IMPORTANT:  Whenever the electric heater power supply is 
downstream of the unit main disconnect switch (Figs. 9, 10 
and 11) it is not permitted to install a heater of higher capacity 
(kW) than indicated in tables 1 and 2, that are the standard 
heaters.

C -  If the unit has been installed and an electric heater is to be 

connected whose control power supply is not connected via 
the main unit disconnect switch or if it is desirable to have an 
independent power supply connect and protect it as follows:

 

Cables of adequate wire section

 

Fuses F1 with a current that complies with the heater 
capacity (kW) installed.

 

A bipole or tripole disconnect switch, depending on 
the voltage with the necessary current (A).

 

Locate a thermal-magnetic disconnect switch with 
current (A) in accordance with tables 3 and 4 in the 
electric heater control box, as described in chapter 5..

Standard heater connection

Fig. 9

4 - ELECTRIC HEATER CAPACITIES (kW)

The electric heater capacities for cooling models or additional 
heater capacities for heat pumps, according to valid Carrier 
publications, are:

Table 1 – Cooling only models

Unit 

Capacity, kW

50TA/TZ 024 

4.0 or 4.6

38TA/FZ-40TY/BZ 024
50TA/TZ 036-048 

6.0 or 9.0

38TA/FZ-40TY/BZ 036-048
50TA/TZ 060 

9.0 or 13.5

38TA/FZ-40TY/BZ 060
50TA/TZ 072 and 084 

12.0 or 18.0

38TA/FZ-40TY/BZ 072
38TA/FZ-40TY/TZ 084

Table 2 – Heat pumps

Unit 

Capacity, kW

50TY/YZ 024 

1.5 or 2.0

38TY/BZ-40TY/BZ 024
50TY/YZ 036-048 

3.0

38TY/BZ-40TY/BZ 036-048
50TY/YZ 060 

4.5

38TY/BZ-40TY/BZ 060
50TY/YZ 072 and 084 

6.0

38TY/BZ-40TY/BZ 072 and 084

Supplied with the voltages indicated in the price list, technical 
data, wiring diagrams and applicable manuals.

5 – ELECTRICAL CONNECTIONS

Before the definitive installation of the electric heaters in the 
unit a number of operations must be carried out.

5.1 – Power supply

The electric heater power supply is suitable for connection to 
the unit control and power wiring box and to the general 
disconnect switch of the unit.

The disconnect switch in the cooling only and heat pump units 
is designed to support the current (A) of the components 
connected to it.

Therefore the power supply of the electric heaters must be 
connected downstream of the disconnect switch, as shown in 
the unit wiring diagrams (see Figs. 9, 10 and 11).

Possible connections:
A -  If the electric heater has not been installed and must be 

incorporated, fuses F1 and the power cable section (L1, 
L, L3, N) are sufficient for the maximum power 
consumption in cooling and heating modes.

B -  If the unit has been installed and supplied with the electric 

heater incorporated please check if fuses F1 and the power 
cable section (L1, L, L3, N) are sufficient for the new 
power consumption. Remember that the unit will operate 
in heating mode when the electric heater is installed.

 

Cooling only models = indoor fan plus electric heater 
power consumption

 

Heat pump models = compressor plus indoor and outdoor 
fan plus electric heater power consumption.

Fig. 10

Fig. 11

Legend:
Q1 

-  Unit main disconnect switch (incorporated)

F1 

-  Fuses to be field-supplied by the installer

----- 

 

Wiring in the unit

----- 

 

Field wiring

NOTE: The unit main disconnect switch has been designed to 
support the current (A) of the electric heaters that are 
installed. It is not necessary to change it.

Electric heating

To the unit

Electric heating

To the unit

Electric heating

To the unit

Summary of Contents for 40TZ Series

Page 1: ...50TA TZ TY YZ 40TA TZ TY BZ 38TA FZ TY BZ Electric Heaters Installation instructions NOTE This manual refers to accessories and options with D as the final letter in the ordering code...

Page 2: ...he nearest Carrier office and make a note on the shipping documents To prevent damage and or loss keep all components in their original packaging until they are installed by qualified personnel 3 UNIT...

Page 3: ...e panel Secure the heater as shown in Fig 6 using the screws supplied Fig 6 View of the unit and electric heater 1 Holes and fixing points of the electric heater to the unit with fixing screws Fig 8 T...

Page 4: ...ges indicated in the price list technical data wiring diagrams and applicable manuals 5 ELECTRICAL CONNECTIONS Before the definitive installation of the electric heaters in the unit a number of operat...

Page 5: ...switch A 6 10 10 10 16 230 1 50 16 16 230 3 50 16 16 16 20 400 3 50 R3 electric heater total kW 1 5 3 3 4 5 6 230 1 50 2 3 230 3 50 3 3 4 5 6 These thermal magnetic switches are located in the control...

Page 6: ...temperatures below 50 C NOTE All data applies to packaged units For split system units the data depends on the distance between indoor and outdoor units These cable assemblies must be run from the the...

Page 7: ...mal magnetic switches cables etc In this case only the installation in the panel shown and the electrical connection as shown in the wiring diagram are required If the electric heater is supplied inst...

Page 8: ...ns without notice Printed in the Netherlands on chlorine free paper Fig 20 Wiring diagram for the connection of the electric heaters models 50TA TZ TY YZ 38TA FZ TY BZ 40TA TZ TY BZ To the unit contro...

Reviews: