background image

30

Unit-powered type

A unit-mounted transformer which is factory-installed to step-

down the main power supply voltage to the unit to 115-v at the du-

plex receptacle. This option also includes a manual switch with

fuse, located in a utility box and mounted on a bracket behind the

convenience outlet; access is through the unit’s control box access

panel. See Fig. 38.
The primary leads to the convenience outlet transformer are not

factory-connected. If local codes permit, the transformer primary

leads can be connected at the line-side terminals on the unit-

mounted non-fused disconnect switch; this will provide service

power to the unit when the unit disconnect switch is open. See

Fig. 38. See Fig. 39 for convenience outlet utilization precautions.

Fig. 38 — Powered Convenience Outlet Wiring

.

Fig. 39 — Convenience Outlet Utilization Notice

Test the GFCI receptacle by pressing the TEST button on the face

of the receptacle to trip and open the receptacle. Check for proper

grounding wires and power line phasing if the GFCI receptacle

does not trip as required. Press the RESET button to clear the

tripped condition.

Using unit-mounted convenience outlets: Units with unit-mounted

convenience outlet circuits will often require that two disconnects

be opened to de-energize all power to the unit. Treat all units as

electrically energized until the convenience outlet power is also

checked and de-energization is confirmed. Observe National Elec-

trical Code Article 210, Branch Circuits, for use of convenience

outlets.
FACTORY-OPTION THRU-BASE CONNECTIONS (ELEC-

TRICAL CONNECTIONS) 
All units are equipped with the ability to bring utilities through the

base.
Gas is brought up through an embossed area located in the gas

section behind the gas entrance post. Access is gained through the

gas access panel. A knock out must be removed to accomplish

this.
The electrical entrance is located in the control box area and can

be accessed through the control box access panel. An embossed

area is provided with three knock outs. High voltage is brought

through the multi knock out by removing the appropriate size for

the size of the fitting required. A 

7

/

8

-in. knock out is provided for

low voltage. An additional 

7

/

8

-in. knock out is provided for a 115

volt line which is used when the unit is equipped with the non-unit

powered convenience outlet option.
All required fittings are field supplied. Install fittings when access

to both top and bottom of the base pan is available. See electrical

and gas connections for routing and connection information.

Units Without Thru-Base Connections

1. Install liquid tight conduit between disconnect and control

box.

2. Pull correctly rated high voltage wires through the conduit.
3. Install power lines to terminal connections as shown in

Fig. 35.

Field Control Wiring

The 48TC unit requires an external temperature control device.

This device can be a thermostat (field-supplied) or a PremierLink

controller (available as factory-installed option or as field-installed

accessory, for use on a Carrier Comfort Network or as a stand

alone control) or the RTU Open for Building Management Sys-

tems using non-CCN protocols (RTU Open is available as a facto-

ry-installed option only).

Thermostat

Install a Carrier-approved accessory 2-stage thermostat according

to installation instructions included with the accessory. Locate the

thermostat accessory on a solid wall in the conditioned space to

sense average temperature in accordance with the thermostat in-

stallation instructions.
If the thermostat contains a logic circuit requiring 24-v power, use

a thermostat cable or equivalent single leads of different colors

with minimum of seven leads. If the thermostat does not require a

24-v source (no “C” connection required), use a thermostat cable

or equivalent with minimum of six leads. Check the thermostat in-

stallation instructions for additional features which might require

additional conductors in the cable.
For wire runs up to 50 ft (15 m), use no. 18 AWG (American Wire

Gage) insulated wire (35°C minimum). For 50 to 75 ft (15 to

23 m), use no. 16 AWG insulated wire (35°C minimum). For over

75 ft (23 m), use no. 14 AWG insulated wire (35°C minimum). All

wire sizes larger than no. 18 AWG cannot be directly connected to

the thermostat and will require a junction box and splice at the

thermostat.

Unit Without Thru-Base Connection Kit

Correctly rated low voltage wire can be routed through the rubber

grommet located on the corner post adjacent to the control box ac-

cess panel. Route wire through the grommet and then route the

wire behind the corner post utilizing the factory provided wire ties

secured to the control box. This will ensure separation of the field

UNIT 

VOLTAGE

CONNECT

AS

PRIMARY

CONNECTIONS

TRANSFORMER 

TERMINALS

208, 230

240

L1: RED+YEL
L2: BLU+GRA

H1+H3
H2+H4

460

480

L1: RED
Splice BLU+YEL
L2: GRA

H1

H2+H3

H4

575

600

L1: RED
L2: GRA

H1
H2

2.0

50HE501288

NOTICE/AVIS

Convenience Outlet Utilization

Maximum Intermittent Use  15 - Amps

Maximum Continuous Use  8 - Amps

Observe a 50% limit on the circuit

Loading above  8 - Amps

Utilisation de la prise utilitaire

Usage intermittent maximum  15 - Amps

Usage continu maximum  8 - Amps

Observez une limite de 50% sur le circuit

Chargement au-dessus de  8 - Amps

Summary of Contents for 48TC D/E17 Series

Page 1: ...SCREENSAVER ENTHALPY SETTINGS TWO SPEED FAN OPERATION CHECKOUT TROUBLESHOOTING PremierLink Control 46 RTU Open Control System 46 Wiring Diagrams 46 Smoke Detectors 59 RETURN AIR SENSOR TUBE INSTALLAT...

Page 2: ...age and amperage listed on the unit rating plate Unit may have more than one power switch WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury death and...

Page 3: ...NOXYDE DE CARBONE Si ces directives ne sont pas suivies cela peut entra ner des blessures graves ou une intoxication au monoxyde de carbone pouvant causer la mort si des produits de combustion s infil...

Page 4: ...Hail Guard Q E coat Al Cu E coat Al Cu Louvered Hail Guard R Cu Cu Al Cu Louvered Hail Guard S Cu Cu Cu Cu Louvered Hail Guard Coil Options Novation Outdoor Indoor Hail Guard G Al Al Al Cu H Al Al Cu...

Page 5: ...5 Fig 2 48TC 17 20 Vertical Airflow...

Page 6: ...6 Fig 3 48TC 17 20 Back View and Condensate Drain Location...

Page 7: ...7 Fig 4 48TC 17 20 Corner Weights and Clearances...

Page 8: ...8 Fig 5 48TC 17 20 Bottom View...

Page 9: ...9 Fig 6 48TC 24 28 Vertical Airflow...

Page 10: ...10 Fig 7 48TC 24 28 Back View and Condensate Drain Location...

Page 11: ...11 Fig 8 48TC 24 28 Corner Weights and Clearances...

Page 12: ...12 Fig 9 48TC 24 28 Bottom View...

Page 13: ...13 Fig 10 48TC 30 Vertical Airflow...

Page 14: ...14 Fig 11 48TC 30 Back View and Condensate Drain Location...

Page 15: ...15 Fig 12 48TC 30 Corner Weights and Clearances...

Page 16: ...16 Fig 13 48TC 30 Bottom View...

Page 17: ...aced on the curb Review the following for rec ommended sequences for installation steps CURB MOUNTED INSTALLATION 1 Install curb 2 Install field fabricated ductwork inside curb 3 Install accessory thr...

Page 18: ...openings Fig 14 Unit Leveling Tolerances Fig 15 Typical Access Panel and Compressor Locations Table 2 Operating Weights A B 0 25 6 B C 0 5 12 A C 0 5 12 MAXIMUM ALLOWABLE DIFFERENCE IN MM A B C CONTR...

Page 19: ...19 Fig 16 Roof Curb Details 17 and 20 Size Units...

Page 20: ...20 Fig 17 Roof Curb Details 24 and 28 Size Units...

Page 21: ...21 Fig 18 Roof Curb Details 30 Size Units...

Page 22: ...on curb after unit is set Doing so will result in damage to the roof curb seal Although unit is weatherproof guard against water from higher level runoff and overhangs Flue vent discharge must have a...

Page 23: ...ms 4 and 5 to upper panel using the screws provided 6 Apply seal strip to mating flange of the hood see Fig 22 7 Secure hood item 3 to upper panel using the screws provided 8 Secure side retainers ite...

Page 24: ...uctions regarding these accessories NOTE Furnace gas input rate on rating plate is for installation up to 2000 ft 610 m above sea level The input rating for altitudes above 2000 ft 610 m must be derat...

Page 25: ...re drop of 0 5 in wg 124 Pa between gas regulator source and unit gas valve connec tion when unit is operating at high fire flow rate The gas supply line can approach the unit in two ways horizontal l...

Page 26: ...m gases as specified by local and or national codes If using PTFE Teflon tape ensure the material is Double Density type and is labeled for use on gas lines Apply tape per manufacturer s instructions...

Page 27: ...connect the source leads to the line side with unit field power leads See Fig 32 Fig 32 Location of TB1 Field power wires are connected to the unit at line side pressure lugs on the terminal block se...

Page 28: ...position 4 Measure the tip of the shaft to the outside surface of the cor ner post to be 0 88 in 5 Tighten the locking screw to secure the shaft to the NFD 6 Turn the handle to OFF position with red...

Page 29: ...37 Remove two slot fillers in the bottom of the cover to per mit service tool cords to exit the cover Check for full closing and latching Fig 37 Weatherproof Cover Installation Non powered type Requir...

Page 30: ...outing and connection information Units Without Thru Base Connections 1 Install liquid tight conduit between disconnect and control box 2 Pull correctly rated high voltage wires through the conduit 3...

Page 31: ...at HL38MG029 1 Route the humidistat 2 conductor cable field supplied through the hole provided in the unit corner post 2 Feed wires through the raceway built into the corner post see Fig 41 to the 24...

Page 32: ...32 Fig 42 Accessory Field Installed Humidistat Fig 43 Edge Pro Thermidistat Fig 44 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring RELATIVE HUMIDITY...

Page 33: ...re of the EconoMi er X system The module is mounted in the unit s control box and includes the user inter face for the system The W7220 economizer module provides the basic inputs and outputs to provi...

Page 34: ...osure to 40 F 40 C Storage Temperature 40 F to 150 F 40 C to 65 C Shipping Temperature 40 F to 150 F 40 C to 65 C Relative Humidity 5 to 95 RH non condensing ECONOMIZER MODULE WIRING DETAILS Use Fig 4...

Page 35: ...ypad on the front of the economizer controller KEYPAD The four navigation buttons see Fig 50 are used to scroll through the menus and menu items select menu items and to change parameter and configura...

Page 36: ...ame ters for the EconoMi er X system The Menus in display order are STATUS SETPOINTS SYSTEM SETUP ADVANCED SETUP CHECKOUT ALARMS NOTE Some parameters in the menus use the letters MA or MAT indicating...

Page 37: ...n Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40 F...

Page 38: ...Displays 2 to 10 V if 3 sensors RA OA and MA In AUTO mode dampers controlled by CFM 100 to 9990 cfm increment by 10 If OA MA RA and CO2 sensors are connected and DCV CAL ENABLE is set to AUTO mode the...

Page 39: ...factory default values NOTE RECHECK AUX2 IN and FANTYPE for required 2 speed values ADVANCED SETUP MA LO SET 45 F 35 F to 55 F 2 F to 13 F incremented by 10 F SUPPLY AIR TEMPERATURE LOW LIMIT Temperat...

Page 40: ...c out Issues a system alarm CONNECT EXH1 N A N A Closes the power exhaust fan 2 relay EXH1 ALARMS Alarms display only when they are active The menu title ALARMS includes the number of active alarms in...

Page 41: ...dry bulb and enthalpy operation with and without DCV see Tables 14 17 For 2 speed fan dry bulb and enthalpy operation with and without DCV see Tables 18 21 Table 13 Damper Minimum Position Settings a...

Page 42: ...4v On 0v Off MIN POS to Full Open Closed to Full Open DEMAND CONTROLLED VENTILATION DCV OUTSIDE AIR GOOD TO ECONOMIZE Y1 I Y2 I FAN SPEED Y1 O Y2 O OCCUPIED UNOCCUPIED Below CO2 Set No OFF OFF HIGH 0v...

Page 43: ...ed ON ON HIGH 24v On 24v On VENTMIN to VENTMAX Closed Yes OFF OFF HIGH 0v Off 0v Off VENTMIN to VENTMAX Closed ON OFF HIGH 0v Off 0v Off VENTMIN to Full Open Closed to Full Open ON ON HIGH 24v On 0v O...

Page 44: ...ff 0v Off MIN POS Closed ON OFF LOW 0v Off 0v Off MIN POS to Full Open Closed to Full Open ON ON HIGH 24v On 0v Off MIN POS to Full Open Closed to Full Open DEMAND CONTROLLED VENTILATION DCV OUTSIDE A...

Page 45: ...lled by the W7220 but it re quires the status to know where to position the OA damper for minimum position for the fan speed The 2 speed fan delay is available when the system is programmed for 2 spee...

Page 46: ...e alarms You can also navigate to the Alarms menu at any time Clearing Alarms Once the alarm has been identified and the cause has been re moved e g replaced faulty sensor the alarm can be cleared fro...

Page 47: ...47 Fig 52 PremierLink Wiring Diagram...

Page 48: ...48 Fig 53 PremierLink Wiring Diagram with Humidi MiZer System...

Page 49: ...49 Fig 54 Typical RTU Open System Control Wiring Diagram...

Page 50: ...50 Fig 55 Typical RTU Open System Control Wiring Diagram with Humidi MiZer System...

Page 51: ...51 Fig 56 48TC 17 30 Control Wiring Diagram...

Page 52: ...52 Fig 57 48TC 17 30 Power Wiring Diagram 208 230 3 60...

Page 53: ...53 Fig 58 48TC 17 30 Power Wiring Diagram 460 3 60...

Page 54: ...54 Fig 59 48TC 17 30 Power Wiring Diagram 575 3 60...

Page 55: ...55 Fig 60 48TC 17 30 Control Wiring Diagram with Humidi MiZer System...

Page 56: ...56 Fig 61 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 208 230 3 60...

Page 57: ...57 Fig 62 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 460 3 60...

Page 58: ...58 Fig 63 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 575 3 60...

Page 59: ...Sensor Location Fig 65 Return Air Sampling Tube Location in Unit without Economizer Fig 66 Return Air Sampling Tube Location in Unit with Economizer To install the return air sensor sampling tube 1 Re...

Page 60: ...Refer to separate installation instructions for information on in stalling these accessories Step 14 Check Belt Tension Measure the belt span length as shown in Fig 68 Calculate the re quired deflect...

Page 61: ...rom HVAC Partners www hvacpartners com Table 1 Table 2 BELT CROSS SECTION SMALLEST SHEAVE DIAMETER BELT DEFLECTION FORCE LBS UNNOTCHED BELTS NOTCHED BELTS USED NEW USED NEW A AX 3 0 3 6 3 7 5 5 4 1 6...

Page 62: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480268 01 Printed in U S A Form 48TC 17 30 V 05SI Pg 62 8 19 Replaces 48TC 1...

Page 63: ...door air filters are clean and in place Y N _____ Verify that unit installation is level Y N _____ Check fan wheels and propeller for location in housing orifice and setscrew tightness Y N _____ Check...

Page 64: ...scharge pressure _______________ PSIG C Entering air temperature _______________ F D Liquid line temperature at outlet or reheat coil _______________ F E Confirm correct rotation for compressor Y N __...

Reviews: