ELECTRICAL DATA
Table 6—Electrical Data
UNIT
SIZE
OPER. VOLTAGE
MAX / MIN*
COMPRESSOR
OUTDOOR FAN
INDOOR FAN
MCA MAX FUSE
CB AMP
V/PH/HZ
RLA
V/PH/HZ
FLA HP
W
V/PH/HZ
FLA
HP
W
9K
253 / 187
208---230/1/60
5.3
208---230/1/60
0.42 0.053 40
208---230/1/60 0.146 0.061
46
15
15
12K
5.7
0.42 0.053 40
15
15
18K
7.3
0.85 0.067 50
13
20
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
FLA --- Full Load Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
CONNECTION DIAGRAMS
A150634
Fig. 36
---
Connection Diagrams
Notes
:
1. Do not use thermostat wire for any connection between indoor and outdoor units.
2. All connections between indoor and outdoor units must be as shown.
The connections are sensitive to polarity and will result in a fault code.
A150635
Fig. 37
---
Control and Power Wiring on Indoor Unit
NOTE
:
For applications where gravity cannot be used for drainage, a condensate pump accessory is available. Consult the
condensate pump installation instructions for more information.