32
Table 26 — Fan Performance 50HJQ007 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
LEGEND
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
NOTES:
1.
Boldface
indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils. See
Table 8 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.9 and the maximum continuous
watts are 2615. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized
with confidence. Using your fan motors up to the wattage rat-
ings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. See Tables 6
and 7 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
821
0.51
700
923
0.65
835
1019
0.81
956
1099
0.96
1031
1178
1.14
1165
1900
854
0.58
779
953
0.73
932
1046
0.90
1006
1126
1.06
1114
1201
1.23
1233
2000
888
0.66
867
984
0.82
1014
1073
0.99
1097
1154
1.16
1216
1226
1.33
1284
2100
923
0.75
998
1015
0.91
1064
1101
1.08
1140
1182
1.27
1292
1252
1.45
1404
2200
958
0.85
1081
1046
1.01
1106
1129
1.19
1258
1209
1.39
1361
1280
1.58
1508
2300
993
0.96
1140
1079
1.13
1224
1160
1.31
1387
1237
1.51
1473
1309
1.71
1648
2400
1029
1.07
1224
1112
1.25
1396
1190
1.43
1447
1264
1.63
1630
1336
1.85
1726
2500
1066
1.20
1335
1145
1.39
1465
1220
1.57
1552
1292
1.77
1761
1363
2.00
1805
2600
1103
1.34
1482
1179
1.52
1560
1251
1.71
1735
1322
1.92
1858
1390
2.15
1936
2700
1140
1.48
1595
1212
1.67
1726
1283
1.87
1892
1352
2.09
1954
1418
2.31
2171
2800
1177
1.64
1639
1246
1.83
1875
1316
2.04
1989
1383
2.26
2136
1446
2.48
2343
2900
1215
1.81
1814
1281
2.00
2050
1349
2.22
2240
1413
2.44
2300
1476
2.67
2521
3000
1253
2.00
2032
1316
2.19
2119
1382
2.42
2343
1444
2.63
2470
1506
2.88
2648
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
1249
1.32
1250
1316
1.52
1378
1382
1.72
1404
1427
1.89
1564
1468
2.06
1704
1900
1274
1.43
1361
1338
1.62
1439
1402
1.83
1482
1447
2.01
1653
1489
2.19
1801
2000
1297
1.53
1473
1363
1.73
1491
1424
1.94
1569
1470
2.13
1752
1512
2.32
1909
2100
1320
1.64
1552
1388
1.85
1534
1448
2.07
1700
1495
2.28
1901
1538
2.48
2070
2200
1345
1.77
1604
1410
1.97
1639
1473
2.20
1831
1521
2.42
2049
1564
2.64
2232
2300
1372
1.91
1665
1434
2.11
1831
1496
2.34
1980
1544
2.57
2218
1589
2.80
2415
2400
1400
2.06
1823
1459
2.26
1980
1519
2.48
2136
1568
2.73
2396
1613
2.97
2609
2500
1428
2.22
1980
1486
2.43
2136
1543
2.65
2292
1593
2.92
2574
1639
3.17
2804
2600
1456
2.38
2119
1514
2.61
2317
1569
2.83
2462
1620
3.11
2772
1666
3.39
3019
2700
1483
2.56
2300
1543
2.80
2487
—
—
—
—
—
—
—
—
—
2800
1510
2.73
2504
—
—
—
—
—
—
—
—
—
—
—
—
2900
1537
2.92
2725
—
—
—
—
—
—
—
—
—
—
—
—
3000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Bhp
—
Brake Horsepower Input to Fan
FIOP —
Factory-Installed Option
Watts —
Input Watts to Motor