background image

20

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment
damage or improper operation.

Never use the system compressor as a vacuum pump.

CAUTION

!

Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used if the procedure outlined
below is followed. Always break a vacuum with dry nitrogen.

Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.

START−UP

Test Operation

Perform test operation after completing gas leak and electrical
safety check (see Fig. 24).

A150643

Fig. 24

 - 

Test Operation

1. Press the MANUAL button on the IR receiver located in

the control box to begin testing.

NOTE:  A protection feature prevents air conditioner from being
activated for approximately 3 to 4 minutes.

2. Push  MODE, select COOLING,  HEATING,  FAN  mode

to check if all functions work correctly.

3. To run the test using the manual button in the indoor unit:

(1.) Open front panel of the indoor unit;

(2.) Push the manual switch once to energize the unit.

The set conditions of manual operation are as
follows:
· Preset set point: 76

_

F (24

_

C)

· Fan speed: AUTO
· Discharge air direction: Pre−set position based on
   operation in “Cool” or “Heat” mode.

4. Be sure to set the manual switch to “OFF” (by pushing it

twice again) after finishing the test operation.

SYSTEM CHECKS

1. Conceal the tubing where possible.

2. Make sure that the drain tube slopes downward along its

entire length.

3. Ensure all tubing and connections are properly insulated.

4. Fasten tubes to the outside wall, when possible.

5. Seal the hole through which the cables and tubing pass.

INDOOR UNIT

1. Do all remote control buttons function properly?

2. Do the display panel lights work properly?

3. Does the air deflection louver function properly?

4. Does the drain work?

Explain Following Items To Customer (with the aid of the
Owner’s Manual):

1. How to turn air conditioner on and off; selecting

COOLINGHEATING and other operating modes;
setting a desired temperature; setting the timer to
automatically start and stop air conditioner operation; and
all other features of the remote control and display panel.

2. How to remove and clean the air filter.

3. How to set air deflection louver.

4. Explain care and maintenance.

5. Present the owner’s manual and installation instructions to

customer.

Summary of Contents for 40MBD-04SI

Page 1: ...lustration purposes only Actual models may differ slightly TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 CLEARANCES 6 INSTALLATION LOCATION RE...

Page 2: ...ds which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor...

Page 3: ...ard arc in the connection pipe before it enters the wall to the indoor unit This ensures that rain drips from the connection pipe before it enters the wall Piping and the interconnecting wiring are fi...

Page 4: ...on Method for Power and Communication Wiring Power and Communication Wiring The main power is supplied to the outdoor unit The field supplied 14 3 power communication wiring from the outdoor unit to t...

Page 5: ...1 740 13 8 350 4 7 120 5 6 143 3 7 95 5 9 150 39 9 18 1 12 27 6 700 8 2 210 25 635 22 4 570 2 5 65 19 4 493 1 3 35 4 6 119 23 4 595 7 8 200 3 1 80 29 1 740 13 8 350 4 7 120 5 6 143 3 7 95 5 9 150 39...

Page 6: ...pacity Kbtu A B C 9K 27 56 in 70cm 8 27 in 21cm 11 81 in 30cm 12K 27 56 in 70cm 8 27 in 21cm 11 81 in 30cm 18K 36 22 in 92cm 8 27 in 21cm 11 81 in 30cm 24K 36 22 in 92cm 10 63 in 27cm 11 81 in 30cm 36...

Page 7: ...UNIT INSTALLATION CAUTION Be sure that the ceiling grid is supported separately from the unit The ceiling grid must not be supported by any part of the unit or any associated wiring or piping work MO...

Page 8: ...t as possible see Fig 11 S Condensate piping should slope downward in the direction of condensate flow with a minimum gradient of 1 50 S When multiple units are connected to a common condensate drain...

Page 9: ...factory installed drain pump has to be disabled place a Jumper field supplied on the Pin CN5 WATER connector and disconnect the Pin CN13 PUMP see Fig 15 Add Jumper Pin CN5 WATER Disconnect Pin CN13 P...

Page 10: ...40 0 0 18 0 45 18 0 04 10 0 10 25 0 14 35 0 18 45 0 22 55 0 0 28 0 70 24 0 04 10 0 10 25 0 16 40 0 22 55 0 28 70 0 0 40 0 100 36 48 0 08 20 0 14 35 0 20 50 0 26 65 0 32 80 0 0 40 0 100 Factory Setting...

Page 11: ...11 STATIC PRESSURE CURVES SIZE 9...

Page 12: ...12 STATIC PRESSURE CURVES SIZE 12...

Page 13: ...13 STATIC PRESSURE CURVES SIZE 18...

Page 14: ...14 STATIC PRESSURE CURVES SIZE 24...

Page 15: ...15 STATIC PRESSURE CURVES SIZE 36...

Page 16: ...16 STATIC PRESSURE CURVES SIZE 48...

Page 17: ...36 1 26 0 20 150 48 2 23 0 32 240 LEGEND FLA Full Load Amps CONNECTION DIAGRAMS A150687 Fig 16 Connection Diagrams 9 12 18 and 24 A150688 Fig 17 Connection Diagrams 36 and 48 A150641 Fig 18 Control a...

Page 18: ...Nut Spacing OUTER DIAM mm A mm Max Min 1 4 6 35 0 05 1 3 0 03 0 7 3 8 9 52 0 06 1 6 0 04 1 0 1 2 12 7 0 07 1 8 0 04 1 0 5 8 15 88 0 09 2 2 0 08 2 0 Bar Copper pipe Clamp handle Red arrow mark Cone Yok...

Page 19: ...relocate the infrared IR receiver within line of sight of remote location using the 6 ft 1 82 m cable included The factory location of the IR receiver is inside the control box see Fig 23 A150642 Fig...

Page 20: ...the indoor unit 1 Open front panel of the indoor unit 2 Push the manual switch once to energize the unit The set conditions of manual operation are as follows Preset set point 76_F 24_C Fan speed AUT...

Page 21: ...H 4 times X E3 Indoor fan speed has been out of control H 5 times X E4 Indoor room temperature sensor T1 open circuit or short circuit H 6 times X E5 Evaporator coil temperature sensor T2 open circuit...

Page 22: ...ration S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MBD 06SI Replaces...

Reviews: