background image

38

STATUS 

(cont)

EXH2 OUT

OFF

ON/OFF

EXHAUST STAGE 2 RELAY OUTPUT

Output of AUX terminal; displays only if AUX = EXH2

ERV

OFF

ON/OFF

ENERGY RECOVERY VENTILATOR

Output of AUX terminal; displays only if AUX = ERV

MECH COOL ON

or

HEAT STAGES ON

0

0, 1, or 2

Displays stage of mechanical cooling that is active.

Displays the stage of heat pump heating that is active.

FAN SPEED

N/A

LOW or HIGH

SUPPLY FAN SPEED

Displays speed setting of fan on a 2-speed fan unit.

W (HEAT ON)

N/A

ON/OFF

HEAT DEMAND STATUS

Displays status of heat demand on a 2-speed fan unit.

SETPOINTS

MAT SET

53F

38°F to 65°F

(3°C to 18°C);

increment by 1°F

SUPPLY AIR SETPOINT

Setpoint determines where the economizer will modulate the OA 

damper to maintain the mixed air temperature.

LOW T LOCK

32F

–45°F to 80°F

(–43°C to 27°C);

increment by 1°F

COMPRESSOR LOW TEMPERATURE LOCKOUT

Setpoint determines outdoor temperature when the mechanical 

cooling cannot be turned on. Commonly referred to as the 

Compressor lockout.

DRYBLB SET

63F

48°F to 80°F

(9°C to 27°C);

 increment by 1°F

OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT

Setpoint determines where the economizer will assume outdoor 

air temperature is good for free cooling; e.g.; at 63°F unit will 

economize at 62°F and below and not economize at 64°F and 

above. There is a 2°F deadband.

ENTH CURVE

ES3

ES1,ES2,ES3,

ES4, or ES5

ENTHALPY CHANGEOVER CURVE

Enthalpy boundary “curves” for economizing using single 

enthalpy.

DCV SET

1100ppm

500 to 2000ppm; 

increment by 100

DEMAND CONTROLLED VENTILATION

Displays only if CO

2

 sensor is connected. Setpoint for Demand 

Controlled Ventilation of space. Above the setpoint, the OA 

dampers will modulate open to bring in additional OA to maintain 

a space ppm level below the setpoint.

MIN POS

2.8 V

2 to 10 Vdc

VENTILATION MINIMUM POSITION

Displays ONLY if a CO

2

 sensor is NOT connected.

VENTMAX 

With 2-speed fan units 

VENTMAX L (low speed 

fan) and VENTMAX H 

(high speed fan) settings 

are required

2.8 V

2 to 10 Vdc

DCV MAXIMUM DAMPER POSITION

Displays only if a CO

2

 sensor is connected. Used for Vbz 

(ventilation max cfm) setpoint. Displays 2 to 10 V if <3 sensors 

(RA,OA, and MA). In AUTO mode dampers controlled by CFM.

100 to 9990 cfm; 

increment

by 10

If OA, MA, RA, and CO

2

 sensors are connected and DCV CAL 

ENABLE is set to AUTO mode, the OA dampers are controlled 

by CFM and displays from 100 to 9990 CFM.

2 to 10 Vdc

With 2-speed fan units VENT L (low speed fan) and MIN POS H 

(high speed fan) settings are required. Default for VENTMAX L 

is 3.2V and VENTMAX H is 2.8V

VENTMIN 

With 2-speed fan units 

VENTMIN L (low speed 

fan) and VENTMIN 

H (high speed fan) set

2.25 V

2 to 10 Vdc or 100 

to 9990 cfm 

increment by 10

DCV MINIMUM DAMPER POSITION

Displays only if a CO

sensor is connected. Used for Ba 

(ventilation min cfm) setpoint. Displays 2 to 10 V if <3 sensors 

(RA, OA, and MA). Va is only set if DCV is used. This is the 

ventilation for less than maximum occupancy of the space. In 

AUTO mode dampers controlled by CFM.

100 to 9990 cfm; 

increment

by 10

If OA, MA, RA, and CO

2

 sensors are connected and DCV CAL 

ENABLE is set to AUTO mode, the OA dampers are controlled 

by CFM and displays from 100 to 9990 CFM.

2 to 10 Vdc

With 2-speed fan units VENTMIN L (low speed fan) and MIN 

POS H (high speed fan) settings are required. Default for 

VENTMIN L is 3.2V and VENTMIN H is 2.8V

ERV OAT SP

32°F

0°F to 50°F

(–18°C to 10°C);

 increment by 1°F

ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR 

TEMPERATURE SETPOINT

Only when AUX1 O = ERV

EXH1 SET 

With 2-speed fan units 

Exh1 L (low speed fan) 

and Exh1 H (high speed 

fan) settings are required

50%

0 to 100%; 

increment by 1

EXHAUST FAN STAGE 1 SETPOINT

Setpoint for OA damper position when exhaust fan 1 is powered 

by the economizer.

With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high 

speed fan) settings are required. Default for Exh1 L is 65% and 

Exh1 H is 50%

EXH2 SET 

With 2-speed fan units 

Exh2 L (low speed fan) 

and Exh2 H (high speed 

fan) settings are required

75%

0 to 100%; 

increment by 1

EXHAUST FAN STAGE 2 SETPOINT

Setpoint for OA damper position when exhaust fan 2 is powered 

by the economizer. Only used when AUX1 O is set to EHX2.

With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high 

speed fan) settings are required. Default for Exh2 L is 80% and 

Exh2 H is 75%

Table 12 — Menu Structure (cont)

MENU

PARAMETER

PARAMETER 

DEFAULT 

VALUE

PARAMETER 

RANGE AND 

INCREMENT

NOTES

Summary of Contents for 48TC D/E17 Series

Page 1: ...SCREENSAVER ENTHALPY SETTINGS TWO SPEED FAN OPERATION CHECKOUT TROUBLESHOOTING PremierLink Control 46 RTU Open Control System 46 Wiring Diagrams 46 Smoke Detectors 59 RETURN AIR SENSOR TUBE INSTALLAT...

Page 2: ...age and amperage listed on the unit rating plate Unit may have more than one power switch WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury death and...

Page 3: ...NOXYDE DE CARBONE Si ces directives ne sont pas suivies cela peut entra ner des blessures graves ou une intoxication au monoxyde de carbone pouvant causer la mort si des produits de combustion s infil...

Page 4: ...Hail Guard Q E coat Al Cu E coat Al Cu Louvered Hail Guard R Cu Cu Al Cu Louvered Hail Guard S Cu Cu Cu Cu Louvered Hail Guard Coil Options Novation Outdoor Indoor Hail Guard G Al Al Al Cu H Al Al Cu...

Page 5: ...5 Fig 2 48TC 17 20 Vertical Airflow...

Page 6: ...6 Fig 3 48TC 17 20 Back View and Condensate Drain Location...

Page 7: ...7 Fig 4 48TC 17 20 Corner Weights and Clearances...

Page 8: ...8 Fig 5 48TC 17 20 Bottom View...

Page 9: ...9 Fig 6 48TC 24 28 Vertical Airflow...

Page 10: ...10 Fig 7 48TC 24 28 Back View and Condensate Drain Location...

Page 11: ...11 Fig 8 48TC 24 28 Corner Weights and Clearances...

Page 12: ...12 Fig 9 48TC 24 28 Bottom View...

Page 13: ...13 Fig 10 48TC 30 Vertical Airflow...

Page 14: ...14 Fig 11 48TC 30 Back View and Condensate Drain Location...

Page 15: ...15 Fig 12 48TC 30 Corner Weights and Clearances...

Page 16: ...16 Fig 13 48TC 30 Bottom View...

Page 17: ...aced on the curb Review the following for rec ommended sequences for installation steps CURB MOUNTED INSTALLATION 1 Install curb 2 Install field fabricated ductwork inside curb 3 Install accessory thr...

Page 18: ...openings Fig 14 Unit Leveling Tolerances Fig 15 Typical Access Panel and Compressor Locations Table 2 Operating Weights A B 0 25 6 B C 0 5 12 A C 0 5 12 MAXIMUM ALLOWABLE DIFFERENCE IN MM A B C CONTR...

Page 19: ...19 Fig 16 Roof Curb Details 17 and 20 Size Units...

Page 20: ...20 Fig 17 Roof Curb Details 24 and 28 Size Units...

Page 21: ...21 Fig 18 Roof Curb Details 30 Size Units...

Page 22: ...on curb after unit is set Doing so will result in damage to the roof curb seal Although unit is weatherproof guard against water from higher level runoff and overhangs Flue vent discharge must have a...

Page 23: ...ms 4 and 5 to upper panel using the screws provided 6 Apply seal strip to mating flange of the hood see Fig 22 7 Secure hood item 3 to upper panel using the screws provided 8 Secure side retainers ite...

Page 24: ...uctions regarding these accessories NOTE Furnace gas input rate on rating plate is for installation up to 2000 ft 610 m above sea level The input rating for altitudes above 2000 ft 610 m must be derat...

Page 25: ...re drop of 0 5 in wg 124 Pa between gas regulator source and unit gas valve connec tion when unit is operating at high fire flow rate The gas supply line can approach the unit in two ways horizontal l...

Page 26: ...m gases as specified by local and or national codes If using PTFE Teflon tape ensure the material is Double Density type and is labeled for use on gas lines Apply tape per manufacturer s instructions...

Page 27: ...connect the source leads to the line side with unit field power leads See Fig 32 Fig 32 Location of TB1 Field power wires are connected to the unit at line side pressure lugs on the terminal block se...

Page 28: ...position 4 Measure the tip of the shaft to the outside surface of the cor ner post to be 0 88 in 5 Tighten the locking screw to secure the shaft to the NFD 6 Turn the handle to OFF position with red...

Page 29: ...37 Remove two slot fillers in the bottom of the cover to per mit service tool cords to exit the cover Check for full closing and latching Fig 37 Weatherproof Cover Installation Non powered type Requir...

Page 30: ...outing and connection information Units Without Thru Base Connections 1 Install liquid tight conduit between disconnect and control box 2 Pull correctly rated high voltage wires through the conduit 3...

Page 31: ...at HL38MG029 1 Route the humidistat 2 conductor cable field supplied through the hole provided in the unit corner post 2 Feed wires through the raceway built into the corner post see Fig 41 to the 24...

Page 32: ...32 Fig 42 Accessory Field Installed Humidistat Fig 43 Edge Pro Thermidistat Fig 44 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring RELATIVE HUMIDITY...

Page 33: ...re of the EconoMi er X system The module is mounted in the unit s control box and includes the user inter face for the system The W7220 economizer module provides the basic inputs and outputs to provi...

Page 34: ...osure to 40 F 40 C Storage Temperature 40 F to 150 F 40 C to 65 C Shipping Temperature 40 F to 150 F 40 C to 65 C Relative Humidity 5 to 95 RH non condensing ECONOMIZER MODULE WIRING DETAILS Use Fig 4...

Page 35: ...ypad on the front of the economizer controller KEYPAD The four navigation buttons see Fig 50 are used to scroll through the menus and menu items select menu items and to change parameter and configura...

Page 36: ...ame ters for the EconoMi er X system The Menus in display order are STATUS SETPOINTS SYSTEM SETUP ADVANCED SETUP CHECKOUT ALARMS NOTE Some parameters in the menus use the letters MA or MAT indicating...

Page 37: ...n Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40 F...

Page 38: ...Displays 2 to 10 V if 3 sensors RA OA and MA In AUTO mode dampers controlled by CFM 100 to 9990 cfm increment by 10 If OA MA RA and CO2 sensors are connected and DCV CAL ENABLE is set to AUTO mode the...

Page 39: ...factory default values NOTE RECHECK AUX2 IN and FANTYPE for required 2 speed values ADVANCED SETUP MA LO SET 45 F 35 F to 55 F 2 F to 13 F incremented by 10 F SUPPLY AIR TEMPERATURE LOW LIMIT Temperat...

Page 40: ...c out Issues a system alarm CONNECT EXH1 N A N A Closes the power exhaust fan 2 relay EXH1 ALARMS Alarms display only when they are active The menu title ALARMS includes the number of active alarms in...

Page 41: ...dry bulb and enthalpy operation with and without DCV see Tables 14 17 For 2 speed fan dry bulb and enthalpy operation with and without DCV see Tables 18 21 Table 13 Damper Minimum Position Settings a...

Page 42: ...4v On 0v Off MIN POS to Full Open Closed to Full Open DEMAND CONTROLLED VENTILATION DCV OUTSIDE AIR GOOD TO ECONOMIZE Y1 I Y2 I FAN SPEED Y1 O Y2 O OCCUPIED UNOCCUPIED Below CO2 Set No OFF OFF HIGH 0v...

Page 43: ...ed ON ON HIGH 24v On 24v On VENTMIN to VENTMAX Closed Yes OFF OFF HIGH 0v Off 0v Off VENTMIN to VENTMAX Closed ON OFF HIGH 0v Off 0v Off VENTMIN to Full Open Closed to Full Open ON ON HIGH 24v On 0v O...

Page 44: ...ff 0v Off MIN POS Closed ON OFF LOW 0v Off 0v Off MIN POS to Full Open Closed to Full Open ON ON HIGH 24v On 0v Off MIN POS to Full Open Closed to Full Open DEMAND CONTROLLED VENTILATION DCV OUTSIDE A...

Page 45: ...lled by the W7220 but it re quires the status to know where to position the OA damper for minimum position for the fan speed The 2 speed fan delay is available when the system is programmed for 2 spee...

Page 46: ...e alarms You can also navigate to the Alarms menu at any time Clearing Alarms Once the alarm has been identified and the cause has been re moved e g replaced faulty sensor the alarm can be cleared fro...

Page 47: ...47 Fig 52 PremierLink Wiring Diagram...

Page 48: ...48 Fig 53 PremierLink Wiring Diagram with Humidi MiZer System...

Page 49: ...49 Fig 54 Typical RTU Open System Control Wiring Diagram...

Page 50: ...50 Fig 55 Typical RTU Open System Control Wiring Diagram with Humidi MiZer System...

Page 51: ...51 Fig 56 48TC 17 30 Control Wiring Diagram...

Page 52: ...52 Fig 57 48TC 17 30 Power Wiring Diagram 208 230 3 60...

Page 53: ...53 Fig 58 48TC 17 30 Power Wiring Diagram 460 3 60...

Page 54: ...54 Fig 59 48TC 17 30 Power Wiring Diagram 575 3 60...

Page 55: ...55 Fig 60 48TC 17 30 Control Wiring Diagram with Humidi MiZer System...

Page 56: ...56 Fig 61 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 208 230 3 60...

Page 57: ...57 Fig 62 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 460 3 60...

Page 58: ...58 Fig 63 48TC 17 30 Power Wiring Diagram with Humidi MiZer System 575 3 60...

Page 59: ...Sensor Location Fig 65 Return Air Sampling Tube Location in Unit without Economizer Fig 66 Return Air Sampling Tube Location in Unit with Economizer To install the return air sensor sampling tube 1 Re...

Page 60: ...Refer to separate installation instructions for information on in stalling these accessories Step 14 Check Belt Tension Measure the belt span length as shown in Fig 68 Calculate the re quired deflect...

Page 61: ...rom HVAC Partners www hvacpartners com Table 1 Table 2 BELT CROSS SECTION SMALLEST SHEAVE DIAMETER BELT DEFLECTION FORCE LBS UNNOTCHED BELTS NOTCHED BELTS USED NEW USED NEW A AX 3 0 3 6 3 7 5 5 4 1 6...

Page 62: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480268 01 Printed in U S A Form 48TC 17 30 V 05SI Pg 62 8 19 Replaces 48TC 1...

Page 63: ...door air filters are clean and in place Y N _____ Verify that unit installation is level Y N _____ Check fan wheels and propeller for location in housing orifice and setscrew tightness Y N _____ Check...

Page 64: ...scharge pressure _______________ PSIG C Entering air temperature _______________ F D Liquid line temperature at outlet or reheat coil _______________ F E Confirm correct rotation for compressor Y N __...

Reviews: