5.2 – Thermal-magnetic disconnect switch

The following thermal-magnetic disconnect switches must be 
incorporated in the electric heater control box (curve C). The 
current must comply with the capacity (kW) of the electric 
heater installed.

The thermal-magnetic disconnect switches are as follows and 
match the models and capacities of the electric heaters in tables 
3 and 4.

Table 3 – Cooling models

Power 
supply
V-ph-Hz

Letter in wiring 
diagram

50TA/TZ – 38TA/FZ – 40TA/TY/TZ/BZ

024

036

042-
048

060

072

084

400-3-50

F18 thermal-
magnetic switch (A)

16

16

16

25

25

32

230-1-50

25

32

-

-

-

-

230-3-50

-

25

40

-

50

50

400-3-50

R3 electric heater 
total (kW)

6

6
9

6
9

9
13.5

12

18

230-1-50

4

6

-

-

-

-

230-3-50

-

6

9

-

12

18

Table 4 – Heat pumps

Power 
supply
V-ph-Hz

Letter in wiring 
diagram

50TY/YZ – 38TY/BZ – 40TY/BZ

024

036

042-
048

060

072-
084

400-3-50

F18 thermal-
magnetic switch (A)

6

10

10

10

16

230-1-50

16

16

-

-

-

230-3-50

-

16

16

16

20

400-3-50

R3 electric heater 
total (kW)

1.5

3

3

4.5

6

230-1-50

2

3

-

-

-

230-3-50

-

3

3

4.5

6

These thermal-magnetic switches are located in the control box 
of the electric heater, as shown in figures 1 and 13.

Fig. 12

Fig. 13

Thermal switch

Once installed in the control box, they must be connected to 
contactor K8 in accordance with the wiring diagram. Afterwards 
they must be connected to the main unit control box with the 
power supply cables.

5.3 - Power supply cables

This manual refers to packaged units. The power supply cables 
used for split system vary,  units depending on the distance 
between the indoor and outdoor units (maximum voltage loss 
5%). The standard cables for the power supply in packaged 
units are:

Fig. 14 - 230 V single-phase heaters with 2, 3, 4 and 

6 kW capacity

F18 installation site

Dimensions, mm

kW

A

2 and 4

3000

3 and 6

3200

Wire section, mm

kW

L1

N

2 and 3

2.5

2.5

2.5

4

4

4

4

6

6

6

6

Colour code:
L1  = Black
N  = Blue

  = Green/yellow striped

= Flexible pipe, type PG 13.5

Summary of Contents for 40TZ Series

Page 1: ...50TA TZ TY YZ 40TA TZ TY BZ 38TA FZ TY BZ Electric Heaters Installation instructions NOTE This manual refers to accessories and options with D as the final letter in the ordering code...

Page 2: ...he nearest Carrier office and make a note on the shipping documents To prevent damage and or loss keep all components in their original packaging until they are installed by qualified personnel 3 UNIT...

Page 3: ...e panel Secure the heater as shown in Fig 6 using the screws supplied Fig 6 View of the unit and electric heater 1 Holes and fixing points of the electric heater to the unit with fixing screws Fig 8 T...

Page 4: ...ges indicated in the price list technical data wiring diagrams and applicable manuals 5 ELECTRICAL CONNECTIONS Before the definitive installation of the electric heaters in the unit a number of operat...

Page 5: ...switch A 6 10 10 10 16 230 1 50 16 16 230 3 50 16 16 16 20 400 3 50 R3 electric heater total kW 1 5 3 3 4 5 6 230 1 50 2 3 230 3 50 3 3 4 5 6 These thermal magnetic switches are located in the control...

Page 6: ...temperatures below 50 C NOTE All data applies to packaged units For split system units the data depends on the distance between indoor and outdoor units These cable assemblies must be run from the the...

Page 7: ...mal magnetic switches cables etc In this case only the installation in the panel shown and the electrical connection as shown in the wiring diagram are required If the electric heater is supplied inst...

Page 8: ...ns without notice Printed in the Netherlands on chlorine free paper Fig 20 Wiring diagram for the connection of the electric heaters models 50TA TZ TY YZ 38TA FZ TY BZ 40TA TZ TY BZ To the unit contro...

Reviews: