![Carrier 50HJQ004-007 Installation, Start-Up And Service Instructions Manual Download Page 22](http://html.mh-extra.com/html/carrier/50hjq004-007/50hjq004-007_installation-start-up-and-service-instructions-manual_2563306022.webp)
22
Table 12 — Fan Performance 50HJQ005 — Vertical Discharge Units; Standard Motor (Belt Drive)*
LEGEND
*Motor drive range: 840 to 1185 rpm. All other rpms require field-
supplied drive.
NOTES:
1.
Boldface
indicates field-supplied motor drive is required.
2.
indicates field-supplied motor and drive are required.
3. Maximum usable watts input is 1000 and maximum continuous
bhp is 1.20. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized
with confidence. Using your fan motors up to the wattage rat-
ings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. For additional
information on motor performance, refer to Tables 6 and 7.
4. Values include losses for filters, unit casing, and wet coils. See
Table 8 for accessory/FIOP static pressure information.
5. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
Table 13 — Fan Performance 50HJQ005 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
LEGEND
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-
supplied drive.
NOTES:
1.
Boldface
indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casings, and wet coils. See
Table 8 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.4 and the maximum continuous
watts are 2120. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings
shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Tables 6 and 7.
5. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.1
0.2
0.3
0.4
0.6
0.7
0.8
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1200
542 0.16
168
616 0.21
221
678 0.27
278
739 0.32
336
842 0.44
462
886 0.50
525
929 0.56
588
1300
576 0.20
210
644 0.25
263
704 0.31
326
764 0.37
389
867 0.50
525
910 0.56
588
952 0.62
651
1400
610 0.24
252
673 0.30
315
732 0.36
378
791 0.42
441
889 0.55
578
933 0.62
651
976 0.69
725
1500
646 0.28
294
704 0.35
368
761 0.42
436
818 0.48
504
912 0.61
641
957 0.69
720 1001 0.76
777
1600
681 0.33
347
735 0.40
420
790 0.47
494
845 0.54
567
920 0.68
695
931 0.76
772 1023 0.83
848
1700
718 0.39
410
768 0.46
483
836 0.54
562
873 0.61
641
965 0.76
777 1005 0.84
853 1045 0.91
930
1800
754 0.45
473
801 0.53
557
851 0.61
641
900 0.69
725
992 0.84
858 1032 0.92
940 1071 1.00 1022
1900
791 0.52
546
836 0.60
630
832 0.69
720
828 0.77
809
1019 0.93
950 1058 1.02 1037 1097 1.10 1124
2000
828 0.60
630
870 0.68
714
864 0.77
809
858 0.86
904
1046 1.03 1053 1085 1.12 1139 1124 1.21 1237
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.0
1.1
1.2
1.4
1.6
1.8
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1200
1008 0.67
704 1052 0.73
762 1096 0.78
820 1134 0.89
835
1203 1.00
885
—
—
—
1300
1029 0.75
788 1065 0.81
846 1101 0.86
904 1174 1.01 1040 1229 1.15 1100 1277 1.27 1029
1400
1052 0.83
826 1087 0.90
890 1121 0.96
918 1183 1.09 1042 1255 1.22 1167 1305 1.38 1190
1500
1076 0.91
905 1111 0.99
980 1145 1.06 1014 1208 1.20 1138 1274 1.33 1272 1337 1.47 1350
1600
1100 1.00
995 1134 1.08 1069 1168 1.15 1100 1232 1.31 1253 1291 1.46 1396 1350 1.60 1558
1700
1124 1.09 1084 1158 1.17 1164 1192 1.25 1196 1255 1.42 1358 1314 1.58 1511 1370 1.77 1738
1800
1147 1.18 1174 1182 1.27 1263 1217 1.36 1301 1279 1.54 1473 1381 1.71 1635 1393 1.89 1907
1900
1169 1.27 1263 1205 1.37 1363 1240 1.47 1406 1303 1.66 1588 1408 1.85 1769 1417 2.03 2068
2000
1194 1.38 1373 1228 1.48 1472 1262 1.58 1511 1327 1.78 1702 1436 1.98 1894 1440 2.18 2229
Bhp
—
Brake Horsepower Input to Fan
FIOP
—
Factory-Installed Option
Watts —
Input Watts to Motor
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1200
618
0.21
263
739
0.32
378
842
0.44
504
928
0.56
630
1008
0.67
725
1300
644
0.25
315
764
0.37
441
867
0.50
578
952
0.62
704
1029
0.75
841
1400
673
0.30
378
791
0.42
504
889
0.55
651
976
0.69
788
1052
0.83
885
1500
704
0.35
441
818
0.48
578
912
0.61
725
1001
0.76
858
1076
0.91
985
1600
736
0.40
515
845
0.54
662
920
0.68
787
1023
0.83
950
1100
1.00
1084
1700
768
0.46
599
873
0.81
757
965
0.76
889
1045
0.91
1063
1124
1.09
1194
1800
801
0.52
693
900
0.69
851
892
0.84
991
1071
1.00
1165
1147
1.18
1313
1900
836
0.60
788
928
0.77
967
1019
0.93
1104
1097
1.10
1277
1169
1.27
1442
2000
870
0.68
904
968
0.86
1082
1046
1.03
1237
1124
1.21
1410
1194
1.38
1572
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1200
1096
0.78
778
1134
0.89
935
1203
1.00
965
1232
1.07
1000
1258
1.14
1083
1300
1101
0.86
935
1174
1.01
988
1229
1.15
999
1277
1.27
1029
1304
1.35
1203
1400
1121
0.96
976
1183
1.09
1071
1255
1.22
1105
1305
1.38
1190
1333
1.47
1367
1500
1145
1.06
1081
1208
1.20
1215
1274
1.33
1294
1337
1.47
1350
1365
1.57
1564
1600
1168
1.15
1196
1232
1.31
1339
1291
1.46
1454
1350
1.60
1558
1379
1.70
1805
1700
1192
1.25
1310
1255
1.42
1463
1314
1.58
1605
1370
1.77
1738
1399
1.89
2013
1800
1217
1.36
1425
1279
1.54
1597
1381
1.71
1757
1383
1.89
1907
1423
2.01
2210
1900
1240
1.47
1559
1303
1.66
1731
1408
1.85
1889
1417
2.03
2068
1447
2.16
2375
2000
1262
1.58
1702
1372
1.78
1884
1436
1.98
2040
1440
2.18
2229
1471
2.32
2551
Bhp
—
Brake Horsepower Input to Fan
FIOP
—
Factory-Installed Option
Watts —
Input Watts to Motor