P5 — ECONOMIZER MINIMUM POSITION — This po-
tentiometer is on the accessory board (provided standard from
the factory) located in the unit main control box. It has both
a valid range and an operational range of 0% to 100%. If a
fault condition is detected by the processor, an alarm con-
dition will be signaled and the economizer dampers will close.

P6 — WARM-UP SET POINT — This potentiometer is on
the accessory board (provided standard from the factory) lo-
cated in the unit main control box, and DIP switch 4 must be
in the ON position if morning warm-up heat is to be used.
The valid range is 0° F to 95 F, but the processor is pro-
grammed to accept a range of 40 F to 80 F. If the set point
is between 0° F and 40 F, a default value of 40 F will be
used. If the range is between 80 F and 95 F, 80 F will be
used. If the value is less than 0° F or greater than 95 F,
40 F will be used as a default and an alarm condition will
result.

P7 — RESET TEMPERATURE — This 10 Kohm poten-
tiometer is used only if the accessory, field-installed tem-
perature reset package is installed, and DIP switch 2 is in the
ON position. This potentiometer determines the temperature
at which reset will begin. It is located on the accessory tem-
perature reset board and has a valid range of 40 F to 100 F.

PROCESSOR BOARD OUTPUTS — The processor board
also controls outputs through the relay board. The relay board
plugs into the processor board using a ribbon cable.

In addition, the processor board controls the display board.

The display board is connected to the processor board by a
ribbon cable, and has an LED (light-emitting diode) display
showing the status of the unit and diagnostic information.

CONFIGURATION HEADER AND DIP SWITCH ASSEM-
BLY — The processor board is programmed to control a va-
riety of air conditioning units. To tailor the processor to the
particular unit being controlled, 2 devices are used. One is
the configuration header, and the other is the DIP switch as-
sembly.

The configuration header is a series of 8 small wires that

are broken or unbroken in a pattern to indicate several unique
characteristics of the unit. The configuration header is fac-
tory set and should not be changed. Changing the factory
setting may cause the unit to malfunction. The purpose of
each jumper is listed in Table 4.

The DIP switches configure the unit for several field-

installed options, as well as for several other options that
may be unique to the unit. The DIP switches are located un-
der a plastic enclosure which must be removed for access.
The switches can be field adjusted, but must be adjusted only
when the unit control circuit breaker is off. See Table 5 for
DIP switch meanings and Table 6 for factory settings of both
the configuration header and DIP switches.

Table 4 — Configuration Header Jumpers

JUMPER

NUMBER

FUNCTION

FACTORY

SETTING

MEANING

1,2

Unit Type

▫ n

VAV Rooftop Unit

3-5

Qty Compressors

n ▫ ▫

2 Compressors

6

Expansion
Valve

n

TXV

7

Power
Frequency

60 Hz

8

Not Used

n

No Significance

LEGEND

TXV — Thermostatic Expansion Valve
VAV — Variable-Air Volume

— Broken Jumper (open circuit)

n

— Unbroken Jumper (closed circuit)

Table 5 — DIP Switches

SWITCH

NO.

FUNCTION

FACTORY
SETTING*

MEANING

1

Reset

Mode

Off

Space or Outdoor-
Air Reset

2

Reset

Select

On
Off

Reset Used
Reset Not Used

3

Economizer

On
Off

Enable Economizer
Disable Economizer†

4

Morning

Warm-Up

On
Off

Enable Morning Warm-Up**
Disable Morning Warm-Up**

5

Demand

Limit

On
Off

Enable Demand Limit
Disable Demand Limit

6,7

Unloaders

Off, Off
On, Off
Off, On

No Unloaders
1 Unloader
2 Unloaders

8

Not Used

Off

No Significance

DIP — Dual, In-Line Package

*Control circuit breaker must be off before changing the setting of

the DIP switch.

†No economizer.

**And/or electric heat (50 Series units only).

Table 6 — Configuration Header and DIP Switch

Factory Settings

JUMPER OR
SWITCH NO.

UNIT SIZES 024-034,

054-074

UNIT SIZE 044

Header

Position

Switch

Position

Header

Position

Switch

Position

1

Off

Off

2

n

Off

n

Off

3

n

On/Off*

n

On/Off*

4

On/Off*

On/Off*

5

Off

Off

6

n

Off

n

On

7

On

Off

8

n

Off

n

Off

LEGEND

DIP — Dual, In-Line Package

— Broken Jumper (open circuit)

n

— Unbroken Jumper (closed circuit)

*Depending on factory-installed options or field-installed accessories.

Relay Board —

The relay board is used to control 24-v

and 115-v loads. See Fig. 5. The relay board is connected to
the processor board by a ribbon cable at pin J9. Electrical
connections to the relay board are made through pins J5
(115 v) and J6 (24 v). The relay board has eight 24-v relays
and five 115-v relays. See Table 7.

Display Board —

The display board is located in the

main unit control box and is connected to the J10 port of the
processor board through a ribbon cable. The display board
contains the leaving-air set point potentiometer P1; a 2-digit,
LED display; and the display button (See Fig. 6). The LED
display is used to convey the operating information and op-
erational error codes.

Thermistors —

The processor uses up to 5 thermistors

to sense the temperatures at various points in the system.
See Table 1 and Fig. 7-18. All the thermistors have identical
temperature versus resistance and voltage drop characteris-
tics, and are monitored by the processor for a short or open
circuit. The valid range for a thermistor is 362,640 to
219 ohms. Thermistor details and locations are as follows:
T1 — LEAVING-AIR SET POINT THERMISTOR — This
thermistor is located in the unit supply fan discharge. It pro-
vides information for the processor to stage the number of
capacity steps required to maintain a desired leaving-air
temperature.

5

Summary of Contents for 48DK024

Page 1: ...ential Pressure Switch 21 SIZE 024 030 UNITS SIZE 034 044 UNITS SIZE 054 074 UNITS Inlet Guide Vane Differential Pressure Switch Units with Inlet Guide Vane and Static Pressure Control Option 21 SIZE...

Page 2: ...mand limit control module Field installed accessories The VAV control system monitors and controls the fol lowing functions of the rooftop unit leaving air temperature unit capacity morning warm up or...

Page 3: ...ssory temperature reset package The fixed resistor has a resistance value of 1200 ohms 5 NOTE Terminal numbers 3 13 are not used on these units Table 2 Pin Terminal Connector J2 Status Switch Inputs C...

Page 4: ...If the set point is between 22 F and 45 F the control will use a value of 45 F If the set point is outside of the valid range less than 22 F or greater than 70 F an alarm condition will be signaled an...

Page 5: ...and Table 6 for factory settings of both the configuration header and DIP switches Table 4 Configuration Header Jumpers JUMPER NUMBER FUNCTION FACTORY SETTING MEANING 1 2 Unit Type n VAV Rooftop Unit...

Page 6: ...IFC J5 2 Morning Warm Up Relay K10 HIR J5 3 Stage 1 Condenser Fan Relay K11 OFC1 OFC2 OFC2 OFC3 J5 4 Stage 2 Condenser Fan Relay K12 Not Used OFC4 J5 5 External Alarm Relay K13 R ALM LEGEND ALM Alarm...

Page 7: ...ter A control signal to check the safety statuses and to start the compressor is sent from the relay board This signal trav els through all of the safeties the high pressure switch the low pressure sw...

Page 8: ...Fig 9 Thermistor T1 Location 50DY024 030 Units GAS SECTION 48DK ONLY HORIZONTAL SUPPLY SECTION 50DY ONLY Fig 10 Thermistor T1 Location 48DK 50DY034 044 Units 8...

Page 9: ...FAN DISCHARGE ELECTRIC HEAT SECTION Fig 11 Thermistor T1 Location 50DK034 044 Units GAS SECTION 48DK FAN DISCHARGE ELECTRIC HEAT SECTION 50DY Fig 12 Thermistor T1 Location 48DK 50DY054 074 Units 9...

Page 10: ...FAN DISCHARGE ELECTRIC HEAT Fig 13 Thermistor T1 Location 50DK054 074 Units Fig 14 Thermistor T2 Location 024 030 Units STANDARD FILTERS BAG FILTERS Fig 15 Thermistor T2 Location 034 044 Units 10...

Page 11: ...STANDARD FILTERS Fig 17 Thermistor T3 and T4 Locations 034 044 Units Fig 18 Thermistor T3 and T4 Locations 054 074 Units BAG FILTERS Fig 16 Thermistor T2 Location 054 074 Units 11...

Page 12: ...nd diagnostic codes CODES 0 THROUGH 6 CAPACITY STEPS These codes indicate the number of cooling stages active at the time the display button is pressed The highest code indicated on the display will b...

Page 13: ...the initialization period is complete the supply and return fans begin operation While the fans are operating the economizer dampers are closed and return air from the building is being circulated Af...

Page 14: ...trol literature for details SIZE 024 030 UNITS All units have a fan cycling ther mostat which cycles OFM2 located over the control box The thermostat switch opens at 60 F 3 F and closes at 70 F 3 F SI...

Page 15: ...OFM Outdoor Condenser Fan Motor Fig 21 Component Arrangement 024 030 Units OFM Outdoor Condenser Fan Motor Fig 22 Component Arrangement 034 044 Units 15...

Page 16: ...054 074 Units LEGEND TB Terminal Block Factory Wiring Field Wiring NOTE For 4 sensor arrangement wire sensors 1 2 4 and 5 as shown Sensors 3 and 6 9 are not used in a 4 sensor application Fig 24 Multi...

Page 17: ...Static Pressure Control Option If unit is equipped with static pressure control option differential pressure switch will modulate fan inlet guide vanes to vary airflow to maintain set point of the swi...

Page 18: ...conomizer outdoor air damper fully open normally open Switch 7 Switch to isolate evaporator fan motor from power exhaust motor normally closed Switch 8 Switch to provide 24 v power to inlet guide vane...

Page 19: ...s and set point potentiometers to ensure that they are functional connected properly and set within proper range for unit configuration Nominal resistance values for all sensors range from 363 000 to...

Page 20: ...Faulty or Option not used Accessory Demand Limit Potentiometer P4 2 2 1 1 Potentiometer OK 0 Potentiometer Faulty or Option not used Minimum Position Economizer Potentiometer P5 2 3 1 1 Potentiometer...

Page 21: ...all 20 to 75 ton rooftop units refer to base unit in stallation instruction literature Inlet Guide Vane Motor Units with Inlet Guide Vanes and Static Pressure Control Option The inlet guide vane moto...

Page 22: ...ull span The null span is the pres sure change that can be made without contacts opening or closing It is adjustable from 0 06 in wg to 0 17 in wg when set point is at minimum position 1 1 in wg and 0...

Page 23: ...ostat in each com pressor is also wired in series with 24 v power that ener gizes CR If thermostat fails or switch opens during opera tion of compressor compressor will shut down and failure is detect...

Page 24: ...4 074 CODE 81 RESET THERMISTOR OR POTENTIOM ETER FAILURE This is a unique code since the reset temperature potentiometer P7 is in series with the space temperature thermistor T10 If either one of thes...

Page 25: ...kwise potentiometer will be out of the allowable range and an error will result Faulty Wiring If wiring between the potentiometer and the processor board is incorrect an error will occur Potentiometer...

Page 26: ...in quick test mode 3 Check voltage TP18 to TP9 4 If voltage is greater than 11 vdc recheck transformer input voltage 5 If transformer is okay replace processor board 6 Turn power to ON position Step...

Page 27: ...r J10 details PIN TERMINAL VOLTAGE DC 17 5 18 5 20 2 5 22 2 5 24 5 Voltage reading is dependent on the meter s impedance Readings may vary with different meters 6 If voltage is not correct replace pro...

Page 28: ...ard Relay Board Checkout Step 1 Low voltage relay resistance check 1 Turn switch to OFF position 2 Remove plug connection from terminal strip J6 3 Set meter to measure resistance Connect negative test...

Page 29: ...ng the voltage readings Test under the following conditions No power to IN1 or IN2 Terminal 1 to 2 should read 4 5 vdc 0 1 v Terminal 2 to 3 should read 5 0 vdc 0 1 v Power to IN2 or to both IN1 and I...