5.4 – Power wiring cable

The connection cable between the electric heater control box 
and the unit control box must be connected to ensure control 
during operation.

Cables corresponding to the unit wiring diagram must be 
connected between terminals 14, 19, 5 and 1 of the terminal 
strip in the electric heater control box and in the unit control 
box. For the packaged 50TA/TY units these have the following 
characteristics:

Fig. 17

Dimensions, mm

50TA/TZ
50TY/YZ

kW

A

024

1.5-6

3000

036-060

3-4, 5-6, 
9-13.5

3900

072-084

6, 12, 18

5000

Wire section, mm

kW

230 V, 3 ph

400 V, 3 ph

L1, L2, L3

L1, L2, L3, 

1.5

1.5

1.5

3

1.5

1.5

4.5

2.5

1.5

6

4

1.5

9

6

2.5

12

10

4

13.5

10

4

18

16

6

Colour code:
L1, L2, L3  =  Black

 

=  Green/yellow striped

=  Flexible pipe, type PG 13.5 for all capacities except 12 and 18 kW 

– these are type PG 16

NOTE: The wire section is suitable for ambient temperatures 
below 50°C.

NOTE:  All data applies to packaged units. For split system 
units the data depends on the distance between indoor and 
outdoor units.

These cable assemblies must be run from the thermal-magnetic 
switch of the electric heaters inside the control box to the power 
and control box for the unit, as shown in the unit wiring dia-
grams. Cable 

, Fig. 16, is taken out of the casing conduit of 

the electric heater control box 

, Fig. 18, and passed through a 

conduit using the pre-punched hole in panel 

.

Fig. 16

Fig. 15 - 230 V three-phase or 400 V three-phase 

heaters with 1.5, 3, 4. 5, 6, 9, 12, 13.5 and 18 kW 

capacity

Dimensions, mm

50TA/TZ
50TY/YZ

A

024

3300

036-060

3900

072-084

5000

1

  Number of the connection terminal and cable

2

  Cables:

 

Section = 1 x 1 mm

 

Colours: 

No. 5 and 1  = Grey

 

 

No. 14 

= Black

 

 

No. 19 

= Blue

3

  Flexible pipe, type PG 7

4

  Terminals:

 

Flag type (4 off)

 

Flag terminal protector (4 off)

 

Rod type, 0.75-1 mm

 (4 off)

Cables 

 are taken out of conduit 

 (Fig. 18) and run to the 

unit power and control box through pre-punched hole 

, as 

shown in Figs. 16, 18 and 19.

Summary of Contents for 40TZ Series

Page 1: ...50TA TZ TY YZ 40TA TZ TY BZ 38TA FZ TY BZ Electric Heaters Installation instructions NOTE This manual refers to accessories and options with D as the final letter in the ordering code...

Page 2: ...he nearest Carrier office and make a note on the shipping documents To prevent damage and or loss keep all components in their original packaging until they are installed by qualified personnel 3 UNIT...

Page 3: ...e panel Secure the heater as shown in Fig 6 using the screws supplied Fig 6 View of the unit and electric heater 1 Holes and fixing points of the electric heater to the unit with fixing screws Fig 8 T...

Page 4: ...ges indicated in the price list technical data wiring diagrams and applicable manuals 5 ELECTRICAL CONNECTIONS Before the definitive installation of the electric heaters in the unit a number of operat...

Page 5: ...switch A 6 10 10 10 16 230 1 50 16 16 230 3 50 16 16 16 20 400 3 50 R3 electric heater total kW 1 5 3 3 4 5 6 230 1 50 2 3 230 3 50 3 3 4 5 6 These thermal magnetic switches are located in the control...

Page 6: ...temperatures below 50 C NOTE All data applies to packaged units For split system units the data depends on the distance between indoor and outdoor units These cable assemblies must be run from the the...

Page 7: ...mal magnetic switches cables etc In this case only the installation in the panel shown and the electrical connection as shown in the wiring diagram are required If the electric heater is supplied inst...

Page 8: ...ns without notice Printed in the Netherlands on chlorine free paper Fig 20 Wiring diagram for the connection of the electric heaters models 50TA TZ TY YZ 38TA FZ TY BZ 40TA TZ TY BZ To the unit contro...

Reviews: