5.5 – Thermal protection

The electric heater includes two thermal protection devices, 
one with manual reset and the other with automatic reset.

The first one must always remain accessible and both must be 
located in the upper part of the electric heater. Once connected, 
this is in the air discharge of the indoor fan.

NOTE: The heating coil assemblies (accessory/option) can be 
supplied with all required connection parts (thermal-magnetic 
switches, cables etc.). In this case only the installation in the 
panel shown and the electrical connection as shown in the 
wiring diagram are required.

If the electric heater is supplied installed in the unit, no 
additional operation is required, except in split system units 
where the connection cables between the electric heater in the 
indoor units must be run to the power and control box in the 
outdoor unit.

NOTE: This manual refers to accessories and options with 
„D“ as the final letter in the ordering code.

WARNING: The power supply must always meet applicable 
local, national and EU standards.

Fig. 18

Fig. 19

Summary of Contents for 40TZ Series

Page 1: ...50TA TZ TY YZ 40TA TZ TY BZ 38TA FZ TY BZ Electric Heaters Installation instructions NOTE This manual refers to accessories and options with D as the final letter in the ordering code...

Page 2: ...he nearest Carrier office and make a note on the shipping documents To prevent damage and or loss keep all components in their original packaging until they are installed by qualified personnel 3 UNIT...

Page 3: ...e panel Secure the heater as shown in Fig 6 using the screws supplied Fig 6 View of the unit and electric heater 1 Holes and fixing points of the electric heater to the unit with fixing screws Fig 8 T...

Page 4: ...ges indicated in the price list technical data wiring diagrams and applicable manuals 5 ELECTRICAL CONNECTIONS Before the definitive installation of the electric heaters in the unit a number of operat...

Page 5: ...switch A 6 10 10 10 16 230 1 50 16 16 230 3 50 16 16 16 20 400 3 50 R3 electric heater total kW 1 5 3 3 4 5 6 230 1 50 2 3 230 3 50 3 3 4 5 6 These thermal magnetic switches are located in the control...

Page 6: ...temperatures below 50 C NOTE All data applies to packaged units For split system units the data depends on the distance between indoor and outdoor units These cable assemblies must be run from the the...

Page 7: ...mal magnetic switches cables etc In this case only the installation in the panel shown and the electrical connection as shown in the wiring diagram are required If the electric heater is supplied inst...

Page 8: ...ns without notice Printed in the Netherlands on chlorine free paper Fig 20 Wiring diagram for the connection of the electric heaters models 50TA TZ TY YZ 38TA FZ TY BZ 40TA TZ TY BZ To the unit contro...