Carrier 40MBC/38MAQ Installation Instructions Manual Download Page 3

3

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air--conditioning equipment
can be hazardous due to system pressures, electrical components,

and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should

install, start--up, and service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning coils. All other operations should be performed by

trained service personnel.
When working on the equipment, observe precautions in the

literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep

quenching cloth and fire extinguisher nearby when brazing. Use
care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or
cautions included in literature and attached to the unit. Consult

local building codes and National Electrical Code (NEC) for

special requirements. Recognize safety information. This is the
safety--alert symbol

!

!

. When you see this symbol on the unit and

in instructions or manuals, be alert to the potential for personal

injury. Understand these signal words: DANGER, WARNING,
and CAUTION. These words are used with the safety--alert

symbol. DANGER identifies the most serious hazards which

will

result in severe personal injury or death. WARNING signifies

hazards which

could

result in personal injury or death. CAUTION

is used to identify unsafe practices which

may

result in minor

personal injury or product and property damage. NOTE is used to

highlight suggestions which

will

result in enhanced installation,

reliability, or operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF

position. There may be more than 1 disconnect switch.

Lock out and tag switch with a suitable warning label.

EXPLOSION HAZARD

Failure to follow this warning could

result in death, serious personal injury,

and/or property damage.
Never use air or gases containing

oxygen for leak testing or operating

refrigerant compressors. Pressurized

mixtures of air or gases containing

oxygen can lead to an explosion.

!

WARNING

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe

in the ground. If any section of pipe is buried, there must be

a 6 in. (152 mm) vertical rise to the valve connections on

the outdoor units. If more than the recommended length is

buried, refrigerant may migrate to the cooler buried section

during extended periods of system shutdown. This causes

refrigerant slugging and could possibly damage the

compressor at start--up.

Summary of Contents for 40MBC/38MAQ

Page 1: ...TENTS PAGE PARTS LIST 2 SAFETY CONSIDERATIONS 3 SYSTEM REQUIREMENTS 4 DIMENSIONS 5 CLEARANCES 7 INSTALLATION TIPS 9 INDOOR UNIT INSTALLATION 9 OUTDOOR UNIT INSTALLATION 15 INSTALL ALL POWER AND INTERC...

Page 2: ...r unit along the connection pipe by creating a downward arc in the connection pipe before it enters the wall to the indoor unit This will ensure that rain drips from the connection pipe before enterin...

Page 3: ...ds which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor...

Page 4: ...lectrical Data table MCA minimum circuit amps and MOCP maximum over current protection to correctly size the wires and the disconnect fuse or breakers respectively Per the caution note only stranded c...

Page 5: ...570 25 47 647 Depth in mm 22 44 570 25 47 647 22 44 570 25 47 647 22 44 570 25 47 647 Packing Height in mm 11 42 290 4 84 123 11 42 290 4 84 123 11 42 290 4 84 123 Width in mm 25 79 655 28 15 715 25...

Page 6: ...door Unit Table 3 Dimensions Outdoor MODEL W in mm D in mm H in mm L1 in mm L2 in mm OPERATING WEIGHT lb kg 9K 12K 32 0 810 12 2 310 22 0 558 20 9 530 11 4 290 82 5 37 4 18K 32 3 845 12 6 320 27 6 700...

Page 7: ...7 CLEARANCES INDOOR Fig 4 Cassette Unit Clearance...

Page 8: ...8 CLEARANCES OUTDOOR A D B Air outlet Air inlet C E A07894 Fig 5 Outdoor Unit Clearance Table 4 Outdoor Unit Clearance Dimensions UNIT MINIMUM VALUE in mm A 24 610 B 24 610 C 24 610 D 4 101 E 4 101...

Page 9: ...lated water can drain easily away from the outdoor unit 6 Ensure there is enough space for care and maintenance Ensure the height between the indoor unit and ground is 3ft 1mt or 16ft 5mt 7 Check if t...

Page 10: ...component kit and branch duct before installing the unit 3 Install the indoor unit temporarily a Attach the hanger bracket to the suspension bolt Be sure to fix it securely by using a nut and washer...

Page 11: ...o spots to prevent any possible water leakage due to dew condensation 1 Indoor drain pipe 2 Drain socket DRAINAGE HOSE IMPORTANT Observe all local sanitary codes when installing condensate drains 1 In...

Page 12: ...cess if several drain hoses join together Fig 21 Slant Gradient 2 Check the smoothness of the drain after the installation 3 Check the drain state by draining 36 3 5 in 3 600 cc of water slowly from t...

Page 13: ...the unit with the supplied screws see Fig 26 1 Decoration panel 2 Screws M5 supplied with the panel 1 2 Fig 26 Attach the Decoration Panel 3 After installing the decoration panel ensure there is no sp...

Page 14: ...nected to Control Board Grille Louver Motor Power 5 Pin Molex plug to be connected to Control Board Grille Louver Motor Power 5 Pin Port Grille Display 10 Pin Port Fig 30 Panel Cassette 6 Fasten the c...

Page 15: ...tion on the tubing 5 Properly align the tubing with the service valve 6 Tighten the flare nut to proper torque value see Table 5 and finish the installation using backup wrenches see Fig 34 A07354 Fig...

Page 16: ...ctorily LEGEND FLA Full Load Amps MCA Minimum Circuit Amps RLA Rated Load Amps CONNECTION DIAGRAMS A150634 Fig 36 Connection Diagrams Notes 1 Do not use thermostat wire for any connection between indo...

Page 17: ...cified in the System Requirements section 8 Disconnect the charge hose from the charge connection of the low side service valve 9 Fully open service valves B and A 10 Securely tighten the service valv...

Page 18: ...lows Preset set point 76_F 24_C Fan speed AUTO Discharge air direction Pre set position based on operation in Cool or Heat mode 4 Be sure to set the manual switch to OFF by pressing it twice again aft...

Page 19: ...s O F2 Open circuit or short circuit of condenser coil temperature sensor T3 4 times O F3 Open circuit or short circuit of Compressor discharge temperature sensor T5 5 times O F4 Outdoor unit EEPROM e...

Page 20: ...ion S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MBC 38MAQ 02SI Repla...

Reviews: