background image

20

7 - WATER CONNECTIONS

ATTENTION: Before carrying out any water connections 

install the water box purge plugs (one plug per water box in 

the lower section - supplied in the control box).

For size and position of the heat exchanger water inlet and outlet 

connections refer to the certified dimensional drawings supplied 

with the unit.
The water pipes must not transmit any radial or axial force to the 

heat exchangers nor any vibration. 

The  water  supply  must  be  analysed  and  appropriate  filtering, 

treatment, control devices, isolation and bleed valves and circuits 

built in, to prevent corrosion, fouling and deteriora-tion of the pump 

fittings. Consult either a water treatment specialist or appropriate 

literature on the subject.

7.1 - Operating precautions

The water circuit should be designed to have the least number of 

elbows and horizontal pipe runs at different levels. Below the main 

points to be checked for the connection:

 

-

Comply with the water inlet and outlet connections shown on 

the unit.

 

-

Install manual or automatic air purge valves at all high points 

in the circuit(s).

 

-

Use an expansion device to maintain pressure in the circuit(s) 

and install a relief valve as well as an expan-sion tank.

 

-

Install thermometers in both the entering and leaving water 

connections.

 

-

Install drain connections at all low points to allow the whole 

circuit to be drained.

 

-

Install stop valves, close to the entering and leaving water 

connections.

 

-

Use flexible connections to reduce the transmission of 

vibrations.

 

-

Insulate all pipework, after testing for leaks, both to reduce 

heat gains and to prevent condensation.

 

-

Cover the insulation with a vapour barrier.

 

-

Where there are particles in the fluid that could foul the heat 

exchanger, a screen filter should be installed ahead of the 

pump, or directly at the exchanger inlet in case the pump is 

more than 20m away. The mesh size of the filter must be 1.2 

mm (see ‘Typical water circuit’ diagram on the right).

 

-

Before the system start-up verify that the water circuits are 

connected to the appropriate heat exchangers (e.g. no 

reversal between evaporator and condenser).

 

-

Do not introduce any significant static or dynamic pres-sure 

into the heat exchange circuit (with regard to the design 

operating pressures).

 

-

Before  any  start-up  verify  that  the  heat  exchange  fluid  is 

compatible with the materials and the water circuit coating.

 

-

The use of different metals on hydraulic piping could generate 

eletrolytic pairs and consequently corrosion. Verify then, the 

need to install sacrificial anodes.

In  case  additives  or  other  fluids  than  those  recommended  by 

Carrier are used, ensure that the fluids are not considered as a 

gas,  and  that  they  belong  to  class  2,  as  defined  in  directive 

2014/68/EU.

Carrier recommendations on heat exchange fluids:

 

-

No NH

4+

  ammonium  ions  in  the  water,  they  are  very 

detrimental for copper. This is one of the most impor-tant 

factors for the operating life of copper piping. A content of 

several tenths of mg/l will badly corrode the copper over time.

 

-

Cl

-

 Chloride ions are detrimental for copper with a risk of 

perforations by corrosion by puncture. If possible keep below 

125 mg/l.

 

-

SO

4

2-

 sulphate ions can cause perforating corrosion, if their 

content is above 30 mg/l.

 

-

No fluoride ions (<0.1 mg/l).

 

-

No Fe

2+

 and Fe

3+

 ions with non negligible levels of dis-solved 

oxygen  must  be  present.  Dissolved  iron    <  5  mg/l  with 

dissolved oxygen < 5 mg/l.

 

-

Dissolved silica: silica is an acid element of water and can 

also lead to corrosion risks. Content < 1 mg/l.

 

-

Water hardness: > 0.5 mmol/l. Values between 1 and 2.5 can 

be recommended. This will facilitate scale deposit that can 

limit corrosion of copper. Values that are too high can cause 

piping blockage over time. A total alkalimetric titre (TAC) 

below 100 is desirable.

 

-

Dissolved oxygen: Any sudden change in water oxy-genation 

conditions must be avoided. It is as detrimen-tal to 

deoxygenate the water by mixing it with inert gas as it is to 

over-oxygenate it by mixing it with pure oxygen. The 

disturbance of the oxygenation conditions encourages 

destabilisation of copper hydroxides and enlargement of 

particles.

 

-

Electric conductivity 10-600 μS/cm.

 

-

pH: Ideal case pH neutral at 20-25 °C

 

-

7.5<pH<9

If the water circuit must be emptied for longer than one month, 

the complete circuit must be placed under nitrogen charge to avoid 

any risk of corrosion by differential aeration.

ATTENTION: Filling, completing and draining the water circuit 

charge must be done by qualified personnel, using the air 

purges and materials that are suitable for the products. 

Charging and removing heat exchange fluids should be done 

with devices that must be included on the water circuit by the 

installer. Never use the unit heat exchangers to add heat 

exchange fluid.

7.2 - 

Victaulic water connections

Inlet/outlet diameters without hydraulic module

30XAS

242-482

Standard

Diameter

in

5

Outside diameter

mm

141,3

Inlet/outlet diameters with hydraulic module (option)

30XAS (option 116)

242-482

Diameter

in

4

Outside diameter

mm

114,3

Expansion tank volume

l

50

Max, operating pressure

kPa

400

Summary of Contents for Aquaforce 30XAS Series

Page 1: ...LLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Air Cooled Liquid Chillers 30XAS A Unit with option 279 compressor enclosure Nominal cooling capacity 232 486 kW 5...

Page 2: ...2...

Page 3: ...entry 17 5 5 Field control wiring 17 6 APPLICATION DATA 18 6 1 Operating range 18 6 2 Minimum chilled water flow units without hydraulic module 18 6 3 Maximum chilled water flow units without hydrauli...

Page 4: ...maintenance see note 34 11 2 Level 2 maintenance see note 34 11 3 Level 3 or higher maintenance see note 34 11 4 Tightening torques for the main electrical connections 34 11 5 Tightening torques for...

Page 5: ...or ice These devices as well as the drain piping must not impair operation and not lead to a pressure drop that is higher than 10 of the control pressure Classification and control In accordance with...

Page 6: ...ed off the power circuit remains energized unless the unit or circuit disconnect switch is open Refer to the wiring diagram for further details Attach appropriate safety labels Units with option 231 a...

Page 7: ...f a leak occurs or if the refrigerant becomes contaminated e g by a short circuit in a motor remove the complete charge using a recovery unit and store the refrigerant in mobile containers Repair the...

Page 8: ...uit Do not attempt to repair or recondition any safety devices when corrosion or build up of foreign material rust dirt scale etc is found within the valve body or mechanism If necessary replace the d...

Page 9: ...e frequency number of phases Maximum current drawn Maximum power input Unit net weight Confirm that all accessories ordered for on site installation have been delivered and are complete and undamaged...

Page 10: ...than 15 WARNING Never push or lever on any of the enclosure panels of the unit Only the base of the unit frame is designed to withstand such stresses 2 2 3 Checks before system start up Before the st...

Page 11: ...ional drawings supplied with the unit or available on request For the positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings B...

Page 12: ...or evaporator tube removal Water inlet Water outlet Air outlet do not obstruct Power supply connection C Control circuit connection 3 4 Multiple chiller installation It is recommended to install multi...

Page 13: ...4798 4798 Width mm 2253 2253 2253 2253 2253 Height mm 2322 2322 2322 2322 2322 Operating weight 4 Standard unit kg 2375 2791 2847 3603 3689 Standard unit option 119 kg 3051 3167 3963 4119 Standard uni...

Page 14: ...15 7 15 7 15 7 Evaporator Flooded multi pipe type Water content l 53 53 53 75 75 Without hydraulic module Water inlet outlet connections Victaulic Nominal diameter in 5 5 5 5 5 Actual outside diamete...

Page 15: ...full load and nominal voltage 88 1 89 4 90 1 91 3 1 Nominal efficiency at 75 rated load and nominal voltage 88 88 9 89 7 91 4 1 Nominal efficiency at 50 rated load and nominal voltage 86 1 86 7 87 9 9...

Page 16: ...60364 Outdoor installation Ambient temperature range from 20 C to 55 C Altitude less than or equal to 2000 m for hydraulic module see paragraph 4 3 in the IOM Presence of hard solids class AE3 no sign...

Page 17: ...ter the control box from below or from the unit side For 30XAS unit sizes 282 to 482 the control box that includes the power supply cable connection terminal is located in the lower part of the unit I...

Page 18: ...peration 3 3 15 Note If the leaving water temperature is below 4 C a glycol water solution or the frost protection option must be used Condenser air temperature C Minimum Maximum Storage 20 68 Operati...

Page 19: ...chieve the required volume The tank must itself be internally baffled in order to ensure proper mixing of the liquid water or brine Refer to the examples below Connection to a buffer tank Bad Bad Good...

Page 20: ...e eletrolytic pairs and consequently corrosion Verify then the need to install sacrificial anodes In case additives or other fluids than those recommended by Carrier are used ensure that the fluids ar...

Page 21: ...lable pressure pump 5 Drain valve 6 Flow control valve 7 Evaporator 8 Evaporator defrost heater option 9 Hydraulic module defrost heater option 10 Air vent evaporator 11 Water drain evaporator 12 Expa...

Page 22: ...in the operating limit table application data 7 5 2 Optional evaporator frost protection 30XAS If it is not possible to apply the recommendations in para graph 7 5 1 the units can be equipped with hea...

Page 23: ...0 350 400 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 282 3 50 100 150 200 250 300 350 400 5 7 9 11 13 15 17 19 21 23 25 27 29 31 342 442 482 7 7 2 NPSH Net Positive Suction Head required option 116C hyd...

Page 24: ...installed but supplied with the unit The sealing joints are in the control box The temperature sensors and the condenser flow switch are wired and fixed in the machine They must be installed as descri...

Page 25: ...r 8 4 Condenser water connections NOTE Drawings are not contractually binding Before designing an installation consult the certified dimensional drawings supplied with the unit or available on request...

Page 26: ...temperature at start up 12 5 1 55 Water entering temperature during operation 20 55 Water leaving temperature during operation 25 60 Evaporator water temperature C Minimum Maximum Water entering temp...

Page 27: ...eat exchange at the air condenser to heat exchange at the water condenser and vice versa is ensured by motorised two way valves located upstream of the air and water condensers ATTENTION Mode changes...

Page 28: ...eat exchange fluid check and carry out internal inspections as described in EN 378 annex C In case of re testing please refer to the maximum operating pressure given on the unit nameplate The reports...

Page 29: ...6 mm Insert this tool into the opening on the pressure switch and push the reset button in this location These pressure switches are located at the discharge of each compressor 9 3 2 Relief valves 30X...

Page 30: ...n insufficient charge or non con densables in the system The presence of moisture changes the colour of the indicator paper in the sight glass 9 8 Filter drier The role of the filter drier is to keep...

Page 31: ...t 1 2 3 4 1 2 4 5 3 1 2 4 5 3 1 2 5 6 3 6 7 4 1 2 5 6 3 7 4 8 x x Start up order Power connection NOTE The values above do not correspond to the fan designation The fan designation and position are gi...

Page 32: ...ified service and maintenance 30XAS 242 482 Compressor discharge valves 93A Shut off valve on the compressor discharge piping Simplified maintenance 30XAS 242 482 HP dual pump hydraulic module 116C Co...

Page 33: ...corrosive environments 30XAS 242 482 Super Enviro Shield anti corrosion protection 263 Extremely durable and flexible epoxy polymer coating applied on micro channel heat exchangers by electro coating...

Page 34: ...replace the mountings Check the water connections Purge the water circuit see chapter Water flow control procedure Clean the water filter see chapter Water flow control procedure Fully clean the conde...

Page 35: ...with clean water For coils installed in a coastal or industrial environment periodical cleaning by rinsing with water is beneficial It is however essential that rinsing is done with a low speed water...

Page 36: ...mpressor terminal pin as originally wired For replacement of the compressor a low pressure switch is included with the compressor This low pressure switch should be temporarily installed as a hard saf...

Page 37: ...of the unit can be recycled for another purpose 12 3 Fluids to be recovered for treatment Refrigerant Heat transfer fluid depending on the installation water brine solution etc Compressor oil 12 4 Ma...

Page 38: ...otection has been sized and installed properly All terminals are tight All chilled water valves are open All chilled water piping is connected properly All air has been vented from the chilled water c...

Page 39: ...y supply at once and ensure that the chiller is not switched on until corrective measures have been taken Check cooler water loop Water loop volume litres Calculated volume litres 3 25 litres nominal...

Page 40: ...alidity of certificate www eurovent certification com Order No 13467 09 2018 Supersedes order No 13467 12 2016 Manufactured by Carrier SCS Montluel France Manufacturer reserves the right to change any...

Reviews: