background image

 

CAUTION

Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure 

that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be 

complied with prior to conducting work on the system.

the charge size is in accordance with the room size within which the refrigerant containing parts are installed;

the ventilation machinery and outlets are operating adequately and are not obstructed;

if an indirect refrigerating circuit is being used, the secondary circuits shall be checked for the presence of 

refrigerant; marking to the equipment continues to be visible and legible.

marking and signs that are illegible shall be corrected;

refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any 

substance which may corrode refrigerant containing components, unless the components are constructed of 

materials which are inherently resistant to being corroded or are suitably protected against being so corroded.

 

7. INFORMATION SERVICING

7.9  CHECKS TO ELECTRICAL DEVICES

Repair and maintenance to electrical components shall include initial safety checks and component inspection 

procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the 

circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue 

operation, and adequate temporary solution shall be used. This shall be reported to the owner of the equipment 

so all parties are advised.

Initial safety checks shall include:

that capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking

that there no live electrical components and wiring are exposed while charging, recovering or purging the system;

that there is continuity of earth bonding.

7.10  REPAIRS TO SEALED COMPONENTS

10.1 During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being

        worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical

        supply to equipment during servicing, then a permanently operating form of leak detection shall be located

        at the most critical point to warn of a potentially hazardous situation.

10.2 Particular attention shall be paid to the following to ensure that by working on electrical components, the

        casing is not altered in such a way that the level of protection is affected.This shall include damage to

        cables, excessive number of connections, terminals not made to original specification, damage to seals,

        incorrect fitting of glands, etc.

        Ensure that apparatus is mounted securely.

        Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of

        preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the

        manufacturer s specifications.

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. 

Instrinsically safe components do not have to be isolated prior to working on them.

7.11  REPAI TO INTRINSICALLY SAFE COMPONENTS

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not 

exceed the permissible voltage and current permitted for the equipment in use. Intrinscially safe components are 

the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus 

shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may 

result in the ignition of refrigerant in the atmosphere from a leak.

18

17

7.12  CABLING

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other 

adverse environmental effects. The check shall also take into account the effects of aging or continual vibration 

from sources such as compressors or fans.

7. INFORMATION SERVICING

7.13  DETECTION OF FLAMMABLE REFRIGERANTS 

Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant 

leaks. A halide torch(or any other detector using a naked flame) shall not be used.

7.14  LEAK DETECTION METHODS

The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. 

Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, 

or may need re-calibration.(Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the 

detector is not a potential source of ignition and is suitable for the refrigerant. Leak detection equipment shall be 

set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the 

appropriate percentage of gas (25% maximum) is confirmed. Leak detection fluids are suitable for use with most 

refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the 

refrigerant and corrode the copper pipe-work. If a leak is suspected ,all naked flames shall be removed or 

extinguished. If a leakage of refrigernat is found which requires brazing, all of the refrigerant shall be recovered 

from the system, or isolated(by means of shut off valves) in a part of the system remote from the leak . Oxygen 

free nitrogen(OFN) shall then be purged through the system both before and during the brazing process.

7.15  REMOVAL AND EVACUATION

When breaking into the refrigerant circuit to make repairs of for any other purpose conventional procedures shall 

be used, However, it is important that best practice is followed since flammability is a consideration. The following 

procedure shall be adhered to:

   remove refrigerant;

   purge the circuit with inert gas;

   evacuate;

   purge again with inert gas;

   open the circuit by cutting or brazing.

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed with 

OFN to render the unit safe. This process may need to be repeated several times. 

Compressed air or oxygen shall not be used for this task. 

Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the 

working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process 

shall be repeated until no refrigerant is within the system.

When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to 

take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that 

the outlet for the vacuum pump is not closed to any ignition sources and there is ventilation available.

GB

Summary of Contents for 38QHP009E8S

Page 1: ...96300 IMROPTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference Please check the applicable models F GA...

Page 2: ...vented to the atmosphere during installation service or disposal When any leakage of the contained fluorinated gas is detected the leak shall be stopped and repaired as soon as possible 4 Only qualifi...

Page 3: ...uld cause severe injury or death Disconnect from power source before attempting any electrical work Connect the connective cable correctly Wrongly connecting may result in electric parts damaged Use t...

Page 4: ...sed to strong winds it is recommended that a wind baffle be used A location which can bear the weight of outdoor unit and where the outdoor unit can be mounted in a level position A location which pro...

Page 5: ...a rise Step 7 Wrap Pipe and Cable Step 8 Hang the Indoor Unit 1 Run refrigerant lines through hole in the wall 2 Hang indoor unit on upper hook of mounting plate then push lower part of indoor unit u...

Page 6: ...le of outdoor unit and rotate 90 degree to securely assemble them 3 5 INSTALL THE DRAIN PIPE FOR OUTDOOR UNIT unit cm unit cm Base pan hole of outdoor unit Drain hose Field supply Gasket Drain Outlet...

Page 7: ...ign the center to tighten the flare nut and finish connection using two wrenches Flare nut Wrench Torque wrench 4 2 2 Select the appropriate insulation material for refrigerant pipe Min 10mm thermal i...

Page 8: ...0mA is advisable This appliance incorporates an earth connection for functional purposes only CAUTION NOTICE 1 All power wires must be sized in according with national state and local electrical wirin...

Page 9: ...n under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed 7 3 GENERAL WORK AREA All mintenance staff and others working in...

Page 10: ...hat can be worked on while live in the presence of a flammable atmosphere The test apparatus shall be at the correct rating Replace components only with parts specified by the manufacturer Other parts...

Page 11: ...t stating the equipment contains flammable refrigerant 20 19 7 19 RECOVERY CAUTION When removing refrigerant from a system either for service or decommissioning it is recommended good practice that al...

Page 12: ...WEEE 2012 19 E 1 2 3 4 1 3 1 1 3 1 2 5 1 3 6 2 7 2 1 7 2 2 8 3 9 3 1 9 3 2 9 3 3 10 3 4 10 3 5 10 4 11 4 1 11 4 2 11 4 3 12 4 4 12 4 5 12 5 13 6 14 6 1 14 6 2 14 6 3 14 7 15 R32 R290 02 42QHP009E8S 3...

Page 13: ...1 1 1 03 R410A 1 R32 4 m2 4 m2 R290 9000 Btu h 13m2 9000Bth h 12000Btu h 17m2 12000Btu h 18000Btu h 26m2 18000Btu h 24000Btu h 35m2 04 BG...

Page 14: ...1 05 1 06 15cm 30cm 2 3m 200cm 60cm 30cm 60cm 12cm 12cm 1 2 3 1 1 2 1 1 1 B 2 5 1 A 5 N 1 3 2 3 m BG...

Page 15: ...07 2 2 1 65 65 mm 5 mm 2 2 A 65 mm 90 mm 1 2 3 4 8 1 2 3 5 6 7 1 2 3 08 2 16 mm 5 8 in 90 mm 3 54 in BG...

Page 16: ...3 3 3 4 M10 3 5 90 3 1 12mm mm mm W H D A B 38QHP009E8S 38QHP012E8S 800 554 333 515 340 3 2 09 3 cm cm H D A B 3 100 mm x 150 mm 10 100 mm x 150 mm 10 W BG...

Page 17: ...2 4 2 1 6 35 mm 18 20 N m 9 52 mm 25 26 N m 12 7 mm 35 36 N m 15 88 mm 45 47 N m 19 05 mm 65 67 N m 4 2 2 10 mm C 27 C 80 120 C 11 4 10 m 5 8 m 10 cm 12 76 cmHg Lo Hi 4 1 R32 4 1 1 90 4 1 2 4 1 3 A mm...

Page 18: ...QHP009 QHP012 13 5 1 5 3 mm 30mA E 1 2 H07RN F 3 4 T20A 250VAC adpot R32 GND 14 A A 38QHP009E8S 10 0 16 3 1 5 mm2 5 1 5 mm2 38QHP012E8S 13 0 20 3 1 5 mm2 5 1 5 mm2 GND 5 Y G 4 cm 4 cm BG...

Page 19: ...15 7 7 1 7 2 7 3 7 4 7 5 7 6 7 7 7 8 16 6 1 6 2 24 C COOLING 30 OFF 6 3 COOLING ON OFF MODE TEMPERATURE FAN SPEED 6 3 BG...

Page 20: ...17 7 7 12 7 13 7 14 25 7 15 18 7 7 9 7 10 10 1 10 2 7 11 BG...

Page 21: ...19 7 20 7 19 7 20 1 2 3 4 5 7 7 16 7 17 80 7 18 BG...

Page 22: ...i ni i elektronski otpad WEEE prema direktivi 2012 19 EZ ne smije mije ati s obi nim ku nim otpadom Ovaj ure aj ne smije se odlagati u ku ni otpad Postoji nekoliko mogu nosti za odlaganje 1 Op ina je...

Page 23: ...cu uklanjanjem bilo koje sigurnosne za tite ili zaobila enjem sigurnosnih prekida a Elektri arski radovi moraju se izvesti u skladu s priru nikom za instalaciju dr avnim i lokalnim propisima za elektr...

Page 24: ...i upravlja 1 Instalacijska plo a 1 Vijak B 2 Dibl 5 Mali filter 1 Vijak A 5 Magnetni prsten neke jedinice N U skladu sa stvarnom koli inom 1 3 IZBOR MJESTA INSTALACIJE Unutra nja jedinica mjesto koje...

Page 25: ...iti cijelom du inom potpuno prohodan mora biti nagnut prema dole i izoliran cijelom du inom do vanjskog zida Ispravno Nemojte oblikovati uspon Nemojte stavljati kraj odvoda u vodu Korak 5 Priklju ite...

Page 26: ...imenzije vanjske jedinice mm Dimenzije monta e mm Vanjska jedinica V D A B 38QHP009E8S 38QHP012E8S 800 554 333 515 340 3 2 POTREBAN PROSTOR ZA VANJSKU JEDINICU 09 3 INSTALACIJA VANJSKE JEDINICE Instal...

Page 27: ...ili dr sli ne lokacije poja ajte izolaciju Temperatura otpornosti izolacije na toplotu treba biti vi a od 120 C Nanesite ljepilo na spojni dio izolacije da biste sprije ili ulazak vlage Popravite i p...

Page 28: ...emljenje koje ovaj ure aj sadr i ima isklju ivo funkcionalnu svrhu NAPOMENA 1 Dimenzije svih elektri nih ica moraju biti u skladu s dr avnim i lokalnim propisima za elektroinstalacije Posebne zahtjeve...

Page 29: ...iti i po mogu nosti izbaciti u atmosferu 7 8 PROVJERE RASHLADNE OPREME Sve zamjenske elektri ne komponente moraju odgovarati namjeni i specifikacijama U svakom trenutku treba slijediti proizvo a eve s...

Page 30: ...lemljenje cijevi Uvjerite se da ispust vakuumske pumpe nije blizu izvora zapaljenja i da je omogu ena ventilacija 18 7 INFORMACIJE O SERVISIRANJU Veli ina punjenja je u skladu s veli inom prostorije u...

Page 31: ...edstva za hla enje uslijed mehani kog o te enja opreme u ambala i Dozvoljeni maksimalni broj dijelova opreme koji se smiju pohraniti zajedno odre uju lokalni propisi 7 INFORMACIJE O SERVISIRANJU 7 16...

Page 32: ...n OEEZ podle sm rnice 2012 19 ES nesm b t sm ch na s b n m komun ln m odpadem Likvidace tohoto za zen spole n s b n m komun ln m odpadem je zak z na Pro likvidaci existuje n kolik mo nost 1 Obec m zav...

Page 33: ...avujte tuto jednotku t m e odstran te jakoukoliv bezpe nostn ochranu nebo p emost te jak koliv sp na bezpe nostn ho blokov n Elektroinstala n pr ce by m ly b t prov d ny v souladu s n vodem k instalac...

Page 34: ...an V vod odtoku 1 Baterie 2 T sn n 1 Dr k d lkov ho ovlada e 1 Mont n deska 1 roub B 2 Kotva 5 Mal filtr 1 roub A 5 Magnetick krou ek n kter jednotky N v z vislosti od skute n ho mno stv 1 3 V B R M S...

Page 35: ...n n m roub demontujte kabelovou svorku 3 Prot hn te p ipojovac vodi e ze zadn strany vnit n jednotky a p ipojte je ke svorkovnici vnit n jednotky Odtok Odtokov potrub nesm b t v dn m m st sv d lky zab...

Page 36: ...r hlavy upev ovac ho roubu by m l b t v ce ne 12 mm Rozm ry venkovn jednotky mm Mont n rozm ry mm Venkovn jednotka W H D A B 38QHP009E8S 38QHP012E8S 800 554 333 515 340 3 2 PROSTOROV PO ADAVKY VENKOV...

Page 37: ...hyn a podobn ch m st zesilte izolaci Teplota tepeln ho odporu izolace by m la b t vy ne 120 C Pou ijte lepidla na spojovac sou sti izolace abyste p ede li vniknut vlhkosti Opravte a zakryjte p padn pr...

Page 38: ...A Tento spot ebi zahrnuje zemnic p pojku pouze pro el funk nosti UPOZORN N 1 V echny nap jec vodi e mus b t dimenzov ny v souladu s n rodn mi st tn mi a m stn mi elektroinstala n mi p edpisy V p pad z...

Page 39: ...prov d n m jak koliv innosti za p tomnosti vysok teploty dostate n odv tr v na Nep etr it odv tr v n mus b t zaji t no po celou dobu prov d n pr ce Odv tr v n mus bezpe n rozptylovat ve ker uvoln n ch...

Page 40: ...adice v v vy nenach z v bl zkosti dn ch zdroj vzn cen a e je zaji t no odv tr v n 18 7 INFORMACE PRO PROV D N SERVISN CH Z SAH plnic objem odpov d velikosti m stnosti ve kter jsou um st ny sou sti obs...

Page 41: ...ho po kozen za zen uvnit balen Maxim ln po et kus za zen kter je dovoleno skladovat spole n bude stanoveno m stn mi p edpisy 7 INFORMACE PRO PROV D N SERVISN CH Z SAH 7 16 POSTUPY PLN N Krom konven n...

Page 42: ...30 2012 19 1 2 3 4 1 3 1 1 3 1 2 5 1 3 6 2 7 2 1 7 2 2 8 3 9 3 1 9 3 2 9 3 3 10 3 4 10 3 5 10 4 11 4 1 11 4 2 11 4 3 12 4 4 12 4 5 12 5 13 6 14 6 1 14 6 2 14 6 3 14 7 15 R32 R290 02 Hz 42QHP009E8S 38Q...

Page 43: ...1 1 1 03 R410A 1 R32 4 m2 4 m2 R290 9000 Btu h 13 m2 9000 Bth h 12000 Btu h 17m2 12000 Btu h 18000 Btu h 26m2 18000 Btu h 24000 Btu h 35m2 04 EL...

Page 44: ...1 05 1 06 15cm 30cm 2 3m 200cm 60cm 30cm 60cm 12cm 12cm A 1 2 3 1 Mode Timer TurboI ON LED ON OFF Fan Follow me Self clean 1 2 1 1 1 2 5 1 5 N 1 3 2 3 m EL...

Page 45: ...895 435 435 5 217 460 242 5 45 150 258 65 232 5 45 45 65 298 16 mm 5 8 90 mm 3 54 A 65 mm 90 mm 07 2 2 1 5 mm 2 2 1 2 3 4 8 1 2 3 5 6 7 1 2 3 08 2 EL...

Page 46: ...3 3 3 4 M10 3 5 90 3 1 12mm mm mm A B 38QHP009E8S 38QHP012E8S 800 554 333 515 340 3 2 09 3 cm cm A B 3 100mm x 150mm M10 100mm x 150mm 10 EL...

Page 47: ...19 05 mm 23 3 22 9 4 1 4 4 3 6 35 mm 9 52mm R32 3 m 5 m 12 g 24 g R32 5 5m R32 Inverter m m 9K 12K 25 10 R32 4 4 76cmHg 4 5 HFC A B 4 2 4 2 1 6 35 mm 18 20 N m 9 52 mm 25 26 N m 12 7 mm 35 36 N m 15...

Page 48: ...QHP009 QHP012 13 5 1 5 3 mm RCD 30 mA 1 2 H07RN F 3 4 T20A 250 V AC R32 14 A 38QHP009E8S 10 0 16 3 1 5 mm2 5 1 5 mm2 38QHP012E8S 13 0 20 3 1 5 mm2 5 1 5 mm2 5 4 cm 4 cm EL...

Page 49: ...15 7 7 1 7 2 7 3 7 4 7 5 CO2 7 6 7 7 7 8 16 6 1 6 2 24 C 30 6 3 COOLING ON OFF MODE TEMPERATURE FAN SPEED E E 6 3 EL...

Page 50: ...17 7 7 12 7 13 7 14 LFL 25 OFN 7 15 OFN OFN OFN 18 7 7 9 7 10 10 1 10 2 7 11 EL...

Page 51: ...19 7 20 7 19 7 20 1 2 3 4 5 7 7 16 OFN 7 17 80 7 18 EL...

Reviews: