background image

7

INSTALLATION LOCATION
REQUIREMENTS

Indoor Unit

S

  Confirm that the ceiling is able to support the weight of the unit.

S

  There should be enough room within the false ceiling for

installation and maintenance.

S

  The false ceiling should be horizontal and leveled.

S

  Install the unit in a location within the room that allows uniform

air flow in all directions.

S

  Do not install the indoor units near a direct source of heat such as

direct sunlight or a heating appliance.

S

  A location which provides appropriate clearances.

S

  Ensure the hanger is strong enough to withstand the unit’s weight.

Indoor and Outdoor Units (General)

S

  Ensure space is left for access for maintenance.

S

  Location should be far away from where there is a heat source,

leakage of any inflammable, explosive substances, or smog.

S

  All wiring and refrigerant lines must be at least 3 ft. (1m) away

from sources of electromagnetic interference (such as televisions,
radios, etc.). Interference is still possible even if this distance is
maintained.

S

  Do not install the indoor or outdoor units in a location with

special environmental conditions. For those applications, contact
your Ductless representative.

INDOOR UNIT INSTALLATION

INDOOR DUCTED UNIT INSTALLATION

CAUTION

!

Be sure that the ceiling grid is supported separately from
the unit.

The ceiling grid must not be supported by any part of the
unit or any associated wiring or piping work.

MOUNTING THE UNIT

1. INSTALLING HANGER BOLTS − Install the hanger bolts

at the locations (see Fig. 4, top view). Use Ø10 / Ø0.394in
all−threaded rod.

A150664

Fig. 4

 - 

Install the Hanger Bolts

2. The unit can now be lifted on to the hanging rods for

mounting.

3. Use rods and fasteners to suspend the unit at the factory

provided mounting holes.

4. Adjust the unit’s height until the bottom is level with the false

ceiling, with adequate space to provide enough pitch for the
drain.

5. Secure the unit in position with lock nuts and washers on

both sides of the mounting bracket. Ensure the threaded
rod does not extend more than 2 in. below the mounting
brackets (see Fig. 5).

A150665

Fig. 5

 - 

Secure the Unit

RETURN AIR ARRANGEMENT

Based on the return air arrangement requirement in the field, the
unit can be modified from the rear return to the bottom return.

1. Remove the return air duct collar/filter rack and plenum

bottom panel.

A150666

Fig. 6

 - 

Remove the Return Air Duct Collar

2. Install the Seal Sponge on the bottom inlet.

A150667

Fig. 7

 - 

Install the Seal Sponge

3. Swap the position to change the rear return to bottom return

arrangement installing the Air Return flange and the filters.

A150668

Fig. 8

 - 

Change the Rear Return

Summary of Contents for 40MBD-04SI

Page 1: ...lustration purposes only Actual models may differ slightly TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 CLEARANCES 6 INSTALLATION LOCATION RE...

Page 2: ...ds which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor...

Page 3: ...ard arc in the connection pipe before it enters the wall to the indoor unit This ensures that rain drips from the connection pipe before it enters the wall Piping and the interconnecting wiring are fi...

Page 4: ...on Method for Power and Communication Wiring Power and Communication Wiring The main power is supplied to the outdoor unit The field supplied 14 3 power communication wiring from the outdoor unit to t...

Page 5: ...1 740 13 8 350 4 7 120 5 6 143 3 7 95 5 9 150 39 9 18 1 12 27 6 700 8 2 210 25 635 22 4 570 2 5 65 19 4 493 1 3 35 4 6 119 23 4 595 7 8 200 3 1 80 29 1 740 13 8 350 4 7 120 5 6 143 3 7 95 5 9 150 39...

Page 6: ...pacity Kbtu A B C 9K 27 56 in 70cm 8 27 in 21cm 11 81 in 30cm 12K 27 56 in 70cm 8 27 in 21cm 11 81 in 30cm 18K 36 22 in 92cm 8 27 in 21cm 11 81 in 30cm 24K 36 22 in 92cm 10 63 in 27cm 11 81 in 30cm 36...

Page 7: ...UNIT INSTALLATION CAUTION Be sure that the ceiling grid is supported separately from the unit The ceiling grid must not be supported by any part of the unit or any associated wiring or piping work MO...

Page 8: ...t as possible see Fig 11 S Condensate piping should slope downward in the direction of condensate flow with a minimum gradient of 1 50 S When multiple units are connected to a common condensate drain...

Page 9: ...factory installed drain pump has to be disabled place a Jumper field supplied on the Pin CN5 WATER connector and disconnect the Pin CN13 PUMP see Fig 15 Add Jumper Pin CN5 WATER Disconnect Pin CN13 P...

Page 10: ...40 0 0 18 0 45 18 0 04 10 0 10 25 0 14 35 0 18 45 0 22 55 0 0 28 0 70 24 0 04 10 0 10 25 0 16 40 0 22 55 0 28 70 0 0 40 0 100 36 48 0 08 20 0 14 35 0 20 50 0 26 65 0 32 80 0 0 40 0 100 Factory Setting...

Page 11: ...11 STATIC PRESSURE CURVES SIZE 9...

Page 12: ...12 STATIC PRESSURE CURVES SIZE 12...

Page 13: ...13 STATIC PRESSURE CURVES SIZE 18...

Page 14: ...14 STATIC PRESSURE CURVES SIZE 24...

Page 15: ...15 STATIC PRESSURE CURVES SIZE 36...

Page 16: ...16 STATIC PRESSURE CURVES SIZE 48...

Page 17: ...36 1 26 0 20 150 48 2 23 0 32 240 LEGEND FLA Full Load Amps CONNECTION DIAGRAMS A150687 Fig 16 Connection Diagrams 9 12 18 and 24 A150688 Fig 17 Connection Diagrams 36 and 48 A150641 Fig 18 Control a...

Page 18: ...Nut Spacing OUTER DIAM mm A mm Max Min 1 4 6 35 0 05 1 3 0 03 0 7 3 8 9 52 0 06 1 6 0 04 1 0 1 2 12 7 0 07 1 8 0 04 1 0 5 8 15 88 0 09 2 2 0 08 2 0 Bar Copper pipe Clamp handle Red arrow mark Cone Yok...

Page 19: ...relocate the infrared IR receiver within line of sight of remote location using the 6 ft 1 82 m cable included The factory location of the IR receiver is inside the control box see Fig 23 A150642 Fig...

Page 20: ...the indoor unit 1 Open front panel of the indoor unit 2 Push the manual switch once to energize the unit The set conditions of manual operation are as follows Preset set point 76_F 24_C Fan speed AUT...

Page 21: ...H 4 times X E3 Indoor fan speed has been out of control H 5 times X E4 Indoor room temperature sensor T1 open circuit or short circuit H 6 times X E5 Evaporator coil temperature sensor T2 open circuit...

Page 22: ...ration S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MBD 06SI Replaces...

Reviews: