background image

11

DRAIN PIPING WORK

Drain Piping Installation

Install the drain piping as shown in Fig. 14 and take steps to

eliminate condensation. Improperly rigged piping could lead to
leaks and eventually wet furniture and belongings.

Fig. 14

---

Drain Piping Installation

™

Fig. 15

---

Hanging Bar

(1.) Hanging bar
(2.)

1/100 gradient

Install the Drain Pipes

S

Keep piping as short as possible and slope it downwards
at a gradient of at least 1/100 so that air does not remain

trapped inside the pipe.

S

Keep the pipe size equal to or greater than that of the
connecting pipe (PVC pipe, nominal diameter 0.79 in.

(20mm)), outside diameter 0.98 in. (25mm).

S

Push the drain hose as far as possible over the drain
socket, and tighten the metal clamp securely.

Fig. 16

---

Push the Drain Hose

7. Remove the paper pattern for installation (for new ceilings

only).

(1.) Drain socket (attached to the unit)
(2.) Metal clamp
(3.) Drain hose
(4.) Insulation (field supply)

a. Insulate the drain hose inside the building.

b. If the drain hose cannot be sufficiently set on a slope, fit

the hose with the drain raising piping (field supplied).

c. Ensure the heat insulation work is executed on the

following two spots to prevent any possible water
leakage due to dew condensation:

(1.) Indoor drain pipe
(2.) Drain socket.

DRAINAGE HOSE

IMPORTANT

: Observe all local sanitary codes when installing

condensate drains.

1. Install the drain hose.

S

The drain hose diameter should be equal or larger than the
connection pipe’s. The diameter of the polythene pipe:
Outer diameter 1 in. (25 mm) Surface thickness

0.06 in.

(1.5 mm).

S

The drain hose should be short and the drooping gradient
should be less than 1/100 to prevent the formation of an
air bubble. If the drain hose does not has enough of a

drooping gradient, a drain raising pipe should be added.

S

To prevent a bend in the drain hose, the distance between
the hoisting stand should be 3 to 5 ft. (1 to 1.5 m) (see

Fig. 17).

Fig. 17

---

Drain Hose

S

Use the drain hose and clamp attached. Insert the drain
hose into the drain vent, and then tighten the clamp.

S

Entwine the big sponge on the drain hose clamp to
insulate heat.

S

Heat insulation should be applied to the indoor drain
hose.

Sponge(attachment)

Clamp(attachment)

Below 

1/6 in (4 mm)

Clamp

 Drain hose

Sponge (gray)

Fig. 18

---

Drain Hose

NOTE

: Drain Setup pipe

S

The install height of the drain raising pipe should be less
than 21 in. (530 mm).

S

The drain raising pipe should form a right angle with the
unit, and the distance to the unit should not exceed 11.81
in. (300 mm).

Summary of Contents for 40MBC/38MAQ

Page 1: ...TENTS PAGE PARTS LIST 2 SAFETY CONSIDERATIONS 3 SYSTEM REQUIREMENTS 4 DIMENSIONS 5 CLEARANCES 7 INSTALLATION TIPS 9 INDOOR UNIT INSTALLATION 9 OUTDOOR UNIT INSTALLATION 15 INSTALL ALL POWER AND INTERC...

Page 2: ...r unit along the connection pipe by creating a downward arc in the connection pipe before it enters the wall to the indoor unit This will ensure that rain drips from the connection pipe before enterin...

Page 3: ...ds which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor...

Page 4: ...lectrical Data table MCA minimum circuit amps and MOCP maximum over current protection to correctly size the wires and the disconnect fuse or breakers respectively Per the caution note only stranded c...

Page 5: ...570 25 47 647 Depth in mm 22 44 570 25 47 647 22 44 570 25 47 647 22 44 570 25 47 647 Packing Height in mm 11 42 290 4 84 123 11 42 290 4 84 123 11 42 290 4 84 123 Width in mm 25 79 655 28 15 715 25...

Page 6: ...door Unit Table 3 Dimensions Outdoor MODEL W in mm D in mm H in mm L1 in mm L2 in mm OPERATING WEIGHT lb kg 9K 12K 32 0 810 12 2 310 22 0 558 20 9 530 11 4 290 82 5 37 4 18K 32 3 845 12 6 320 27 6 700...

Page 7: ...7 CLEARANCES INDOOR Fig 4 Cassette Unit Clearance...

Page 8: ...8 CLEARANCES OUTDOOR A D B Air outlet Air inlet C E A07894 Fig 5 Outdoor Unit Clearance Table 4 Outdoor Unit Clearance Dimensions UNIT MINIMUM VALUE in mm A 24 610 B 24 610 C 24 610 D 4 101 E 4 101...

Page 9: ...lated water can drain easily away from the outdoor unit 6 Ensure there is enough space for care and maintenance Ensure the height between the indoor unit and ground is 3ft 1mt or 16ft 5mt 7 Check if t...

Page 10: ...component kit and branch duct before installing the unit 3 Install the indoor unit temporarily a Attach the hanger bracket to the suspension bolt Be sure to fix it securely by using a nut and washer...

Page 11: ...o spots to prevent any possible water leakage due to dew condensation 1 Indoor drain pipe 2 Drain socket DRAINAGE HOSE IMPORTANT Observe all local sanitary codes when installing condensate drains 1 In...

Page 12: ...cess if several drain hoses join together Fig 21 Slant Gradient 2 Check the smoothness of the drain after the installation 3 Check the drain state by draining 36 3 5 in 3 600 cc of water slowly from t...

Page 13: ...the unit with the supplied screws see Fig 26 1 Decoration panel 2 Screws M5 supplied with the panel 1 2 Fig 26 Attach the Decoration Panel 3 After installing the decoration panel ensure there is no sp...

Page 14: ...nected to Control Board Grille Louver Motor Power 5 Pin Molex plug to be connected to Control Board Grille Louver Motor Power 5 Pin Port Grille Display 10 Pin Port Fig 30 Panel Cassette 6 Fasten the c...

Page 15: ...tion on the tubing 5 Properly align the tubing with the service valve 6 Tighten the flare nut to proper torque value see Table 5 and finish the installation using backup wrenches see Fig 34 A07354 Fig...

Page 16: ...ctorily LEGEND FLA Full Load Amps MCA Minimum Circuit Amps RLA Rated Load Amps CONNECTION DIAGRAMS A150634 Fig 36 Connection Diagrams Notes 1 Do not use thermostat wire for any connection between indo...

Page 17: ...cified in the System Requirements section 8 Disconnect the charge hose from the charge connection of the low side service valve 9 Fully open service valves B and A 10 Securely tighten the service valv...

Page 18: ...lows Preset set point 76_F 24_C Fan speed AUTO Discharge air direction Pre set position based on operation in Cool or Heat mode 4 Be sure to set the manual switch to OFF by pressing it twice again aft...

Page 19: ...s O F2 Open circuit or short circuit of condenser coil temperature sensor T3 4 times O F3 Open circuit or short circuit of Compressor discharge temperature sensor T5 5 times O F4 Outdoor unit EEPROM e...

Page 20: ...ion S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MBC 38MAQ 02SI Repla...

Reviews: