Table 24 — Fan Performance 50HJQ006 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
LEGEND
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
NOTES:
1.
Boldface
indicates field-supplied drive is required.
2.
indicates field-supplied motor is required.
3. Values include losses for filters, unit casing, and wet coils. See
Table 8 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.9 and the maximum continuous
watts are 2615. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized
with confidence. Using your fan motors up to the wattage rat-
ings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. See Tables 6
and 7 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1500
722
0.33
420
840
0.46
557
937
0.59
704
1027
0.74
872
1108
0.90
1051
1600
754
0.38
483
867
0.52
641
963
0.65
788
1052
0.81
956
1130
0.97
1145
1700
787
0.44
567
895
0.58
725
991
0.73
883
1075
0.88
1061
1154
1.06
1240
1800
821
0.51
661
923
0.65
820
1019
0.81
977
1099
0.96
1156
1178
1.14
1355
1900
854
0.58
757
953
0.73
925
1046
0.90
1093
1126
1.06
1271
1201
1.23
1471
2000
900
0.66
862
984
0.82
1030
1073
0.99
1219
1154
1.16
1397
1226
1.33
1608
2100
923
0.75
977
1015
0.91
1156
1101
1.08
1355
1182
1.27
1545
1252
1.45
1744
2200
958
0.85
1103
1046
1.01
1282
1129
1.19
1503
1209
1.39
1702
1280
1.58
1902
2300
993
0.96
1240
1079
1.13
1429
1160
1.31
1650
1237
1.51
1870
1309
1.71
2070
2400
1029
1.07
1387
1112
1.25
1524
1190
1.43
1818
1264
1.63
2038
1336
1.80
2259
2500
1066
1.20
1555
1145
1.39
1765
1220
1.57
1986
1292
1.77
2227
1363
2.00
2459
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1500
1186
1.08
1229
1263
1.30
1366
1343
1.58
1387
1431
1.79
1282
1480
1.98
1390
1600
1205
1.15
1334
1278
1.35
1524
1350
1.61
1660
1424
1.80
1692
1473
1.99
1834
1700
1226
1.23
1439
1296
1.42
1650
1364
1.64
1849
1432
1.89
1986
1481
2.09
2153
1800
1249
1.32
1555
1316
1.52
1776
1382
1.72
1996
1447
1.95
2196
1497
2.16
2381
1900
1274
1.43
1671
1338
1.62
1902
1402
1.80
2133
1464
2.05
2364
1514
2.27
2563
2000
1297
1.53
1818
1363
1.73
2038
1424
1.94
2270
1484
2.16
2522
1535
2.39
2734
2100
1320
1.64
1965
1388
1.80
2185
1448
2.07
2427
1505
2.29
2674
1557
2.53
2905
2200
1345
1.77
2122
1410
1.97
2354
1473
2.20
2585
1529
2.43
2821
1581
2.69
3087
2300
1372
1.91
2291
1434
2.11
2532
1496
2.34
2758
1554
2.58
2976
1607
2.85
3280
2400
1400
2.06
2480
1459
2.26
2721
1519
2.48
2947
1578
2.76
3152
1632
3.05
3497
2500
1428
2.22
2679
1486
2.43
2905
1543
2.65
3134
1600
2.89
3345
1655
3.20
3736
Bhp
—
Brake Horsepower Input to Fan
FIOP —
Factory-Installed Option
Watts —
Input Watts to Motor
Summary of Contents for 50HJQ004-007
Page 42: ...42 Fig 43 Typical Wiring Schematic 50HJQ006 007 Shown ...
Page 43: ...43 Fig 43 Typical Wiring Schematic 50HJQ006 007 Shown cont ...
Page 45: ......