background image

08

07

Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system ressures, 

electrical components, and equipment location (roofs, elevated structures, etc.).

Only trained, qualified installers and service mechanics should install, start-up, and serve this equipment.

When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached 

to the equipment.

Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher

nearby when brazing. Use care in handing, rigging, and setting bulky equipment.

Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the

unit. Consult local building codes and National Electrical Code for special requirement.

Note:

   The installation plate is fixed with a screw for the conve-

nience of shipment, please remove the screw first before 

installation. (see figure)

  

 The mounting plate will look like one of the figure 

depending on the unit size.

The holes for fixing anchors should be 5mm.

Screw

Step 1: Determine Wall Hole Position 

Step 2: Attach Mounting Plate

Step 3: Drill Wall Hole

Fix the mounting plate horizontally and level on the wall with five 

or more A-type screws.

Install The Mounting Plate

Drill Hole In The Wall 

Indoor

Wall

Outdoor

5-7mm

Step 4: Connect Pipe

L

N

S

Step 5: Connect Wire

Step 6: Prepare Drain Hose

STEP

 

8

     

Indoor Wire Connection

1. Lift the indoor unit front panel.

2. Open the indoor unit electrical cover with a screwdriver 

    through the hole, remove the terminal block cover by 

    hand and remove the cable clamp by loosening the 

    screws

3. Pass the connecting wires from the back of indoor unit 

    and connect to the indoor terminal block.

Front panel

The drain line must not have a trap anywhere in 

its length, must pitch downwards, and must be 

insulated up to the outside wall.

Drainage

Do not put drain end into water

Proper

Do not form a rise

Step 7: Wrap Pipe and Cable

Step 8: Hang the Indoor Unit

1. Run refrigerant lines through hole in the wall.

2. Hang indoor unit on upper hook of mounting plate, 

then push lower part of indoor unit up on wall to lower 

hook.

3. Move indoor unit from side to side, up and down to 

check if it is hooked securely.

Hang The Indoor Unit

For proper orientation of the refrigerant piping, 

electrical cable and drain lines, refer to below Fig:

- Place the drain hose below the refrigerant piping.

- Make sure that the drain hose is not heaved or 

snaked.

Wrap The Pipe

Indoor unit

Electrical

cable

Drain hose

Heat insulation
type

  Refrigerant piping

Pipe room

Ponding box

2.1 INDOOR UNIT MOUNTIN PLATE

2.2 INSTALLATION PROCESS

2. INDOOR UNIT INSTALLATION

2

INDOOR UNIT INSTALLATION

Electrical cover

Open the cover 

from this hole

Connector for wired controller

(optional,come out from display box)

30

Wedge

Drill a 65mm or 90mm(depending on 

models) hole on the wall which is 

slightly tilted towards the outside.

The connector parts of connective pipe must 

be placed outside of room.

CAUTION

Indoor unit 
outline

895

435

435.5

217

460

242.5

45

150

258

wall hole 
      65

232.5

45

45

wall hole 
       65

298

Unit: mm

Note: When the gas side connective pipe is Ф16mm(5/8in) or more, the pipe hole should be 90mm(3.54in).

Wire box cover

Screw

Screw

Terminal block
cover

Cable clamp

GB

Summary of Contents for 38QHP009E8S

Page 1: ...96300 IMROPTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference Please check the applicable models F GA...

Page 2: ...vented to the atmosphere during installation service or disposal When any leakage of the contained fluorinated gas is detected the leak shall be stopped and repaired as soon as possible 4 Only qualifi...

Page 3: ...uld cause severe injury or death Disconnect from power source before attempting any electrical work Connect the connective cable correctly Wrongly connecting may result in electric parts damaged Use t...

Page 4: ...sed to strong winds it is recommended that a wind baffle be used A location which can bear the weight of outdoor unit and where the outdoor unit can be mounted in a level position A location which pro...

Page 5: ...a rise Step 7 Wrap Pipe and Cable Step 8 Hang the Indoor Unit 1 Run refrigerant lines through hole in the wall 2 Hang indoor unit on upper hook of mounting plate then push lower part of indoor unit u...

Page 6: ...le of outdoor unit and rotate 90 degree to securely assemble them 3 5 INSTALL THE DRAIN PIPE FOR OUTDOOR UNIT unit cm unit cm Base pan hole of outdoor unit Drain hose Field supply Gasket Drain Outlet...

Page 7: ...ign the center to tighten the flare nut and finish connection using two wrenches Flare nut Wrench Torque wrench 4 2 2 Select the appropriate insulation material for refrigerant pipe Min 10mm thermal i...

Page 8: ...0mA is advisable This appliance incorporates an earth connection for functional purposes only CAUTION NOTICE 1 All power wires must be sized in according with national state and local electrical wirin...

Page 9: ...n under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed 7 3 GENERAL WORK AREA All mintenance staff and others working in...

Page 10: ...hat can be worked on while live in the presence of a flammable atmosphere The test apparatus shall be at the correct rating Replace components only with parts specified by the manufacturer Other parts...

Page 11: ...t stating the equipment contains flammable refrigerant 20 19 7 19 RECOVERY CAUTION When removing refrigerant from a system either for service or decommissioning it is recommended good practice that al...

Page 12: ...WEEE 2012 19 E 1 2 3 4 1 3 1 1 3 1 2 5 1 3 6 2 7 2 1 7 2 2 8 3 9 3 1 9 3 2 9 3 3 10 3 4 10 3 5 10 4 11 4 1 11 4 2 11 4 3 12 4 4 12 4 5 12 5 13 6 14 6 1 14 6 2 14 6 3 14 7 15 R32 R290 02 42QHP009E8S 3...

Page 13: ...1 1 1 03 R410A 1 R32 4 m2 4 m2 R290 9000 Btu h 13m2 9000Bth h 12000Btu h 17m2 12000Btu h 18000Btu h 26m2 18000Btu h 24000Btu h 35m2 04 BG...

Page 14: ...1 05 1 06 15cm 30cm 2 3m 200cm 60cm 30cm 60cm 12cm 12cm 1 2 3 1 1 2 1 1 1 B 2 5 1 A 5 N 1 3 2 3 m BG...

Page 15: ...07 2 2 1 65 65 mm 5 mm 2 2 A 65 mm 90 mm 1 2 3 4 8 1 2 3 5 6 7 1 2 3 08 2 16 mm 5 8 in 90 mm 3 54 in BG...

Page 16: ...3 3 3 4 M10 3 5 90 3 1 12mm mm mm W H D A B 38QHP009E8S 38QHP012E8S 800 554 333 515 340 3 2 09 3 cm cm H D A B 3 100 mm x 150 mm 10 100 mm x 150 mm 10 W BG...

Page 17: ...2 4 2 1 6 35 mm 18 20 N m 9 52 mm 25 26 N m 12 7 mm 35 36 N m 15 88 mm 45 47 N m 19 05 mm 65 67 N m 4 2 2 10 mm C 27 C 80 120 C 11 4 10 m 5 8 m 10 cm 12 76 cmHg Lo Hi 4 1 R32 4 1 1 90 4 1 2 4 1 3 A mm...

Page 18: ...QHP009 QHP012 13 5 1 5 3 mm 30mA E 1 2 H07RN F 3 4 T20A 250VAC adpot R32 GND 14 A A 38QHP009E8S 10 0 16 3 1 5 mm2 5 1 5 mm2 38QHP012E8S 13 0 20 3 1 5 mm2 5 1 5 mm2 GND 5 Y G 4 cm 4 cm BG...

Page 19: ...15 7 7 1 7 2 7 3 7 4 7 5 7 6 7 7 7 8 16 6 1 6 2 24 C COOLING 30 OFF 6 3 COOLING ON OFF MODE TEMPERATURE FAN SPEED 6 3 BG...

Page 20: ...17 7 7 12 7 13 7 14 25 7 15 18 7 7 9 7 10 10 1 10 2 7 11 BG...

Page 21: ...19 7 20 7 19 7 20 1 2 3 4 5 7 7 16 7 17 80 7 18 BG...

Page 22: ...i ni i elektronski otpad WEEE prema direktivi 2012 19 EZ ne smije mije ati s obi nim ku nim otpadom Ovaj ure aj ne smije se odlagati u ku ni otpad Postoji nekoliko mogu nosti za odlaganje 1 Op ina je...

Page 23: ...cu uklanjanjem bilo koje sigurnosne za tite ili zaobila enjem sigurnosnih prekida a Elektri arski radovi moraju se izvesti u skladu s priru nikom za instalaciju dr avnim i lokalnim propisima za elektr...

Page 24: ...i upravlja 1 Instalacijska plo a 1 Vijak B 2 Dibl 5 Mali filter 1 Vijak A 5 Magnetni prsten neke jedinice N U skladu sa stvarnom koli inom 1 3 IZBOR MJESTA INSTALACIJE Unutra nja jedinica mjesto koje...

Page 25: ...iti cijelom du inom potpuno prohodan mora biti nagnut prema dole i izoliran cijelom du inom do vanjskog zida Ispravno Nemojte oblikovati uspon Nemojte stavljati kraj odvoda u vodu Korak 5 Priklju ite...

Page 26: ...imenzije vanjske jedinice mm Dimenzije monta e mm Vanjska jedinica V D A B 38QHP009E8S 38QHP012E8S 800 554 333 515 340 3 2 POTREBAN PROSTOR ZA VANJSKU JEDINICU 09 3 INSTALACIJA VANJSKE JEDINICE Instal...

Page 27: ...ili dr sli ne lokacije poja ajte izolaciju Temperatura otpornosti izolacije na toplotu treba biti vi a od 120 C Nanesite ljepilo na spojni dio izolacije da biste sprije ili ulazak vlage Popravite i p...

Page 28: ...emljenje koje ovaj ure aj sadr i ima isklju ivo funkcionalnu svrhu NAPOMENA 1 Dimenzije svih elektri nih ica moraju biti u skladu s dr avnim i lokalnim propisima za elektroinstalacije Posebne zahtjeve...

Page 29: ...iti i po mogu nosti izbaciti u atmosferu 7 8 PROVJERE RASHLADNE OPREME Sve zamjenske elektri ne komponente moraju odgovarati namjeni i specifikacijama U svakom trenutku treba slijediti proizvo a eve s...

Page 30: ...lemljenje cijevi Uvjerite se da ispust vakuumske pumpe nije blizu izvora zapaljenja i da je omogu ena ventilacija 18 7 INFORMACIJE O SERVISIRANJU Veli ina punjenja je u skladu s veli inom prostorije u...

Page 31: ...edstva za hla enje uslijed mehani kog o te enja opreme u ambala i Dozvoljeni maksimalni broj dijelova opreme koji se smiju pohraniti zajedno odre uju lokalni propisi 7 INFORMACIJE O SERVISIRANJU 7 16...

Page 32: ...n OEEZ podle sm rnice 2012 19 ES nesm b t sm ch na s b n m komun ln m odpadem Likvidace tohoto za zen spole n s b n m komun ln m odpadem je zak z na Pro likvidaci existuje n kolik mo nost 1 Obec m zav...

Page 33: ...avujte tuto jednotku t m e odstran te jakoukoliv bezpe nostn ochranu nebo p emost te jak koliv sp na bezpe nostn ho blokov n Elektroinstala n pr ce by m ly b t prov d ny v souladu s n vodem k instalac...

Page 34: ...an V vod odtoku 1 Baterie 2 T sn n 1 Dr k d lkov ho ovlada e 1 Mont n deska 1 roub B 2 Kotva 5 Mal filtr 1 roub A 5 Magnetick krou ek n kter jednotky N v z vislosti od skute n ho mno stv 1 3 V B R M S...

Page 35: ...n n m roub demontujte kabelovou svorku 3 Prot hn te p ipojovac vodi e ze zadn strany vnit n jednotky a p ipojte je ke svorkovnici vnit n jednotky Odtok Odtokov potrub nesm b t v dn m m st sv d lky zab...

Page 36: ...r hlavy upev ovac ho roubu by m l b t v ce ne 12 mm Rozm ry venkovn jednotky mm Mont n rozm ry mm Venkovn jednotka W H D A B 38QHP009E8S 38QHP012E8S 800 554 333 515 340 3 2 PROSTOROV PO ADAVKY VENKOV...

Page 37: ...hyn a podobn ch m st zesilte izolaci Teplota tepeln ho odporu izolace by m la b t vy ne 120 C Pou ijte lepidla na spojovac sou sti izolace abyste p ede li vniknut vlhkosti Opravte a zakryjte p padn pr...

Page 38: ...A Tento spot ebi zahrnuje zemnic p pojku pouze pro el funk nosti UPOZORN N 1 V echny nap jec vodi e mus b t dimenzov ny v souladu s n rodn mi st tn mi a m stn mi elektroinstala n mi p edpisy V p pad z...

Page 39: ...prov d n m jak koliv innosti za p tomnosti vysok teploty dostate n odv tr v na Nep etr it odv tr v n mus b t zaji t no po celou dobu prov d n pr ce Odv tr v n mus bezpe n rozptylovat ve ker uvoln n ch...

Page 40: ...adice v v vy nenach z v bl zkosti dn ch zdroj vzn cen a e je zaji t no odv tr v n 18 7 INFORMACE PRO PROV D N SERVISN CH Z SAH plnic objem odpov d velikosti m stnosti ve kter jsou um st ny sou sti obs...

Page 41: ...ho po kozen za zen uvnit balen Maxim ln po et kus za zen kter je dovoleno skladovat spole n bude stanoveno m stn mi p edpisy 7 INFORMACE PRO PROV D N SERVISN CH Z SAH 7 16 POSTUPY PLN N Krom konven n...

Page 42: ...30 2012 19 1 2 3 4 1 3 1 1 3 1 2 5 1 3 6 2 7 2 1 7 2 2 8 3 9 3 1 9 3 2 9 3 3 10 3 4 10 3 5 10 4 11 4 1 11 4 2 11 4 3 12 4 4 12 4 5 12 5 13 6 14 6 1 14 6 2 14 6 3 14 7 15 R32 R290 02 Hz 42QHP009E8S 38Q...

Page 43: ...1 1 1 03 R410A 1 R32 4 m2 4 m2 R290 9000 Btu h 13 m2 9000 Bth h 12000 Btu h 17m2 12000 Btu h 18000 Btu h 26m2 18000 Btu h 24000 Btu h 35m2 04 EL...

Page 44: ...1 05 1 06 15cm 30cm 2 3m 200cm 60cm 30cm 60cm 12cm 12cm A 1 2 3 1 Mode Timer TurboI ON LED ON OFF Fan Follow me Self clean 1 2 1 1 1 2 5 1 5 N 1 3 2 3 m EL...

Page 45: ...895 435 435 5 217 460 242 5 45 150 258 65 232 5 45 45 65 298 16 mm 5 8 90 mm 3 54 A 65 mm 90 mm 07 2 2 1 5 mm 2 2 1 2 3 4 8 1 2 3 5 6 7 1 2 3 08 2 EL...

Page 46: ...3 3 3 4 M10 3 5 90 3 1 12mm mm mm A B 38QHP009E8S 38QHP012E8S 800 554 333 515 340 3 2 09 3 cm cm A B 3 100mm x 150mm M10 100mm x 150mm 10 EL...

Page 47: ...19 05 mm 23 3 22 9 4 1 4 4 3 6 35 mm 9 52mm R32 3 m 5 m 12 g 24 g R32 5 5m R32 Inverter m m 9K 12K 25 10 R32 4 4 76cmHg 4 5 HFC A B 4 2 4 2 1 6 35 mm 18 20 N m 9 52 mm 25 26 N m 12 7 mm 35 36 N m 15...

Page 48: ...QHP009 QHP012 13 5 1 5 3 mm RCD 30 mA 1 2 H07RN F 3 4 T20A 250 V AC R32 14 A 38QHP009E8S 10 0 16 3 1 5 mm2 5 1 5 mm2 38QHP012E8S 13 0 20 3 1 5 mm2 5 1 5 mm2 5 4 cm 4 cm EL...

Page 49: ...15 7 7 1 7 2 7 3 7 4 7 5 CO2 7 6 7 7 7 8 16 6 1 6 2 24 C 30 6 3 COOLING ON OFF MODE TEMPERATURE FAN SPEED E E 6 3 EL...

Page 50: ...17 7 7 12 7 13 7 14 LFL 25 OFN 7 15 OFN OFN OFN 18 7 7 9 7 10 10 1 10 2 7 11 EL...

Page 51: ...19 7 20 7 19 7 20 1 2 3 4 5 7 7 16 OFN 7 17 80 7 18 EL...

Reviews: