Carrier 40MBC/38MAQ Installation Instructions Manual Download Page 19

19

TROUBLESHOOTING

For ease of service, the systems are equipped with diagnostic code
display LEDs on both the indoor and outdoor units. The outdoor

diagnostic display consists of two LEDs (Red and Green) on the
outdoor unit board and is limited to a few errors. The indoor

diagnostic display is a combination of flashing LEDs on the

display panel or the front of the unit. If possible, always check the
diagnostic codes displayed on the indoor unit first.
The diagnostic codes displayed in the indoor and outdoor units are
listed in the tables below.

INDOOR UNIT DIAGNOSTIC GUIDES

Table 7—Indoor Unit Diagnostic Guides

Operation Lamp

Timer Lamp

Display

LED Status

1 time

X

E0

Indoor unit EEPROM error

2 times

X

E1

Communication malfunction between indoor and outdoor units

4 times

X

E3

Indoor fan speed has been out of control

5 times

X

E4

Indoor room temperature sensor T1 open circuit or short circuit

6 times

X

E5

Evaporator coil temperature sensor T2 open circuit or short circuit

7 times

X

EC

Refrigerant leakage detection

8 times

X

EE

Water---level alarm malfunction

1 time

O

F0

Current overload protection

2 times

O

F1

Open circuit or short circuit of outdoor ambient temperature sensor T4

3 times

O

F2

Open circuit or short circuit of condenser coil temperature sensor T3

4 times

O

F3

Open circuit or short circuit of Compressor discharge temperature sensor T5

5 times

O

F4

Outdoor unit EEPROM error

6 times

O

F5

Outdoor fan speed has been out of control

7 times

O

F6

T2B sensor error

8 times

O

F7

Lifting---panel communication error

9 times

O

F8

Lifting---panel malfunction

10 times

O

F9

Lifting---panel is not closed

1 time

P0

IPM malfunction

2 times

P1

Over voltage or over low voltage protection

3 times

P2

High temperature protection of compressor top

4 times

P3

Outdoor low temperature protection

5 times

P4

Inverter compressor drive error

6 times

P5

Mode conflict

7 times

P6

Compressor low---pressure protection

8 times

P7

Outdoor IGBT temperature sensor error

O (light) X (off)

(

flash

)

For additional diagnostic information, refer to the

Service Manual.

OUTDOOR UNIT DIAGNOSTIC GUIDES

Table 8—Outdoor Unit Diagnostic Guides

LED2

LED1

Indoor Unit display

Failure Mode

(Green)

(Red)

O

X

Standby, normal

X

O

Operation, normal

O

E5

Compressor drive board EEPROM error

X

P0

IPM malfunction or IGBT over---strong current protection

O

O

P1

Over voltage or too low voltage protection

X

P4

Inverter compressor drive error

O

P4

Inverter compressor drive error

P4

Communication malfunction between main control board and driver board

= Flashing, X = Off

For additional diagnostic information, refer to the Service Manual

Summary of Contents for 40MBC/38MAQ

Page 1: ...TENTS PAGE PARTS LIST 2 SAFETY CONSIDERATIONS 3 SYSTEM REQUIREMENTS 4 DIMENSIONS 5 CLEARANCES 7 INSTALLATION TIPS 9 INDOOR UNIT INSTALLATION 9 OUTDOOR UNIT INSTALLATION 15 INSTALL ALL POWER AND INTERC...

Page 2: ...r unit along the connection pipe by creating a downward arc in the connection pipe before it enters the wall to the indoor unit This will ensure that rain drips from the connection pipe before enterin...

Page 3: ...ds which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor...

Page 4: ...lectrical Data table MCA minimum circuit amps and MOCP maximum over current protection to correctly size the wires and the disconnect fuse or breakers respectively Per the caution note only stranded c...

Page 5: ...570 25 47 647 Depth in mm 22 44 570 25 47 647 22 44 570 25 47 647 22 44 570 25 47 647 Packing Height in mm 11 42 290 4 84 123 11 42 290 4 84 123 11 42 290 4 84 123 Width in mm 25 79 655 28 15 715 25...

Page 6: ...door Unit Table 3 Dimensions Outdoor MODEL W in mm D in mm H in mm L1 in mm L2 in mm OPERATING WEIGHT lb kg 9K 12K 32 0 810 12 2 310 22 0 558 20 9 530 11 4 290 82 5 37 4 18K 32 3 845 12 6 320 27 6 700...

Page 7: ...7 CLEARANCES INDOOR Fig 4 Cassette Unit Clearance...

Page 8: ...8 CLEARANCES OUTDOOR A D B Air outlet Air inlet C E A07894 Fig 5 Outdoor Unit Clearance Table 4 Outdoor Unit Clearance Dimensions UNIT MINIMUM VALUE in mm A 24 610 B 24 610 C 24 610 D 4 101 E 4 101...

Page 9: ...lated water can drain easily away from the outdoor unit 6 Ensure there is enough space for care and maintenance Ensure the height between the indoor unit and ground is 3ft 1mt or 16ft 5mt 7 Check if t...

Page 10: ...component kit and branch duct before installing the unit 3 Install the indoor unit temporarily a Attach the hanger bracket to the suspension bolt Be sure to fix it securely by using a nut and washer...

Page 11: ...o spots to prevent any possible water leakage due to dew condensation 1 Indoor drain pipe 2 Drain socket DRAINAGE HOSE IMPORTANT Observe all local sanitary codes when installing condensate drains 1 In...

Page 12: ...cess if several drain hoses join together Fig 21 Slant Gradient 2 Check the smoothness of the drain after the installation 3 Check the drain state by draining 36 3 5 in 3 600 cc of water slowly from t...

Page 13: ...the unit with the supplied screws see Fig 26 1 Decoration panel 2 Screws M5 supplied with the panel 1 2 Fig 26 Attach the Decoration Panel 3 After installing the decoration panel ensure there is no sp...

Page 14: ...nected to Control Board Grille Louver Motor Power 5 Pin Molex plug to be connected to Control Board Grille Louver Motor Power 5 Pin Port Grille Display 10 Pin Port Fig 30 Panel Cassette 6 Fasten the c...

Page 15: ...tion on the tubing 5 Properly align the tubing with the service valve 6 Tighten the flare nut to proper torque value see Table 5 and finish the installation using backup wrenches see Fig 34 A07354 Fig...

Page 16: ...ctorily LEGEND FLA Full Load Amps MCA Minimum Circuit Amps RLA Rated Load Amps CONNECTION DIAGRAMS A150634 Fig 36 Connection Diagrams Notes 1 Do not use thermostat wire for any connection between indo...

Page 17: ...cified in the System Requirements section 8 Disconnect the charge hose from the charge connection of the low side service valve 9 Fully open service valves B and A 10 Securely tighten the service valv...

Page 18: ...lows Preset set point 76_F 24_C Fan speed AUTO Discharge air direction Pre set position based on operation in Cool or Heat mode 4 Be sure to set the manual switch to OFF by pressing it twice again aft...

Page 19: ...s O F2 Open circuit or short circuit of condenser coil temperature sensor T3 4 times O F3 Open circuit or short circuit of Compressor discharge temperature sensor T5 5 times O F4 Outdoor unit EEPROM e...

Page 20: ...ion S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MBC 38MAQ 02SI Repla...

Reviews: