background image

PROCESSOR BOARD CHECKOUT — Refer to Fig. 32
and 33 for location of terminal pins and test points.
Step 1 — Check transformer input to the board.

Connector J4 is used to connect the control transformer to

the processor board.
1. Set the volt-ohmmeter to ac voltage with a range setting

of approximately 30 v.

2. Turn control switch to ON position.
3. Check voltage at following terminals on pin terminal con-

nector J4:

TERMINALS

VOLTAGE (AC)

1 to 2

15.3 to 20.9

4 to 6

16.2 to 22.0

5 to 6

8.1 to 11.0

5 to 4

8.1 to 11.0

4. If voltage is not within range, check primary side.

115-v transformer — 104 to 127 vac
230-v transformer — 207 to 254 vac

5. If primary voltage is not correct, check system fuse, trans-

former, ON-OFF switch, and wiring. If these are okay,
contact power company.

6. If primary voltage is correct, but secondary voltage

(24 v ± 10%) is incorrect, replace transformer.

7. Turn control switch to OFF position.
Step 2 — Check processor board power supply.
1. Set meter to approximately 20 vdc.
2. Turn power to OFF position.
3. Connect negative lead to TP18.
4. Turn power switch to ON position and press display but-

ton to enter quick test mode.

5. Check voltage between TP18 and each of the following

test pins:

TEST PIN

VOLTAGE (DC)

TP3

1

10

TP4

1

12

TP6

1

5

TP10

1

5

TP14

1

12

TP15

1

12

TP7

−5*

*If not using a digital meter, leads must be reversed.

6. If voltage is incorrect, replace processor board.
7. Turn power to ON position.

Step 3 — Check voltage tolerance circuitry.
1. Turn power to OFF position.
2. Negative test probe on TP18 and system in quick test mode.
3. Check voltage TP18 to TP9.
4. If voltage is greater than

1

1 vdc, recheck transformer

input voltage.

5. If transformer is okay, replace processor board.
6. Turn power to ON position.
Step 4 — Check processor reset line.
1. Turn power to OFF position.
2. Negative probe on TP18.
3. Check voltage TP18 to TP11.
4. If voltage is greater than

1

3 vdc, reset power and re-

check.

5. If voltage is still incorrect, replace processor board.
6. Turn power to ON position.
Step 5 — Check relay board outputs from the processor board.

This step involves checking the output signals from re-

lays K1-K3 on the relay board.
1. Turn power to OFF position.
2. Connect negative test probe to TP19 (meter still set to

dc).

3. Turn switch to ON position and enter quick test mode.
4. Connect positive test probe to terminal 14 on pin termi-

nal connector J9, and check voltage from TP19 to ter-
minal 14 on pin terminal connector J9.

5. If not

1

12 ± 1 vdc, replace processor board.

6. Turn switch to OFF position.
7. Remove negative test probe from TP19. Connect positive

test probe to TP15.

8. Turn switch to ON position and go into quick test mode.
9. Place negative lead on terminals shown in Table 13, and

check voltage between TP15 and terminals shown in
Table 13 on pin terminal connector J9. See Fig. 34 for J9
details.

K1

K2

K3

C1

C2

C3

C4

C5

C6

C7

C8

CR1

CR2

CR3

CR4

CR5

CR6

CR7

CR8

C27

C15

C14

C26

C25

C24

C23

C22

E3

CR9

CR10

CR11

CR12

CR13

C9

C10

C11

C12

C13

R9

R10

R11

R12

R13

J5

J6

C19

C16

C18

C21

CR — Control Relay
J

— Pin Terminal Strip

K

— Relay

Fig. 33 — Relay Board Test Points

Q2

C14

CR5

R65

R13

E6

Z6

J7

TP19

J9

TP18

TP10

TP15

TP14

J10

J3

TP9

TP3

TP4

TP7

TP6

J4

TP11

J

— Pin Terminal Strip

TP — Test Pin

Fig. 32 — Processor Board Test Points

26

Summary of Contents for 48DK024

Page 1: ...ential Pressure Switch 21 SIZE 024 030 UNITS SIZE 034 044 UNITS SIZE 054 074 UNITS Inlet Guide Vane Differential Pressure Switch Units with Inlet Guide Vane and Static Pressure Control Option 21 SIZE...

Page 2: ...mand limit control module Field installed accessories The VAV control system monitors and controls the fol lowing functions of the rooftop unit leaving air temperature unit capacity morning warm up or...

Page 3: ...ssory temperature reset package The fixed resistor has a resistance value of 1200 ohms 5 NOTE Terminal numbers 3 13 are not used on these units Table 2 Pin Terminal Connector J2 Status Switch Inputs C...

Page 4: ...If the set point is between 22 F and 45 F the control will use a value of 45 F If the set point is outside of the valid range less than 22 F or greater than 70 F an alarm condition will be signaled an...

Page 5: ...and Table 6 for factory settings of both the configuration header and DIP switches Table 4 Configuration Header Jumpers JUMPER NUMBER FUNCTION FACTORY SETTING MEANING 1 2 Unit Type n VAV Rooftop Unit...

Page 6: ...IFC J5 2 Morning Warm Up Relay K10 HIR J5 3 Stage 1 Condenser Fan Relay K11 OFC1 OFC2 OFC2 OFC3 J5 4 Stage 2 Condenser Fan Relay K12 Not Used OFC4 J5 5 External Alarm Relay K13 R ALM LEGEND ALM Alarm...

Page 7: ...ter A control signal to check the safety statuses and to start the compressor is sent from the relay board This signal trav els through all of the safeties the high pressure switch the low pressure sw...

Page 8: ...Fig 9 Thermistor T1 Location 50DY024 030 Units GAS SECTION 48DK ONLY HORIZONTAL SUPPLY SECTION 50DY ONLY Fig 10 Thermistor T1 Location 48DK 50DY034 044 Units 8...

Page 9: ...FAN DISCHARGE ELECTRIC HEAT SECTION Fig 11 Thermistor T1 Location 50DK034 044 Units GAS SECTION 48DK FAN DISCHARGE ELECTRIC HEAT SECTION 50DY Fig 12 Thermistor T1 Location 48DK 50DY054 074 Units 9...

Page 10: ...FAN DISCHARGE ELECTRIC HEAT Fig 13 Thermistor T1 Location 50DK054 074 Units Fig 14 Thermistor T2 Location 024 030 Units STANDARD FILTERS BAG FILTERS Fig 15 Thermistor T2 Location 034 044 Units 10...

Page 11: ...STANDARD FILTERS Fig 17 Thermistor T3 and T4 Locations 034 044 Units Fig 18 Thermistor T3 and T4 Locations 054 074 Units BAG FILTERS Fig 16 Thermistor T2 Location 054 074 Units 11...

Page 12: ...nd diagnostic codes CODES 0 THROUGH 6 CAPACITY STEPS These codes indicate the number of cooling stages active at the time the display button is pressed The highest code indicated on the display will b...

Page 13: ...the initialization period is complete the supply and return fans begin operation While the fans are operating the economizer dampers are closed and return air from the building is being circulated Af...

Page 14: ...trol literature for details SIZE 024 030 UNITS All units have a fan cycling ther mostat which cycles OFM2 located over the control box The thermostat switch opens at 60 F 3 F and closes at 70 F 3 F SI...

Page 15: ...OFM Outdoor Condenser Fan Motor Fig 21 Component Arrangement 024 030 Units OFM Outdoor Condenser Fan Motor Fig 22 Component Arrangement 034 044 Units 15...

Page 16: ...054 074 Units LEGEND TB Terminal Block Factory Wiring Field Wiring NOTE For 4 sensor arrangement wire sensors 1 2 4 and 5 as shown Sensors 3 and 6 9 are not used in a 4 sensor application Fig 24 Multi...

Page 17: ...Static Pressure Control Option If unit is equipped with static pressure control option differential pressure switch will modulate fan inlet guide vanes to vary airflow to maintain set point of the swi...

Page 18: ...conomizer outdoor air damper fully open normally open Switch 7 Switch to isolate evaporator fan motor from power exhaust motor normally closed Switch 8 Switch to provide 24 v power to inlet guide vane...

Page 19: ...s and set point potentiometers to ensure that they are functional connected properly and set within proper range for unit configuration Nominal resistance values for all sensors range from 363 000 to...

Page 20: ...Faulty or Option not used Accessory Demand Limit Potentiometer P4 2 2 1 1 Potentiometer OK 0 Potentiometer Faulty or Option not used Minimum Position Economizer Potentiometer P5 2 3 1 1 Potentiometer...

Page 21: ...all 20 to 75 ton rooftop units refer to base unit in stallation instruction literature Inlet Guide Vane Motor Units with Inlet Guide Vanes and Static Pressure Control Option The inlet guide vane moto...

Page 22: ...ull span The null span is the pres sure change that can be made without contacts opening or closing It is adjustable from 0 06 in wg to 0 17 in wg when set point is at minimum position 1 1 in wg and 0...

Page 23: ...ostat in each com pressor is also wired in series with 24 v power that ener gizes CR If thermostat fails or switch opens during opera tion of compressor compressor will shut down and failure is detect...

Page 24: ...4 074 CODE 81 RESET THERMISTOR OR POTENTIOM ETER FAILURE This is a unique code since the reset temperature potentiometer P7 is in series with the space temperature thermistor T10 If either one of thes...

Page 25: ...kwise potentiometer will be out of the allowable range and an error will result Faulty Wiring If wiring between the potentiometer and the processor board is incorrect an error will occur Potentiometer...

Page 26: ...in quick test mode 3 Check voltage TP18 to TP9 4 If voltage is greater than 11 vdc recheck transformer input voltage 5 If transformer is okay replace processor board 6 Turn power to ON position Step...

Page 27: ...r J10 details PIN TERMINAL VOLTAGE DC 17 5 18 5 20 2 5 22 2 5 24 5 Voltage reading is dependent on the meter s impedance Readings may vary with different meters 6 If voltage is not correct replace pro...

Page 28: ...ard Relay Board Checkout Step 1 Low voltage relay resistance check 1 Turn switch to OFF position 2 Remove plug connection from terminal strip J6 3 Set meter to measure resistance Connect negative test...

Page 29: ...ng the voltage readings Test under the following conditions No power to IN1 or IN2 Terminal 1 to 2 should read 4 5 vdc 0 1 v Terminal 2 to 3 should read 5 0 vdc 0 1 v Power to IN2 or to both IN1 and I...

Page 30: ...Evaporator Fan Contactor IGVM Inlet Guide Vane Motor IP Internal Protector J Pin Terminal Connector LAT Leaving Air Temperature LPS Low Pressure Switch LS Limit Switch MTR Motor NC Normally Closed NO...

Page 31: ...Fig 36 Typical Control Wiring 034 044 Units Shown cont 31...

Page 32: ...96 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 1 Tab 1a 1b PC 111 Catalog...

Reviews: