Combination ratings*

Ratings are based on: Cooling Standard: 80°F (27°C) db 67°F (19°C) wb indoor entering air temperature and 95°F (35°C) db air entering outdoor 

unit.

NOTES:

1. Ratings are net values re

fl

ecting the effects of circulating fan motor heat. Supplemental electric heat is not included.

2. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature.
3. Minimum outdoor operating ambient in cooling mode is 55°F (12.8°C), maximum 125°F (51.7°C).

COOLING CAPACITY @ 95°F (35°C)

COOLING CAPACITY @ 115°F (46°C)

UNIT

SIZE-SERIES

INDOOR 

UNIT

NOMINAL AIRFLOW

RATED CAPACITY

POWER

RATED

RATED CAPACITY

POWER

CFM

L/S

BTUH

kW

kW

EER

BTUH

kW

kW

018-3A

FB4BNF018

600

280

17,000

4.98

1.81

9.40

14,000

4.10

2.06

FB4BNF024

600

280

17,600

5.16

1.83

9.60

15,000

4.39

2.14

FA4CN(F,C)018

600

280

17,600

5.16

1.83

9.60

15,500

4.54

2.21

FA4CN(F,C)024

600

280

17,800

5.22

1.84

9.70

15,500

4.54

2.21

024-3A

FB4BNF024

800

380

23,200

6.80

2.39

9.70

18,700

5.48

2.75

FB4BNF030

800

380

23,500

6.89

2.40

9.80

19,000

5.57

2.71

FA4CN(F,C)024

800

380

23,500

6.89

2.40

9.80

19,500

5.71

2.79

FA4CN(F,C)030

800

380

23,800

6.97

2.43

9.80

19,500

5.71

2.79

030-3A

FB4BNF030

1000

467

28,600

8.38

3.04

9.40

23,200

6.80

3.41

FB4BNF036

1000

467

28,800

8.44

3.06

9.40

23,500

6.89

3.36

FA4CN(F,C)030

1000

467

29,000

8.50

3.05

9.50

23,800

6.97

3.40

FA4CN(F,C)036

1000

467

29,200

8.56

3.07

9.50

24,000

7.03

3.43

036-3A

FB4BNF036

1200

550

33,500

9.82

3.72

9.00

27,800

8.15

4.09

FB4BN(F,B)042

1200

550

33,800

9.90

3.63

9.30

28,200

8.26

4.03

FA4CN(F,C)036

1200

550

33,800

9.90

3.63

9.30

28,500

8.35

4.07

FA4CN(F,C)042

1200

550

34,400

10.08

3.62

9.50

29,200

8.56

4.17

042-3A

FB4BN(F,B)042

1400

653

41,000

12.01

4.56

9.00

34,400

10.08

5.06

FB4BN(F,B)048

1400

653

41,500

12.16

4.51

9.20

35,000

10.25

5.00

FA4CN(F,C)042

1400

653

41,500

12.16

4.51

9.20

35,800

10.49

5.11

FA4CN(F,C)048

1400

653

42,400

12.42

4.56

9.30

36,600

10.72

5.23

048-3A

FB4BN(F,B)048

1600

750

47,500

13.92

5.05

9.40

41,000

12.01

6.03

FB4BN(F,B)060

1600

750

48,500

14.21

5.16

9.40

42,000

12.31

6.00

FB4BNB070

1600

750

49,000

14.36

5.16

9.50

42,800

12.54

5.94

FA4CN(F,C)048

1600

750

48,000

14.06

5.05

9.50

42,800

12.54

6.11

FA4CN(F,C)060

1600

750

49,000

14.36

5.16

9.50

43,800

12.83

6.08

060-3A

FB4BN(F,B)060

2000

919

57,500

16.85

6.39

9.00

49,500

14.50

7.62

FB4BNB070

2000

919

58,000

16.99

6.24

9.30

50,500

14.80

7.43

FA4CN(F,C)060

2000

919

58,000

16.99

6.24

9.30

50,500

14.80

7.43

Summary of Contents for 38CKS

Page 1: ...otective coating on the coil Heavy Duty Inlet Grille The WeatherArmor coil protector made of a coated steel wire grid with vertical 3 8 in 9 5 mm spacing is designed to help protect the coil from incl...

Page 2: ...nt seating with provision for field sweat connections Valves are externally located for quick and easy refrigerant tube connections Each valve provides service ports for ease in checking operating ref...

Page 3: ...125 COND COIL Face Area Sq Ft m2 Fins per In Fins per cm Rows Circuits Copper Tube Aluminum Plate Fin 6 8 63 9 1 85 9 9 92 12 4 1 15 14 8 1 37 18 5 1 72 16 1 1 50 20 8 20 8 20 8 20 8 20 8 20 8 20 8 1...

Page 4: ...or and Relay Size 042 KSAHS1601AAA Start Assist Capacitor and Relay Sizes 048 060 KAACS0201PTC Start Assist PTC All Sizes KAACH1001AAA Crankcase Heater Sizes 018 042 KAACH1201AAA Crankcase Heater Size...

Page 5: ...to the compressor motor at each start up Usage Guideline Suggested when compressor power supply is marginal Suggested in reciprocating compressor applications with rapid pressure balance RPB expansion...

Page 6: ...sure at low ambient temperatures down to 0 F 17 8 C when properly installed Usage Guideline A Low Ambient Pressure Switch or Motor Master Low Ambient Controller must be used when cooling operation is...

Page 7: ...path between the unit and service panel for a voltage drop not to exceed 2 Time delay fuse FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps NOTES 1 Control circuit...

Page 8: ...65 2 365 1 496 9 560 4 260 4 241 3 298 5 571 5 X 571 5 036 A 571 5 862 01 81 0 19 1 93 7 460 4 501 7 565 2 365 1 496 9 560 4 260 4 241 3 393 7 571 5 X 571 5 042 A 762 0 709 61 82 6 22 2 165 1 596 9 69...

Page 9: ...0 800 380 23 800 6 97 2 43 9 80 19 500 5 71 2 79 030 3A FB4BNF030 1000 467 28 600 8 38 3 04 9 40 23 200 6 80 3 41 FB4BNF036 1000 467 28 800 8 44 3 06 9 40 23 500 6 89 3 36 FA4CN F C 030 1000 467 29 00...

Page 10: ...90 2 98 7 55 5 51 3 15 6 82 5 13 3 31 6 13 4 78 3 48 22 10 59 5 42 2 67 9 93 5 13 2 87 9 22 4 83 3 07 8 49 4 52 3 27 7 74 4 20 3 48 7 00 3 88 3 68 470 14 8 63 8 63 2 58 8 02 8 02 2 74 7 40 7 40 2 91 6...

Page 11: ...30 4 87 8 68 8 68 5 18 17 12 25 10 96 3 73 11 57 10 62 4 05 10 82 10 23 4 31 10 04 9 80 4 59 9 31 9 31 4 87 8 67 8 67 5 18 19 13 41 9 21 3 83 12 86 9 04 4 17 12 16 8 77 4 51 11 33 8 42 4 82 10 49 8 0...

Page 12: ...15 37 5 05 14 73 14 73 5 45 14 07 14 07 5 91 13 32 13 32 6 39 12 60 12 60 6 93 11 84 11 84 7 53 17 16 37 14 30 5 12 15 66 13 90 5 56 14 80 13 42 6 00 13 86 12 90 6 46 12 92 12 36 6 98 11 98 11 78 7 56...

Page 13: ...42 2 92 72 28 79 14 67 2 01 27 33 14 06 2 21 25 62 13 35 2 42 23 78 12 60 2 64 21 86 11 81 2 87 19 87 10 99 3 10 800 57 23 26 23 26 1 94 21 74 21 74 2 11 20 27 20 27 2 28 18 73 18 73 2 47 17 26 17 26...

Page 14: ...4 97 25 79 4 98 32 14 24 62 5 26 72 48 12 24 41 3 83 46 80 23 94 4 19 44 82 23 19 4 54 42 40 22 28 4 90 39 55 21 15 5 26 36 67 20 07 5 57 1400 57 39 57 39 57 3 68 37 75 37 75 3 97 35 79 35 79 4 26 33...

Page 15: ...52 46 52 46 5 05 50 29 50 29 5 45 48 01 48 01 5 91 45 47 45 47 6 39 42 99 42 99 6 93 40 41 40 41 7 53 62 55 86 48 81 5 12 53 43 47 43 5 56 50 50 45 80 6 00 47 31 44 02 6 46 44 11 42 18 6 98 40 89 40 2...

Page 16: ...88 1 91 1 94 4 TCG 9 00 8 20 7 50 6 70 6 00 5 30 4 60 4 00 SDT 30 00 35 00 40 00 45 00 49 00 53 00 58 00 62 00 KW 1 67 1 76 1 85 1 91 1 96 2 00 2 04 2 09 7 TCG 10 30 9 30 8 50 7 70 7 00 6 20 5 50 4 8...

Page 17: ...7 3 71 4 TCG 15 60 14 20 13 00 11 80 10 70 9 50 8 40 7 30 SDT 29 00 35 00 39 00 44 00 49 00 53 00 58 00 62 00 KW 2 90 3 16 3 39 3 57 3 69 3 82 3 92 3 98 7 TCG 17 80 16 10 14 70 13 40 12 20 10 90 9 70...

Page 18: ...00 35 00 40 00 45 00 50 00 54 00 59 00 64 00 KW 3 73 4 10 4 46 4 81 5 19 5 62 6 07 6 53 4 TCG 19 10 18 60 17 90 17 00 15 90 14 70 13 60 12 30 SDT 30 00 36 00 41 00 46 00 51 00 56 00 61 00 65 00 KW 3 7...

Page 19: ...1 1 94 40 TCG 30 60 27 90 25 40 23 00 20 50 18 10 15 80 13 60 SDT 86 90 95 50 103 80 112 10 120 20 128 00 136 00 144 10 KW 1 67 1 76 1 85 1 91 1 96 2 00 2 04 2 09 45 TCG 35 00 31 80 29 10 26 40 23 80...

Page 20: ...9 3 60 3 67 3 71 40 TCG 53 20 48 40 44 30 40 30 36 40 32 60 28 80 24 90 SDT 85 10 94 30 103 10 111 60 120 00 128 10 136 20 144 10 KW 2 90 3 16 3 39 3 57 3 69 3 82 3 92 3 98 45 TCG 60 80 55 00 50 20 45...

Page 21: ...60 103 70 112 40 121 10 129 80 138 60 147 40 KW 3 73 4 10 4 46 4 81 5 19 5 62 6 07 6 53 40 TCG 65 30 63 40 61 10 58 10 54 40 50 30 46 30 42 00 SDT 86 10 96 80 106 00 115 00 123 80 132 30 141 00 149 8...

Page 22: ...or interconnecting refrigerant tube lengths between 50 15 24m and 175 53 34m ft and or 20 6 1m ft vertical dif ferential consult Residential s Split System Long Line Application Guideline available fr...

Page 23: ...23...

Page 24: ...drive propeller type discharging air upward Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Air Cooled Split System Air Condition...

Reviews: