![Carrier 50HJQ004-007 Installation, Start-Up And Service Instructions Manual Download Page 24](http://html.mh-extra.com/html/carrier/50hjq004-007/50hjq004-007_installation-start-up-and-service-instructions-manual_2563306024.webp)
24
Table 16 — Fan Performance 50HJQ006 — Vertical Discharge Units; High-Static Motor (Belt Drive)
LEGEND
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
NOTES:
1.
Boldface
indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casings, and wet coils.
See Table 8 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.9 and the maximum continuous
watts are 2615. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized
with confidence. Using your fan motors up to the wattage rat-
ings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. See Tables 6
and 7 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1500
789
0.40
429
896
0.53
572
990
0.67
705
1072
0.83
869
1153
1.00
1032
1600
826
0.46
501
931
0.61
645
1020
0.75
797
1101
0.91
961
1178
1.09
1134
1700
865
0.54
582
966
0.69
736
1051
0.84
899
1133
1.01
1053
1206
1.18
1237
1800
905
0.62
674
1002
0.78
838
1084
0.93
1001
1163
1.10
1155
1235
1.29
1349
1900
946
0.72
777
1037
0.88
940
1119
1.04
1124
1194
1.21
1288
1266
1.40
1461
2000
984
0.82
889
1072
0.98
1063
1154
1.16
1247
1226
1.33
1431
1297
1.53
1604
2100
1024
0.93
1012
1108
1.10
1196
1192
1.29
1380
1259
1.47
1574
1327
1.66
1758
2200
1064
1.05
1145
1145
1.22
1328
1225
1.43
1523
1294
1.62
1737
1359
1.80
1931
2300
1104
1.18
1288
1183
1.36
1502
1260
1.57
1686
1330
1.78
1901
1392
1.97
2115
2400
1145
1.32
1441
1222
1.45
1645
1296
1.73
1860
1365
1.94
2074
1426
2.15
2310
2500
1186
1.48
1604
1262
1.68
1819
1331
1.80
2044
1400
2.12
2269
1461
2.34
2504
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1500
1221
1.17
1216
1256
1.30
1492
1280
1.32
1757
1320
1.22
1944
1360
1.33
2164
1600
1252
1.27
1308
1311
1.45
1523
1340
1.58
1800
1380
1.61
2047
1421
1.76
2280
1700
1278
1.37
1420
1345
1.57
1615
1397
1.76
1850
1424
1.89
2070
1467
2.06
2305
1800
1303
1.48
1553
1371
1.69
1747
1433
1.90
1952
1480
2.09
2197
1524
2.28
2446
1900
1330
1.59
1676
1396
1.80
1891
1460
2.03
2095
1517
2.25
2358
1562
2.46
2625
2000
1362
1.73
1809
1422
1.94
2034
1485
2.16
2258
1544
2.40
2542
1590
2.62
2830
2100
1393
1.80
1952
1452
2.08
2167
1510
2.31
2501
1569
2.55
2821
1616
2.79
3141
2200
1423
2.02
2126
1483
2.24
2350
1538
2.46
2688
1595
2.71
3031
1643
2.96
3375
2300
1454
2.18
2310
1515
2.41
2698
1569
2.64
3091
1622
2.88
3486
1671
3.15
3881
2400
1485
2.36
2524
1544
2.59
2948
1601
2.84
3379
1652
3.07
3715
—
—
—
2500
1518
2.55
3010
1575
2.78
3522
1631
3.03
4036
1684
3.28
3970
—
—
—
Bhp
—
Brake Horsepower Input to Fan
FIOP
—
Factory-Installed Option
Watts —
Input Watts to Motor
Summary of Contents for 50HJQ004-007
Page 42: ...42 Fig 43 Typical Wiring Schematic 50HJQ006 007 Shown ...
Page 43: ...43 Fig 43 Typical Wiring Schematic 50HJQ006 007 Shown cont ...
Page 45: ......
Page 47: ......