12
0~2.95in
0~75
21in/530
29.5in/750
8.7in/220
Unit: in/mm
Fig. 19
---
Drain Setup Pipe
INSTRUCTION
The slant gradient of the attached drain hose should be within 3 in.
(75 mm) so that the drain hole does not have to endure unnecessary
outside force.
Fig. 20
---
Slant Gradient
1. Install the drain hose according to the following process if
several drain hoses join together.
Fig. 21
---
Slant Gradient
2. Check the smoothness of the drain after the installation.
3. Check the drain state by draining 36 3/5 in. 3 (600 cc) of
water slowly from the outlet vent or test hole.
4. Check the drain in the state of refrigerating after installing
the electric circuit.
Unit: in/mm
Fig. 22
---
Drain