Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480268-01
Printed in U.S.A.
Form 48TC-17-30-V-05SI
Pg 1
8-19
Replaces: 48TC-17-30-V-04SI
Installation Instructions
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Rated Indoor Airflow (cfm) . . . . . . . . . . . . . . . . . . . . . 3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Job-Site Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Step 1 — Plan for Unit Location . . . . . . . . . . . . . . . . 17
Step 2 — Plan for Sequence of Unit Installation . . . 17
• ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR
Step 7 — Install Outside Air Hood (Factory-
Option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Step 8 — Install Flue Hood and Combustion Air
Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Step 9 — Install Gas Piping. . . . . . . . . . . . . . . . . . . . 24
• FACTORY-OPTION THRU-BASE CONNECTIONS
Step 10 — Install External Condensate Trap and
Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Step 11 — Make Electrical Connections . . . . . . . . . 27
• UNITS WITH FACTORY-INSTALLED NON-FUSED
• UNITS WITH FACTORY-INSTALLED NON-FUSED
• TO FIELD INSTALL THE NFD SHAFT AND HANDLE:
Convenience Outlets . . . . . . . . . . . . . . . . . . . . . . . . . 29
• INSTALLING WEATHERPROOF COVER
• FACTORY-OPTION THRU-BASE CONNECTIONS
Humidi-MiZer® Control Connections . . . . . . . . . . . . 31
• HUMIDI-MIZER – SPACE RH CONTROLLER
EconoMi$er® X (Factory-Installed Option) . . . . . . . 33
• ECONOMIZER MODULE WIRING DETAILS
PremierLink™ Control . . . . . . . . . . . . . . . . . . . . . . . 46
RTU Open Control System. . . . . . . . . . . . . . . . . . . . 46
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
• RETURN AIR SENSOR TUBE INSTALLATION
Step 12 — Adjust Factory-Installed Options . . . . . 60
• ECONOMI$ER IV OCCUPANCY SWITCH
• BELT FORCE — DEFLECTION METHOD
Pre-Start and Start-Up . . . . . . . . . . . . . . . . . . . . . . . 61
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or
service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the litera-
ture, tags and labels attached to the unit, and other safety precau-
tions that may apply.
48TC units for installation in the United States contain use of Carrier's Staged Air Volume (SAV™) 2-
speed indoor fan control system. This complies with the U.S. Department of Energy (DOE) efficiency
standard of 2018.
48TC units for installation outside the United States may or may not contain use of the SAV 2-speed
indoor fan control system as they are not required to comply with the U.S. Department of Energy
(DOE) efficiency standard of 2018.
For specific details on operation of the Carrier SAV 2-speed indoor fan system refer to the Variable
Frequency Drive (VFD) Factory-Installed Option 2-Speed Motor Control Installation, Setup, and
Troubleshooting manual.
WeatherMaker
®
48TC 17-30
Single Package Rooftop with Gas Heat/Electric Cooling
Vertical Air Flow Unit with Puron
®
(R-410A) Refrigerant
Summary of Contents for 48TC D/E17 Series
Page 5: ...5 Fig 2 48TC 17 20 Vertical Airflow...
Page 6: ...6 Fig 3 48TC 17 20 Back View and Condensate Drain Location...
Page 7: ...7 Fig 4 48TC 17 20 Corner Weights and Clearances...
Page 8: ...8 Fig 5 48TC 17 20 Bottom View...
Page 9: ...9 Fig 6 48TC 24 28 Vertical Airflow...
Page 10: ...10 Fig 7 48TC 24 28 Back View and Condensate Drain Location...
Page 11: ...11 Fig 8 48TC 24 28 Corner Weights and Clearances...
Page 12: ...12 Fig 9 48TC 24 28 Bottom View...
Page 13: ...13 Fig 10 48TC 30 Vertical Airflow...
Page 14: ...14 Fig 11 48TC 30 Back View and Condensate Drain Location...
Page 15: ...15 Fig 12 48TC 30 Corner Weights and Clearances...
Page 16: ...16 Fig 13 48TC 30 Bottom View...
Page 19: ...19 Fig 16 Roof Curb Details 17 and 20 Size Units...
Page 20: ...20 Fig 17 Roof Curb Details 24 and 28 Size Units...
Page 21: ...21 Fig 18 Roof Curb Details 30 Size Units...
Page 47: ...47 Fig 52 PremierLink Wiring Diagram...
Page 48: ...48 Fig 53 PremierLink Wiring Diagram with Humidi MiZer System...
Page 49: ...49 Fig 54 Typical RTU Open System Control Wiring Diagram...
Page 50: ...50 Fig 55 Typical RTU Open System Control Wiring Diagram with Humidi MiZer System...
Page 51: ...51 Fig 56 48TC 17 30 Control Wiring Diagram...
Page 52: ...52 Fig 57 48TC 17 30 Power Wiring Diagram 208 230 3 60...
Page 53: ...53 Fig 58 48TC 17 30 Power Wiring Diagram 460 3 60...
Page 54: ...54 Fig 59 48TC 17 30 Power Wiring Diagram 575 3 60...
Page 55: ...55 Fig 60 48TC 17 30 Control Wiring Diagram with Humidi MiZer System...
Page 56: ...56 Fig 61 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 208 230 3 60...
Page 57: ...57 Fig 62 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 460 3 60...
Page 58: ...58 Fig 63 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 575 3 60...