![Carrier 38CKS Product Data Download Page 12](http://html.mh-extra.com/html/carrier/38cks/38cks_product-data_2560595012.webp)
12
Detailed cooling capacities* (S.I.) continued
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length
and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835
Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S)
of indoor coil air per degree above 80°F (27°C).
** Unit kW is total of indoor and outdoor unit kilowatts.
EWB — Entering Wet Bulb.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES
°
C
24
29
35
41
46
52
CFM
EWB
Capacity
kW
Tot
Sys
kW**
Capacity
kW
Tot
Sys
kW**
Capacity
kW
Tot
Sys
kW**
Capacity
kW
Tot
Sys
kW**
Capacity
kW
Tot
Sys
kW**
Capacity
kW
Tot
Sys
kW**
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
38CKS060-3A Outdoor Section With FA4CN(F,C)060 Indoor Section
825
14
15.37 15.37
5.05
14.73 14.73
5.45
14.07 14.07
5.91
13.32 13.32
6.39
12.60 12.60
6.93
11.84 11.84
7.53
17
16.37 14.30
5.12
15.66 13.90
5.56
14.80 13.42
6.00
13.86 12.90
6.46
12.92 12.36
6.98
11.98 11.78
7.56
19
17.84 12.12
5.21
17.19 11.82
5.69
16.40 11.45
6.20
15.51 11.03
6.73
14.49 10.55
7.24
13.47 10.09
7.84
22
19.07
9.77
5.30
18.65
9.62
5.79
17.93
9.34
6.31
17.08
8.99
6.87
16.15
8.61
7.47
15.15
8.21
8.12
945
14
15.99 15.99
5.21
15.38 15.38
5.64
14.67 14.67
6.10
13.91 13.91
6.58
13.13 13.13
7.13
12.34 12.34
7.74
17
16.68 15.20
5.25
15.98 14.80
5.71
15.12 14.29
6.16
14.19 13.73
6.63
13.19 13.19
7.14
12.33 12.33
7.74
19
18.12 12.71
5.34
17.50 12.48
5.82
16.70 12.12
6.33
15.82 11.70
6.89
14.80 11.24
7.43
13.72 10.75
8.01
22
19.26 10.02
5.42
18.90
9.95
5.91
18.19
9.71
6.43
17.35
9.38
7.00
16.41
9.01
7.60
15.39
8.61
8.25
1060
14
16.50 16.50
5.34
15.91 15.91
5.81
15.20 15.20
6.28
14.43 14.43
6.79
13.58 13.58
7.32
12.77 12.77
7.94
17
16.94 16.01
5.37
16.23 15.59
5.83
15.41 15.07
6.31
14.48 14.48
6.80
13.57 13.57
7.32
12.76 12.76
7.94
19
18.32 13.24
5.45
17.74 13.09
5.94
16.93 12.76
6.46
16.03 12.35
7.02
15.05 11.90
7.61
13.92 11.39
8.17
22
19.38 10.23
5.54
19.05 10.23
6.04
18.40 10.04
6.56
17.55
9.74
7.12
16.60
9.38
7.72
15.57
9.00
8.36
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
FB4BN(F,B)
060
1.01
1.01
FB4BNF
070
1.02
0.98
Summary of Contents for 38CKS