Page 1: ...le com U ˎ Mˊ ˊ 009_027_011_181010_V001_EN AIR HEATERS BURNING GASEOUS FUELS Appliance types GTV E 20A C CL GTV E 27A C CL GTV E 33A C CL GTV E 40A C CL GTV E 48A C CL GTV E 58A C CL GTV E 68A GTV E 87A GTV E 107A ...

Page 2: ...et 9 Electrical connecting specification 9 Regulation possibilities 10 6 A 10 Ventilation 10 Protective distances 11 7 A 11 Start restart 11 Control and regulation of appliance 12 8 M 13 13 Maintenance procedures 13 Gas change 14 9 T 14 14 10 E 15 Enclosure 1 A Appliance performance data 16 Enclosure 1 B Gas consumption 16 Enclosure 2 appliance dimensions per types 16 Enclosure 3 Flue longs allowed...

Page 3: ...reach your gas supplier call the Fire Department The GTV E type warm air blower appliances have been developed and certified in compliance with MSZ EN 1020 standard and quali fied for heating of industrial rooms The function of these heater appliances to ensure heating of appointed workplace temporarily or continuously In case of proper using the appliance guarantees safety and energy saving operati...

Page 4: ... not leave it to grow old Do not use seriously aged equipment any longer Fix the appliance on such stable surface which during operation despite warming of appliance preserves its stability If the appliance is put out of use in every case it must be cut off the current and gas Never block the air supply and exhaust pipes Keep away the children and animals from the equipment Never service mend such ...

Page 5: ... the closest dealer www pakole com and ask for further informa tions ATTENTION COMPULSORY EARTHING ATTENTION ONLY QUALIFIED PERSON CAUTION DANGER CAUTION ELECTRIC SUPPLY According to the installation project install the electric power lines Always make sure that the unit and all its electrical parts have been cor rectly earthed prior starting up the unit CAUTION DANGER ATTENTION ONLY QUALIFIED PER...

Page 6: ...g set until the gas attachment investigate the device if it is not damaged during the transportation if it is damaged in that case notify the retailer from whom the device was bought There is an envelope inside the unit containing the Instructions for Installation and Servicing User s Guide use and Guarantee and ser vices and the warranty documents The appliance operates based on direct heater pri...

Page 7: ...orable conditions for the formation of NOx which are the result of the formation of flame and high flame temperatures and the long residence time of the molecules in the flame during combustion ATTENTION During regular maintenance service technicians must check the status of the NOx reducers physical damage dirt lack of material etc and must measure the value of carbon monoxide emissions If this valu...

Page 8: ...he attached air duct system to the demanded places 4 picture Centrifugal fan type with air duct execution C GTV E CL 5 picture Air duct execution at CL type SOLELY INTERIOR installa on is possible for the sake of appropriate efficiency the position and the high of installation has to be carefully defined the mounting of appliance can be executed by cantilever respectively suspension the appliance has...

Page 9: ...s protection against electric shock for this reason it must be supplied with wired protection against electric shock The appliance must be operated under dry circumstances At electrical installation of appliance the relevant MSZ 2364 standard must be considered For the sake of suitable detachability of appliance from the electrical supply double poles phase null switching off detaching ma in switch...

Page 10: ...er control located in the appliance receives and processes the transmitted control signals from the temperature regulator transmitted by the mentioned control cable and as a function of these signals starts the requested programme Rਤਦ ਫਠਲ਼ਨਮਭ ਯਮਲਲਨਡਨਫਨਲ਼ਨਤਲ A ECO DESIGN EU2016 426 3 GTV E 20 58 W 8 picture Possible regulation mode controlled by AHP 3 type thermostat 9 picture Possible regulation mod...

Page 11: ...ure switch is changed during operation namely switches over from work switched on position to ba sic standstill position in that case the automatic electronic control stops the gas supply by closing of magnetic valves and controls the appliance in error mode moreover the red control lamp located on front side of device is lighting In case the flame detector of automatic burner control does not sens...

Page 12: ...erated by AHP 3 and AHP MOD type temperature regulator which may be purchased at appliance manufacturer In case of using different temperature regulator please contact with the manufacturer in interest of proper installation The control of appliance is performed by temperature regulator room thermostat It can be manually operated or equipped with prog ramme clock according to the request AHP 3 The...

Page 13: ...re at the outlet of solenoid valve check of the condition of pressure regulator check of the protective ground check of the electrical connection check of the exhaust fan and circulating fan check the free rotation of fan and remove the possible contaminations from the impellers supervision of the heat exchanger supervision of working of the temperature controller check of the ignition and ionizat...

Page 14: ...e local authorized representative or a qualified service department Gਠਲ ਢਧਠਭਦਤ ATTENTION This action can only be realized by qualified expert or service ATTENTION If the heater appliance is working than it is prohibited to close the shutters completely There are installed mode indicator lamps on the front side of appliance GREEN operation indicator lamp RED error indicator lamp 11 T T ...

Page 15: ...0 3720 4490 5480 6410 Q 1 1 1 1 1 1 D ΔT C 24 1 24 9 24 5 24 7 25 2 25 A 12 16 18 20 22 25 E Ø100 Ø100 G G1 2 ISO 228 OD E 230V 50H N AVERAGE A 0 9 0 9 1 77 1 77 1 9 1 9 E W 0 21 0 21 0 41 0 41 0 44 0 44 N B A 53 53 55 55 55 57 W 64 86 95 IP IP21 M GTV E 68A GTV E 87A GTV E 107A I NCV W 68 3 54 86 8 68 6 108 1 46 3 O NCV W 63 4 49 5 80 4 62 9 99 8 77 9 E 3 M 92 82 91 6 92 65 91 7 92 3 91 2 A 3 778...

Page 16: ...0 G G1 2 ISO 228 OD E 230V 50H N AVERAGE A 7 9 4 1 7 9 4 1 8 3 5 8 3 5 9 2 6 9 2 6 E W 943 943 1150 1150 1380 1380 N B A 56 58 56 58 58 58 W C 70 93 121 IP CL 75 98 126 IP21 T Input Output Gas consumption 3 L 3 L 3 L 3 L W W N 3 P A GTV E 20 21 16 6 19 4 15 2 2 22 1 76 1 73 1 37 GTV E 27 25 8 20 4 23 9 18 7 2 73 2 16 2 13 1 68 GTV E 33 34 1 26 9 31 5 24 6 3 61 2 85 2 81 2 22 GTV E 40 39 6 31 3 36 ...

Page 17: ...187 GTV E 40A 610 510 625 805 187 GTV E 48A 750 650 625 805 252 GTV E 58A 750 650 625 805 252 Type A a b M e GTV E 20C 470 370 625 990 135 GTV E 27C 470 370 625 990 135 GTV E 33C 610 510 625 1040 187 GTV E 40C 610 510 625 1040 187 GTV E 48C 750 650 625 1110 252 GTV E 58C 750 650 625 1110 252 GTV A 68 107 W 200 200 Type A a b M e GTV E 68A 810 700 840 970 238 GTV E 87A 960 850 840 970 318 GTV E 107...

Page 18: ... a b c d M D e GTV E 20CL 470 350 600 350 500 1050 50 135 GTV E 27CL 470 350 600 350 500 1050 50 135 GTV E 33CL 610 500 600 400 550 1100 50 187 GTV E 40CL 610 500 600 400 550 1100 50 187 GTV E 48CL 750 650 600 450 600 1150 50 252 GTV E 58CL 750 650 600 450 600 1150 50 252 ...

Page 19: ...32 C52 i2H 20 DK EE FI LT LV NO SE i2E 20 LU DE i3P 37 BE FR 50 CY DE i2H3P 20 28 30 BA BG MD RO RU SK UA HR RS 20 37 CH ES GB IE PT SI 20 28 30 37 CZ GR IT 20 50 AT TR i2E3P 20 37 PL i2HS3P 25 28 30 50 HU The appliances were tested together with the flue system recommended by the manufacturer The applied flue system parts LIM MONT ECO DIM DW LIM MONT ECO DIM DE Type GTV E 20A C CL GTV E 27A C CL GT...

Page 20: ...EU 2016 2281 Emission efficiency s flow 93 28 Seasonal space hea ng energy efficiency s h 72 7 Model GTV E 20A C CL MODModulatedIndirectgas firedforcedconvec onairheaterwithaxialfan B1 Warm air heater No C2 Warm air heater No C4 Warm air heater No Type of fuel Gas Item Symbol Value Unit Item Symbol Value Unit Capacity Useful efficiency Rated hea ng capacity Prated h 19 4 kW Useful efficiency at rated hea ng...

Page 21: ...on efficiency s flow 93 27 Seasonal space hea ng energy efficiency s h 72 9 Model GTV E 27A C CL MODModulatedIndirectgas firedforcedconvec onairheaterwithaxialfan B1 Warm air heater No C2 Warm air heater No C4 Warm air heater No Type of fuel Gas Item Symbol Value Unit Item Symbol Value Unit Capacity Useful efficiency Rated hea ng capacity Prated h 23 9 kW Useful efficiency at rated hea ng capacity nom 83 54...

Page 22: ...ciency s flow 92 79 Seasonal space hea ng energy efficiency s h 72 3 Model GTV E 33A C CL MOD Modulated Indirect gas fired forced convec on air heater with axial fan B1 Warm air heater No C2 Warm air heater No C4 Warm air heater No Type of fuel Gas Item Symbol Value Unit Item Symbol Value Unit Capacity Useful efficiency Rated hea ng capacity Prated h 31 5 kW Useful efficiency at rated hea ng capacity nom ...

Page 23: ...fficiency s flow 93 1 Seasonal space hea ng energy efficiency s h 72 6 Model GTV E 40A C CL MOD Modulated Indirect gas fired forced convec on air heater with axial fan B1 Warm air heater No C2 Warm air heater No C4 Warm air heater No Type of fuel Gas Item Symbol Value Unit Item Symbol Value Unit Capacity Useful efficiency Rated hea ng capacity Prated h 36 7 kW Useful efficiency at rated hea ng capacity nom ...

Page 24: ...ency s flow 93 03 Seasonal space hea ng energy efficiency s h 72 4 Model GTV E 48A C CL MOD Modulated Indirect gas fired forced convec on air heater with axial fan B1 Warm air heater No C2 Warm air heater No C4 Warm air heater No Type of fuel Gas Item Symbol Value Unit Item Symbol Value Unit Capacity Useful efficiency Rated hea ng capacity Prated h 45 1 kW Useful efficiency at rated hea ng capacity nom 83...

Page 25: ...ciency s flow 92 91 Seasonal space hea ng energy efficiency s h 72 3 Model GTV E 58A C CL MOD Modulated Indirect gas fired forced convec on air heater with axial fan B1 Warm air heater No C2 Warm air heater No C4 Warm air heater No Type of fuel Gas Item Symbol Value Unit Item Symbol Value Unit Capacity Useful efficiency Rated hea ng capacity Prated h 54 2 kW Useful efficiency at rated hea ng capacity nom ...

Page 26: ...ciency s flow 93 24 Seasonal space hea ng energy efficiency s h 72 9 Model GTV E 68A MOD Modulated Indirect gas fired forced convec on air heater with axial fan B1 Warm air heater No C2 Warm air heater No C4 Warm air heater No Type of fuel Gas Item Symbol Value Unit Item Symbol Value Unit Capacity Useful efficiency Rated hea ng capacity Prated h 63 4 kW Useful efficiency at rated hea ng capacity nom 83 6 ...

Page 27: ...ciency s flow 92 13 Seasonal space hea ng energy efficiency s h 72 1 Model GTV E 87A MOD Modulated Indirect gas fired forced convec on air heater with axial fan B1 Warm air heater No C2 Warm air heater No C4 Warm air heater No Type of fuel Gas Item Symbol Value Unit Item Symbol Value Unit Capacity Useful efficiency Rated hea ng capacity Prated h 80 4 kW Useful efficiency at rated hea ng capacity nom 83 5 ...

Page 28: ...ciency s flow 92 68 Seasonal space hea ng energy efficiency s h 72 2 Model GTV E 107A MOD Modulated Indirect gas fired forced convec on air heater with axial fan B1 Warm air heater No C2 Warm air heater No C4 Warm air heater No Type of fuel Gas Item Symbol Value Unit Item Symbol Value Unit Capacity Useful efficiency Rated hea ng capacity Prated h 99 8 kW Useful efficiency at rated hea ng capacity nom 83 2...

Page 29: ...ce station The regular maintenance is the owner s responsibility The manufacturer does not assume the responsibility in case of accidentally happened or directly caused mistake respectively improper using We reserve the right to change of this specification without extra notification The guarantee can be applied in accordance with above defined Additional guarantee is not accepted Guarantee servicing...

Page 30: ...PAKOLE TRADE LLC H 8000 Székesfehérvár Börgöndi út 8 10 http www pakole com E mail mail pakole hu Tel 36 22 316 484 Fax 36 22 316 074 www pakole com ...