
45
Fig. 51 — Single Enthalpy Curve Boundaries
Table 22 — Single Enthalpy and Dual Enthalpy High Limit Curves
ENTHALPY SETTINGS
When the OA temperature, enthalpy and dew point are below the
respective setpoints, the Outdoor Air can be used for economiz-
ing. Figure 51 shows the new single enthalpy boundaries in the
W7220. There are 5 boundaries (setpoints ES1 through ES5),
which are defined by dry bulb temperature, enthalpy and dew
point.
Refer to Table 22 for ENTH CURVE setpoint values.
The W7220 calculates the enthalpy and dew point using the OA
temperature and humidity input from the OA enthalpy sensor.
When the OA temperature, OA humidity and OA dew point are
all below the selected boundary, the economizer sets the econo-
mizing mode to YES, economizing is available.
When all of the OA conditions are above the selected boundary,
the conditions are not good to economize and the mode is set to
NO.
Figure 51 shows the 5 current boundaries. There is also a high lim-
it boundary for differential enthalpy. The high limit boundary is
ES1 when there are no stages of mechanical cooling energized and
HL (high limit) when a compressor stage is energized.
Table 22 provides the values for each boundary limit.
TWO-SPEED FAN OPERATION
The W7220 controller has the capability to work with a system us-
ing a 2-speed supply fan. The W7220 does not control the supply
directly but uses the following input status to determine the speed
of the supply fan and controls the OA damper to the required posi-
tion, see Table 23.
Table 23 — Fan Speed
The W (heating mode) is not controlled by the W7220 but it re-
quires the status to know where to position the OA damper for
minimum position for the fan speed.
The 2 speed fan delay is available when the system is programmed
for 2 speed fan (in the System Setup menu item). The 2 speed fan
delay is defaulted to 5 minutes and can be changed in the Ad-
vanced Setup menu item. When the unit has a call for Y1 In and in
the free cooling mode and there is a call for Y2 In, the 2-speed fan
delay starts and the OA damper will modulate 100% open, the
supply fan should be set to high speed by the unit controller.
After the delay, one of two actions will happen:
• The Y2 In call will be satisfied with the damper 100%
open and fan on high speed and the call will turn off
OR
• If the call for additional cooling in the space has not been
satisfied then the first stage of mechanical cooling will be
enabled through Y1 Out or Y2 Out.
CHECKOUT
Inspect all wiring connections at the economizer module’s termi-
nals, and verify compliance with the installation wiring diagrams.
For checkout, review the Status of each configured parameter and
perform the Checkout tests.
NOTE: See “Interface Overview” on page 35. for information
about menu navigation and use of the keypad.
ECONOMIZING
AVAILABLE
NOT AVAILABLE
ENTHALPY
RA
HUM (%RH)
RA
TEMP
TEMPERATURE
ABSOLUTE HUMIDITY
ES5
ES4
ES3
ES2
ES1
HL
P1
(T,RH)
P2 (T,RH)
SINGLE ENTHALPY
DUAL ENTHALPY
HIGH LIMIT
ENTHALPY
CURVE
TEMP. DRY
BULB (F)
TEMP.
DEWPOINT (F)
ENTHALPY
(btu/lb/da)
POINT P1
POINT P2
TEMP. (F)
HUMIDITY
(%RH)
TEMP. (F)
HUMIDITY
(%RH)
ES1
80
60
28.0
80
36.8
66.3
80.1
ES2
75
57
26.0
75
39.6
63.3
80.0
ES3
70
54
24.0
70
42.3
59.7
81.4
ES4
65
51
22.0
65
44.8
55.7
84.2
ES5
60
48
20.0
60
46.9
51.3
88.5
HL
86
66
32.4
86
38.9
72.4
80.3
STATE
FAN SPEED
OCC
Low
Y1
Low
Y2
High
W
High
Summary of Contents for 48TC D/E17 Series
Page 5: ...5 Fig 2 48TC 17 20 Vertical Airflow...
Page 6: ...6 Fig 3 48TC 17 20 Back View and Condensate Drain Location...
Page 7: ...7 Fig 4 48TC 17 20 Corner Weights and Clearances...
Page 8: ...8 Fig 5 48TC 17 20 Bottom View...
Page 9: ...9 Fig 6 48TC 24 28 Vertical Airflow...
Page 10: ...10 Fig 7 48TC 24 28 Back View and Condensate Drain Location...
Page 11: ...11 Fig 8 48TC 24 28 Corner Weights and Clearances...
Page 12: ...12 Fig 9 48TC 24 28 Bottom View...
Page 13: ...13 Fig 10 48TC 30 Vertical Airflow...
Page 14: ...14 Fig 11 48TC 30 Back View and Condensate Drain Location...
Page 15: ...15 Fig 12 48TC 30 Corner Weights and Clearances...
Page 16: ...16 Fig 13 48TC 30 Bottom View...
Page 19: ...19 Fig 16 Roof Curb Details 17 and 20 Size Units...
Page 20: ...20 Fig 17 Roof Curb Details 24 and 28 Size Units...
Page 21: ...21 Fig 18 Roof Curb Details 30 Size Units...
Page 47: ...47 Fig 52 PremierLink Wiring Diagram...
Page 48: ...48 Fig 53 PremierLink Wiring Diagram with Humidi MiZer System...
Page 49: ...49 Fig 54 Typical RTU Open System Control Wiring Diagram...
Page 50: ...50 Fig 55 Typical RTU Open System Control Wiring Diagram with Humidi MiZer System...
Page 51: ...51 Fig 56 48TC 17 30 Control Wiring Diagram...
Page 52: ...52 Fig 57 48TC 17 30 Power Wiring Diagram 208 230 3 60...
Page 53: ...53 Fig 58 48TC 17 30 Power Wiring Diagram 460 3 60...
Page 54: ...54 Fig 59 48TC 17 30 Power Wiring Diagram 575 3 60...
Page 55: ...55 Fig 60 48TC 17 30 Control Wiring Diagram with Humidi MiZer System...
Page 56: ...56 Fig 61 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 208 230 3 60...
Page 57: ...57 Fig 62 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 460 3 60...
Page 58: ...58 Fig 63 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 575 3 60...