Prepare the power source for exclusive with the air conditioner.
The supply voltage must comply with the rated voltage of the air conditioner: The plug socket shall be accessible
after installation.
Power Source
Model
Plug socket and Fuse rating
Wiring
50Hz 220-240V~
9000Btu/h
12000Btu/h
2
=1.5mm
2
=1.5mm
10A
16A
Perform the wiring with sufficient capacity. Installation places legally require a short circuit isolator to be attached
to prevent electrical shock.
Do not extend the power cable code by cutting.
Power voltage should in the range of 90% 110% of rated voltage.
The plug of the air conditioner takes a grounding leg, so clients should use a grounding socket so that the air
conditioner can be grounded efficiently.
If the power cord is damaged, replacement should be conducted by qualified technician or a serviceman.
NOTE: Remark per EMC Directive 89/336/EEC
For to prevent flicker impressions during the start of the compressor (technical process),
following installation conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution.
The distribution has to be of an low impedance, normally the required impedance reaches at a 32 A fusing point.
2. No other equipment has to be connected with this power line,.
3. For detailed installation acceptance, please refer to your contract with the power supplier if
restrictions do apply for products like washing machines, air conditioner or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
5. For any question contact your local dealer.
4. Wiring
~
42HQE009(012)/38YE009(012)
GB
ENGLISH
.
..
.
CAUTION
.
5. Connecting Cables
1. Indoor/Outdoor connection cable should be H07RN-F5G type.
2. Remove the panel and remove the screw of electric cover, then take
down the cover.
3. Connect cables according to their marks to terminals.
4. Wrap those cables not connected with terminals with insulation tapes, so
that they will not touch any electrical components.
Panel
Frame
Electric Cover
Terminal block of indoor unit
Cord clamp
1 2(N) 3 4
(Cooling & heating type)
Connective cable
10mm
40mm
GB-7