
29
Example: Supply voltage is 230-3-60
Determine maximum deviation from average voltage.
(AB) 227-224 = 3 v
(BC) 231-227 = 4 v
(AC) 227-226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
NOTE: Check all factory and field electrical connections for tightness.
Fig. 35 — Power Wiring Connections
Convenience Outlets
Two types of convenience outlets are offered on 48TC models:
non-unit powered and unit-powered. Both types provide a 125-v
GFCI (ground-fault circuit-interrupter) duplex receptacle rated at
15-A behind a hinged access cover, located on the corner panel of
the unit. See Fig. 36.
Fig. 36 — Convenience Outlet Location
INSTALLING WEATHERPROOF COVER
A weatherproof while-in-use cover for the factory-installed conve-
nience outlets is now required by UL standards. This cover cannot
be factory-mounted due to its depth; it must be installed at unit in-
stallation. For shipment, the convenience outlet is covered with a
blank cover plate.
The weatherproof cover kit is shipped in the unit’s control box.
The kit includes the hinged cover, a backing plate and gasket.
Disconnect all power to unit and convenience outlet. Lock-out
and tag-out all power.
Remove the blank cover plate at the convenience outlet; discard
the blank cover.
Loosen the two screws at the GFCI duplex outlet, until approxi-
mately
1
/
2
in. (13 mm) under screw heads are exposed. Press the
gasket over the screw heads. Slip the backing plate over the screw
heads at the keyhole slots and align with the gasket; tighten the
two screws until snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as shown in
Fig. 37. Remove two slot fillers in the bottom of the cover to per-
mit service tool cords to exit the cover. Check for full closing and
latching.
Fig. 37 — Weatherproof Cover Installation
Non-powered type
Requires the field installation of a general-purpose 125-v 15-A
circuit powered from a source elsewhere in the building. Ob-
serve national and local codes when selecting wire size, fuse or
breaker requirements and disconnect switch size and location.
Route 125-v power supply conductors into the bottom of the
utility box containing the duplex receptacle.
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage
=
(224 + 231 + 226)
=
681
= 227
3
3
% Voltage Imbalance = 100x
4
= 1.78%
227
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Operation on improper line voltage or excessive phase imbal-
ance constitutes abuse and may cause damage to electrical
components. Such operation would invalidate any applicable
Carrier warranty.
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or
death.
Units with convenience outlet circuits may use multiple
disconnects. Check convenience outlet for power status before
opening unit for service. Locate its disconnect switch, if
appropriate, and open it. Lock-out and tag-out this switch, if
necessary.
A
B
C
MOTOR
11
1
3
L1
L2
L
3
GROUND
(GR)
TB1
20
8
/2
3
0-
3
-60
460-
3
-60
575-
3
-60
T1
T2
T
3
L1
L2
L
3
L1
L2
L
3
FACTORY
WIRING
DI
S
CONNECT
PER NEC
OPTIONAL
DI
S
CONNECT
S
WITCH
12
EQUIP
GR LUG
GROUND
(GR)
EQUIP
GR LUG
UNIT
S
WITHOUT DI
S
CONNECT OPTION
UNIT
S
WITH DI
S
CONNECT OPTION
CONVENIENCE
OUTLET
ELECTRIC
DISCONNECT
SWITCH
CONTROL BOX
ACCESS PANEL
COVER - WHILE-IN-U
S
E
WEATHERPROOF
BA
S
EPLATE FOR
GFCI RECEPTACLE
GA
S
KET
GFCI RECEPTACLE
NOT INCLUDED
TOP
TO
P
TOP
WET LOC
ATIONS
W
ET
L
OC
ATI
ON
S
Summary of Contents for 48TC D/E17 Series
Page 5: ...5 Fig 2 48TC 17 20 Vertical Airflow...
Page 6: ...6 Fig 3 48TC 17 20 Back View and Condensate Drain Location...
Page 7: ...7 Fig 4 48TC 17 20 Corner Weights and Clearances...
Page 8: ...8 Fig 5 48TC 17 20 Bottom View...
Page 9: ...9 Fig 6 48TC 24 28 Vertical Airflow...
Page 10: ...10 Fig 7 48TC 24 28 Back View and Condensate Drain Location...
Page 11: ...11 Fig 8 48TC 24 28 Corner Weights and Clearances...
Page 12: ...12 Fig 9 48TC 24 28 Bottom View...
Page 13: ...13 Fig 10 48TC 30 Vertical Airflow...
Page 14: ...14 Fig 11 48TC 30 Back View and Condensate Drain Location...
Page 15: ...15 Fig 12 48TC 30 Corner Weights and Clearances...
Page 16: ...16 Fig 13 48TC 30 Bottom View...
Page 19: ...19 Fig 16 Roof Curb Details 17 and 20 Size Units...
Page 20: ...20 Fig 17 Roof Curb Details 24 and 28 Size Units...
Page 21: ...21 Fig 18 Roof Curb Details 30 Size Units...
Page 47: ...47 Fig 52 PremierLink Wiring Diagram...
Page 48: ...48 Fig 53 PremierLink Wiring Diagram with Humidi MiZer System...
Page 49: ...49 Fig 54 Typical RTU Open System Control Wiring Diagram...
Page 50: ...50 Fig 55 Typical RTU Open System Control Wiring Diagram with Humidi MiZer System...
Page 51: ...51 Fig 56 48TC 17 30 Control Wiring Diagram...
Page 52: ...52 Fig 57 48TC 17 30 Power Wiring Diagram 208 230 3 60...
Page 53: ...53 Fig 58 48TC 17 30 Power Wiring Diagram 460 3 60...
Page 54: ...54 Fig 59 48TC 17 30 Power Wiring Diagram 575 3 60...
Page 55: ...55 Fig 60 48TC 17 30 Control Wiring Diagram with Humidi MiZer System...
Page 56: ...56 Fig 61 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 208 230 3 60...
Page 57: ...57 Fig 62 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 460 3 60...
Page 58: ...58 Fig 63 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 575 3 60...