background image

18

INSTALL ALL POWER, INTERCONNECTING
WIRING, AND PIPING TO INDOOR UNIT

1. Run interconnecting piping and wiring from the outdoor

unit to the indoor unit.

2. Connect wiring from outdoor unit per the connection

diagram (see Fig. 16 and Fig. 17).

3. Replace field wiring cover of the indoor unit.

4. Connect refrigerant piping and drain line outside of indoor

unit. Complete pipe insulation at flare connection then
fasten piping and wiring to the wall as required.
Completely seal the hole in the wall.

5. Piping:

a. Cut the pipe, with a pipe cutter, at 90 degrees (see Fig. 19).

b. Remove the service connection, if provided with the unit.

Oblique

DŽ

90

Roughness

Burr

A150767

Fig. 19

 - 

Pipe Cutting

c. Remove all the burrs from the cut cross section of the pipe

avoiding any burrs inside the tubes.

d. Remove the flare nuts attached to the indoor and outdoor

units.

e. Install the correct size flare nut onto the tubing and make

the flare connection. Refer to Table 9 for the flare nut
spaces.

Table 9—Flare Nut Spacing

OUTER DIAM. (mm)

A (mm)

Max.

Min.

Ø

 

1/4

(

6.3

5)

0.05 (1.3)

0.03 (0.7)

Ø

 3

/

8" 

(9

.

52)

0.06 (1.6)

0.04 (1.0)

Ø

 

1/2

(12

.7

)

0.07 (1.8)

0.04 (1.0)

Ø 5/8" (15.88)

0.09 (2.2)

0.08 (2.0)

Bar

Copper pipe

Clamp handle

Red arrow mark

Cone

Yoke

Handle

Bar

"

A

"

A150768

Fig. 20

 - 

Flare Nut Spacing

f. Apply a small amount of refrigerant oil to the flare

connection on the tubing.

g. Align center of the pipes and/or service valve.

Indoor unit tubing

Flare nut

Piping

A150769

Fig. 21

 - 

Align Pipe Center

h. Connect both the liquid and gas piping to the indoor unit

i. Tighten the flare nut using a torque wrench as specified in

Table 10.

Table 10—Tightening Torque

PIPE DIAMETER INCH

(mm)

TIGHTENING TORQUE

Ft-lb

N-m

Ø1/4

” 

(

6.3

5)

10 to 13

13.6 to 17.6

Ø

3

/

8” 

(9

.

52)

24 to 31

32.5 to 42.0

Ø1/2

” 

(12

.7

)

37 to 46

50.1 to 62.3

Ø5/

8” 

(15

.88

)

50 to 60

67.7 to 81.3

Flare nut

Copper tube

A150770

Fig. 22

 - 

Tighten the Flare Nut

6. Connect the drain line. The drain line must not have a trap

anywhere in its length, must pitch downwards, and must be
insulated up to the outside wall.

NOTE:  For applications where gravity cannot be used for
drainage, a condensate pump accessory is available. Consult the
condensate pump Installation Instructions for more information.

Summary of Contents for 40MBD-04SI

Page 1: ...lustration purposes only Actual models may differ slightly TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 CLEARANCES 6 INSTALLATION LOCATION RE...

Page 2: ...ds which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor...

Page 3: ...ard arc in the connection pipe before it enters the wall to the indoor unit This ensures that rain drips from the connection pipe before it enters the wall Piping and the interconnecting wiring are fi...

Page 4: ...on Method for Power and Communication Wiring Power and Communication Wiring The main power is supplied to the outdoor unit The field supplied 14 3 power communication wiring from the outdoor unit to t...

Page 5: ...1 740 13 8 350 4 7 120 5 6 143 3 7 95 5 9 150 39 9 18 1 12 27 6 700 8 2 210 25 635 22 4 570 2 5 65 19 4 493 1 3 35 4 6 119 23 4 595 7 8 200 3 1 80 29 1 740 13 8 350 4 7 120 5 6 143 3 7 95 5 9 150 39...

Page 6: ...pacity Kbtu A B C 9K 27 56 in 70cm 8 27 in 21cm 11 81 in 30cm 12K 27 56 in 70cm 8 27 in 21cm 11 81 in 30cm 18K 36 22 in 92cm 8 27 in 21cm 11 81 in 30cm 24K 36 22 in 92cm 10 63 in 27cm 11 81 in 30cm 36...

Page 7: ...UNIT INSTALLATION CAUTION Be sure that the ceiling grid is supported separately from the unit The ceiling grid must not be supported by any part of the unit or any associated wiring or piping work MO...

Page 8: ...t as possible see Fig 11 S Condensate piping should slope downward in the direction of condensate flow with a minimum gradient of 1 50 S When multiple units are connected to a common condensate drain...

Page 9: ...factory installed drain pump has to be disabled place a Jumper field supplied on the Pin CN5 WATER connector and disconnect the Pin CN13 PUMP see Fig 15 Add Jumper Pin CN5 WATER Disconnect Pin CN13 P...

Page 10: ...40 0 0 18 0 45 18 0 04 10 0 10 25 0 14 35 0 18 45 0 22 55 0 0 28 0 70 24 0 04 10 0 10 25 0 16 40 0 22 55 0 28 70 0 0 40 0 100 36 48 0 08 20 0 14 35 0 20 50 0 26 65 0 32 80 0 0 40 0 100 Factory Setting...

Page 11: ...11 STATIC PRESSURE CURVES SIZE 9...

Page 12: ...12 STATIC PRESSURE CURVES SIZE 12...

Page 13: ...13 STATIC PRESSURE CURVES SIZE 18...

Page 14: ...14 STATIC PRESSURE CURVES SIZE 24...

Page 15: ...15 STATIC PRESSURE CURVES SIZE 36...

Page 16: ...16 STATIC PRESSURE CURVES SIZE 48...

Page 17: ...36 1 26 0 20 150 48 2 23 0 32 240 LEGEND FLA Full Load Amps CONNECTION DIAGRAMS A150687 Fig 16 Connection Diagrams 9 12 18 and 24 A150688 Fig 17 Connection Diagrams 36 and 48 A150641 Fig 18 Control a...

Page 18: ...Nut Spacing OUTER DIAM mm A mm Max Min 1 4 6 35 0 05 1 3 0 03 0 7 3 8 9 52 0 06 1 6 0 04 1 0 1 2 12 7 0 07 1 8 0 04 1 0 5 8 15 88 0 09 2 2 0 08 2 0 Bar Copper pipe Clamp handle Red arrow mark Cone Yok...

Page 19: ...relocate the infrared IR receiver within line of sight of remote location using the 6 ft 1 82 m cable included The factory location of the IR receiver is inside the control box see Fig 23 A150642 Fig...

Page 20: ...the indoor unit 1 Open front panel of the indoor unit 2 Push the manual switch once to energize the unit The set conditions of manual operation are as follows Preset set point 76_F 24_C Fan speed AUT...

Page 21: ...H 4 times X E3 Indoor fan speed has been out of control H 5 times X E4 Indoor room temperature sensor T1 open circuit or short circuit H 6 times X E5 Evaporator coil temperature sensor T2 open circuit...

Page 22: ...ration S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MBD 06SI Replaces...

Reviews: