a very high level 

of safety during installation, start-up, operation and maintenance. 

They will provide safe and reliable service when operated within 

their application range.
They are designed for an operating life of 15 years by assuming a 

75% utilisation factor; that is approximately 100,000 operating hours.

This manual provides the necessary information to fami liarize 

yourself with the control system before performing start-up 

procedures. The procedures in this manual are arranged in the 

sequence  required  for  machine  installation,  start-up,  operation 

and maintenance.

Always  ensure  that  all  required  safety  measures  are  followed, 

including  those  in  this  document,  such  as:  wearing  protec tive 

clothing (gloves, ear defenders, safety glasses and shoes), using 

appropriate  tools,  employing  qualified  and  skilled  technicians 

(electricians, refrigeration engineers) and following local regulations.
To  find  out,  if  these  products  comply  with  European  directives 

(machine  safety,  low  voltage,  electromagnetic  compatibility, 

equipment under pressure etc.) check the declarations of 

conformity for these products.

1.1 - Installation safety considerations

Access to the unit must be reserved to authorised personnel, 

qualified and trained in monitoring and maintenance. The 

access limitation device must be installed by the customer 

(e.g. cut-off, enclosure).
After the unit has been received, when it is ready to be installed 

or reinstalled, and before it is started up, it must be inspected for 

damage.  Check  that  the  refrigerant  circuit(s)  is  (are)  intact, 

especially that no components or pipes have shifted (e.g. following 

a shock). If in doubt, carry out a leak tightness check and verify 

with the manufacturer that the circuit integrity has not been 

impaired. If damage is detected, immediately file a claim with the 

shipping company.

Carrier strongly recommends employing a specialised 

company to unload the machine.
Do not remove the skid or the packaging until the unit is in 

its final position. These units can be moved with a fork lift 

truck, as long as the forks are positioned in the right place 

and direction on the unit.

The  units  can  also  be  lifted  with  slings,  using  only  the 

designated lifting points marked on the unit.

These units are not designed to be lifted from above. Use 

slings with the correct capacity, and always follow the lifting 

instructions on the certified drawings supplied with the unit. 

Safety is only guaranteed, if these instructions are carefully 

followed. If this is not the case,  there  is a  risk  of material 

deterioration and injuries to personnel.
DO NOT COVER ANY PROTECTION DEVICES. 
This applies to fuse plugs and relief valves (if used) in the 

refrigerant or heat transfer medium circuits. Check if the 

original protection plugs are still present at the valve outlets. 

These plugs are generally made of plastic and should not be 

used. If they are still present, please remove them. Install 

devices at the valve outlets or drain piping that prevent the 

penetration of foreign bodies (dust, building debris, etc.) and 

atmospheric  agents  (water  can  form  rust  or  ice).  These 

devices, as well as the drain piping, must not impair operation 

and not lead to a pressure drop that is higher than 10% of the 

control pressure.

Classification and control
In  accordance  with  the  Pressure  Equipment  Directive  and 

national usage monitoring regulations in the European Union 

the protection devices for these machines are classified as 

follows:

Safety 

accessory

(1)

Damage limitation 

accessory

(2)

 

in case of an external fire

Refrigerant side

High-pressure switch

x

External relief valve***

x

Rupture disk

x

Fuse plug

x

Heat transfer fluid side

External relief valve

(4)

(4)

(1)  Classified for protection in normal service situations.

(2)  Classified for protection in abnormal service situations.

(3)  The instantaneous over-pressure limited to 10% of the operating pressure does 

not apply to this abnormal service situation. The control pressure can be higher 

than the service pressure. In this case either the design temperature or the 

high-pressure switch ensures that the service pressure is not exceeded in normal 

service situations.

(4)  The classification of these relief valves must be made by the personnel that 

completes the whole hydraulic installation.

Do not remove these valves and fuses, even if the fire risk is 

under control for a particular installation. There is no 

guarantee that the accessories are re-installed if the instal-

lation is changed or for transport with a gas charge.
When  the  unit  is  subjected  to  fire,  safety  devices  prevent 

rupture due to over-pressure by releasing the refrigerant. The 

fluid  may  then  be  decomposed  into  toxic  residues  when 

subjected to the flame:

 

-

Stay away from the unit.

 

-

Set up warnings and recommendations for personnel in 

charge to stop the fire.

 

-

Fire extinguishers appropriate to the system and the 

refrigerant type must be easily accessible.

All factory-installed relief valves are lead-sealed to prevent any 

calibration change. If the relief valves are installed on a change-

over valve this is equipped with a relief valve on each of the 

two outlets. Only one of the two relief valves is in operation, 

the other one is isolated. Never leave the change-over valve 

in the intermediate position, i.e. with both ways open (Bring 

the actuator in abutment, front or back according to the outlet 

to isolate). If a relief valve is removed for checking or 

replacement please ensure that there is always an active relief 

valve on each of the change-over valves installed in the unit.

The external relief valves must always be connected to drain 

pipes for units installed in a closed room. Refer to the 

installation regulations, for example those of European 

standard EN 378 and EN 13136.

These  pipes  must  be  installed  in  a  way  that  ensures  that 

people and property are not exposed to refrigerant leaks. As 

the fluids can be diffused in the air, ensure that the outlet is 

far  away  from  any  building  air  intake,  or  that  they  are 

discharged  in  a  quantity  that  is  appropriate  for  a  suitably 

absorbing environment.
Periodic  check  of  the  relief  valves:  See  paragraph  1.3 

“Maintenance safety considerations”.
Provide a drain in the discharge circuit, close to each relief 

valve, to avoid an accumulation of condensate or rain water.
All precautions concerning handling of refrigerant must be 

observed in accordance with local regulations.

Ensure good ventilation, as accumulation of refrigerant in an 

enclosed space can displace oxygen and cause asphyxiation 

or explosions.
Inhalation of high concentrations of vapour is harmful and 

may cause heart irregularities, unconsciousness, or death. 

Vapour is heavier than air and reduces the amount of oxygen 

available for breathing. These products cause eye and skin 

irritation. Decomposition products are hazardous.

Summary of Contents for Aquaforce 30XAS Series

Page 1: ...LLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Air Cooled Liquid Chillers 30XAS A Unit with option 279 compressor enclosure Nominal cooling capacity 232 486 kW 5...

Page 2: ...2...

Page 3: ...entry 17 5 5 Field control wiring 17 6 APPLICATION DATA 18 6 1 Operating range 18 6 2 Minimum chilled water flow units without hydraulic module 18 6 3 Maximum chilled water flow units without hydrauli...

Page 4: ...maintenance see note 34 11 2 Level 2 maintenance see note 34 11 3 Level 3 or higher maintenance see note 34 11 4 Tightening torques for the main electrical connections 34 11 5 Tightening torques for...

Page 5: ...or ice These devices as well as the drain piping must not impair operation and not lead to a pressure drop that is higher than 10 of the control pressure Classification and control In accordance with...

Page 6: ...ed off the power circuit remains energized unless the unit or circuit disconnect switch is open Refer to the wiring diagram for further details Attach appropriate safety labels Units with option 231 a...

Page 7: ...f a leak occurs or if the refrigerant becomes contaminated e g by a short circuit in a motor remove the complete charge using a recovery unit and store the refrigerant in mobile containers Repair the...

Page 8: ...uit Do not attempt to repair or recondition any safety devices when corrosion or build up of foreign material rust dirt scale etc is found within the valve body or mechanism If necessary replace the d...

Page 9: ...e frequency number of phases Maximum current drawn Maximum power input Unit net weight Confirm that all accessories ordered for on site installation have been delivered and are complete and undamaged...

Page 10: ...than 15 WARNING Never push or lever on any of the enclosure panels of the unit Only the base of the unit frame is designed to withstand such stresses 2 2 3 Checks before system start up Before the st...

Page 11: ...ional drawings supplied with the unit or available on request For the positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings B...

Page 12: ...or evaporator tube removal Water inlet Water outlet Air outlet do not obstruct Power supply connection C Control circuit connection 3 4 Multiple chiller installation It is recommended to install multi...

Page 13: ...4798 4798 Width mm 2253 2253 2253 2253 2253 Height mm 2322 2322 2322 2322 2322 Operating weight 4 Standard unit kg 2375 2791 2847 3603 3689 Standard unit option 119 kg 3051 3167 3963 4119 Standard uni...

Page 14: ...15 7 15 7 15 7 Evaporator Flooded multi pipe type Water content l 53 53 53 75 75 Without hydraulic module Water inlet outlet connections Victaulic Nominal diameter in 5 5 5 5 5 Actual outside diamete...

Page 15: ...full load and nominal voltage 88 1 89 4 90 1 91 3 1 Nominal efficiency at 75 rated load and nominal voltage 88 88 9 89 7 91 4 1 Nominal efficiency at 50 rated load and nominal voltage 86 1 86 7 87 9 9...

Page 16: ...60364 Outdoor installation Ambient temperature range from 20 C to 55 C Altitude less than or equal to 2000 m for hydraulic module see paragraph 4 3 in the IOM Presence of hard solids class AE3 no sign...

Page 17: ...ter the control box from below or from the unit side For 30XAS unit sizes 282 to 482 the control box that includes the power supply cable connection terminal is located in the lower part of the unit I...

Page 18: ...peration 3 3 15 Note If the leaving water temperature is below 4 C a glycol water solution or the frost protection option must be used Condenser air temperature C Minimum Maximum Storage 20 68 Operati...

Page 19: ...chieve the required volume The tank must itself be internally baffled in order to ensure proper mixing of the liquid water or brine Refer to the examples below Connection to a buffer tank Bad Bad Good...

Page 20: ...e eletrolytic pairs and consequently corrosion Verify then the need to install sacrificial anodes In case additives or other fluids than those recommended by Carrier are used ensure that the fluids ar...

Page 21: ...lable pressure pump 5 Drain valve 6 Flow control valve 7 Evaporator 8 Evaporator defrost heater option 9 Hydraulic module defrost heater option 10 Air vent evaporator 11 Water drain evaporator 12 Expa...

Page 22: ...in the operating limit table application data 7 5 2 Optional evaporator frost protection 30XAS If it is not possible to apply the recommendations in para graph 7 5 1 the units can be equipped with hea...

Page 23: ...0 350 400 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 282 3 50 100 150 200 250 300 350 400 5 7 9 11 13 15 17 19 21 23 25 27 29 31 342 442 482 7 7 2 NPSH Net Positive Suction Head required option 116C hyd...

Page 24: ...installed but supplied with the unit The sealing joints are in the control box The temperature sensors and the condenser flow switch are wired and fixed in the machine They must be installed as descri...

Page 25: ...r 8 4 Condenser water connections NOTE Drawings are not contractually binding Before designing an installation consult the certified dimensional drawings supplied with the unit or available on request...

Page 26: ...temperature at start up 12 5 1 55 Water entering temperature during operation 20 55 Water leaving temperature during operation 25 60 Evaporator water temperature C Minimum Maximum Water entering temp...

Page 27: ...eat exchange at the air condenser to heat exchange at the water condenser and vice versa is ensured by motorised two way valves located upstream of the air and water condensers ATTENTION Mode changes...

Page 28: ...eat exchange fluid check and carry out internal inspections as described in EN 378 annex C In case of re testing please refer to the maximum operating pressure given on the unit nameplate The reports...

Page 29: ...6 mm Insert this tool into the opening on the pressure switch and push the reset button in this location These pressure switches are located at the discharge of each compressor 9 3 2 Relief valves 30X...

Page 30: ...n insufficient charge or non con densables in the system The presence of moisture changes the colour of the indicator paper in the sight glass 9 8 Filter drier The role of the filter drier is to keep...

Page 31: ...t 1 2 3 4 1 2 4 5 3 1 2 4 5 3 1 2 5 6 3 6 7 4 1 2 5 6 3 7 4 8 x x Start up order Power connection NOTE The values above do not correspond to the fan designation The fan designation and position are gi...

Page 32: ...ified service and maintenance 30XAS 242 482 Compressor discharge valves 93A Shut off valve on the compressor discharge piping Simplified maintenance 30XAS 242 482 HP dual pump hydraulic module 116C Co...

Page 33: ...corrosive environments 30XAS 242 482 Super Enviro Shield anti corrosion protection 263 Extremely durable and flexible epoxy polymer coating applied on micro channel heat exchangers by electro coating...

Page 34: ...replace the mountings Check the water connections Purge the water circuit see chapter Water flow control procedure Clean the water filter see chapter Water flow control procedure Fully clean the conde...

Page 35: ...with clean water For coils installed in a coastal or industrial environment periodical cleaning by rinsing with water is beneficial It is however essential that rinsing is done with a low speed water...

Page 36: ...mpressor terminal pin as originally wired For replacement of the compressor a low pressure switch is included with the compressor This low pressure switch should be temporarily installed as a hard saf...

Page 37: ...of the unit can be recycled for another purpose 12 3 Fluids to be recovered for treatment Refrigerant Heat transfer fluid depending on the installation water brine solution etc Compressor oil 12 4 Ma...

Page 38: ...otection has been sized and installed properly All terminals are tight All chilled water valves are open All chilled water piping is connected properly All air has been vented from the chilled water c...

Page 39: ...y supply at once and ensure that the chiller is not switched on until corrective measures have been taken Check cooler water loop Water loop volume litres Calculated volume litres 3 25 litres nominal...

Page 40: ...alidity of certificate www eurovent certification com Order No 13467 09 2018 Supersedes order No 13467 12 2016 Manufactured by Carrier SCS Montluel France Manufacturer reserves the right to change any...

Reviews: