SYSTEM REQUIREMENTS

Allow sufficient space for airflow and servicing unit. See Fig. 3 for
minimum required distances between the unit and the walls or
ceilings.

Piping

IMPORTANT:  Both refrigerant lines must be insulated
separately.

S

  Minimum refrigerant line length between the indoor and outdoor

units is 10 ft. (3 m).

S

  Table 3 lists the pipe sizes for the indoor unit. Refer to the

outdoor unit installation instructions for other allowed piping
lengths and refrigerant information.

Table 3—Piping Lengths

9K

12K

18K

24K

36K

48K

Gas Pipe
(size-connection
type)

In

(mm)

3/8

(9.52)

1/2

(12.7)

1/2

(12.7)

5/8

(16)

5/8

(16)

5/8

(16)

Liquid Pipe
(size-connection
type)

In

(mm)

1/4

(6.35)

1/4

(6.35)

1/4

(6.35)

3/8

(9.52)

3/8

(9.52)

3/8

(9.52)

WIRING

All wires must be sized per NEC (National Electrical Code) or
CEC (Canadian Electrical Code) and local codes. Use the
Electrical Data table MCA (minimum circuit amps) and MOCP
(maximum over current protection) to correctly size the wires and
the disconnect fuse or breakers respectively.
Per caution note, only stranded copper conductors with a 600 volt
rating and double insulated copper wire must be used. The use of
BX cable is not recommended.

Recommended Connection Method for Power and
Communication Wiring − Power and Communication Wiring:
The main power is supplied to the outdoor unit. The field
supplied 14/3 power/communication wiring from the outdoor unit
to the indoor unit consists of four (4) wires and provides the
power for the indoor unit. Two wires are high voltage AC power,
one is communication wiring and the other is a ground wire.

Recommended Connection Method for Power and
Communication Wiring (To minimize communication wiring
interference) Power Wiring:
The main power is supplied to the outdoor unit. The field
supplied power wiring from the outdoor unit to the indoor unit
consists of three (3) wires and provides the power for the indoor
unit. Two wires are high voltage AC power and one is a ground
wire.

To minimize voltage drop, the factory recommended wire size is
14/2 stranded with a ground.

Communication Wiring:
A separate shielded stranded copper conductor only, with a 600
volt rating and double insulated copper wire, must be used as the
communication wire from the outdoor unit to the indoor unit.
Please use a separate shielded 16GA stranded control wire.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment
damage or improper operation.

S

Wires should be sized based on NEC and local codes.

S

Use copper conductors only with a 600 volt rating and 
double insulated copper wire.

Summary of Contents for 40MBD-04SI

Page 1: ...lustration purposes only Actual models may differ slightly TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 CLEARANCES 6 INSTALLATION LOCATION RE...

Page 2: ...ds which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor...

Page 3: ...ard arc in the connection pipe before it enters the wall to the indoor unit This ensures that rain drips from the connection pipe before it enters the wall Piping and the interconnecting wiring are fi...

Page 4: ...on Method for Power and Communication Wiring Power and Communication Wiring The main power is supplied to the outdoor unit The field supplied 14 3 power communication wiring from the outdoor unit to t...

Page 5: ...1 740 13 8 350 4 7 120 5 6 143 3 7 95 5 9 150 39 9 18 1 12 27 6 700 8 2 210 25 635 22 4 570 2 5 65 19 4 493 1 3 35 4 6 119 23 4 595 7 8 200 3 1 80 29 1 740 13 8 350 4 7 120 5 6 143 3 7 95 5 9 150 39...

Page 6: ...pacity Kbtu A B C 9K 27 56 in 70cm 8 27 in 21cm 11 81 in 30cm 12K 27 56 in 70cm 8 27 in 21cm 11 81 in 30cm 18K 36 22 in 92cm 8 27 in 21cm 11 81 in 30cm 24K 36 22 in 92cm 10 63 in 27cm 11 81 in 30cm 36...

Page 7: ...UNIT INSTALLATION CAUTION Be sure that the ceiling grid is supported separately from the unit The ceiling grid must not be supported by any part of the unit or any associated wiring or piping work MO...

Page 8: ...t as possible see Fig 11 S Condensate piping should slope downward in the direction of condensate flow with a minimum gradient of 1 50 S When multiple units are connected to a common condensate drain...

Page 9: ...factory installed drain pump has to be disabled place a Jumper field supplied on the Pin CN5 WATER connector and disconnect the Pin CN13 PUMP see Fig 15 Add Jumper Pin CN5 WATER Disconnect Pin CN13 P...

Page 10: ...40 0 0 18 0 45 18 0 04 10 0 10 25 0 14 35 0 18 45 0 22 55 0 0 28 0 70 24 0 04 10 0 10 25 0 16 40 0 22 55 0 28 70 0 0 40 0 100 36 48 0 08 20 0 14 35 0 20 50 0 26 65 0 32 80 0 0 40 0 100 Factory Setting...

Page 11: ...11 STATIC PRESSURE CURVES SIZE 9...

Page 12: ...12 STATIC PRESSURE CURVES SIZE 12...

Page 13: ...13 STATIC PRESSURE CURVES SIZE 18...

Page 14: ...14 STATIC PRESSURE CURVES SIZE 24...

Page 15: ...15 STATIC PRESSURE CURVES SIZE 36...

Page 16: ...16 STATIC PRESSURE CURVES SIZE 48...

Page 17: ...36 1 26 0 20 150 48 2 23 0 32 240 LEGEND FLA Full Load Amps CONNECTION DIAGRAMS A150687 Fig 16 Connection Diagrams 9 12 18 and 24 A150688 Fig 17 Connection Diagrams 36 and 48 A150641 Fig 18 Control a...

Page 18: ...Nut Spacing OUTER DIAM mm A mm Max Min 1 4 6 35 0 05 1 3 0 03 0 7 3 8 9 52 0 06 1 6 0 04 1 0 1 2 12 7 0 07 1 8 0 04 1 0 5 8 15 88 0 09 2 2 0 08 2 0 Bar Copper pipe Clamp handle Red arrow mark Cone Yok...

Page 19: ...relocate the infrared IR receiver within line of sight of remote location using the 6 ft 1 82 m cable included The factory location of the IR receiver is inside the control box see Fig 23 A150642 Fig...

Page 20: ...the indoor unit 1 Open front panel of the indoor unit 2 Push the manual switch once to energize the unit The set conditions of manual operation are as follows Preset set point 76_F 24_C Fan speed AUT...

Page 21: ...H 4 times X E3 Indoor fan speed has been out of control H 5 times X E4 Indoor room temperature sensor T1 open circuit or short circuit H 6 times X E5 Evaporator coil temperature sensor T2 open circuit...

Page 22: ...ration S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MBD 06SI Replaces...

Reviews: