Guide speci

fi

cations

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system air conditioner 

unit suitable for ground or rooftop installation. Unit consists 
of a hermetic compressor, an air-cooled coil, propeller-type 
condenser fan, and a control box. Unit will discharge supply 
air upward as shown on contract drawings. Unit will be used 
in a refrigeration circuit to match up to a packaged fan coil 
or coil unit.

Quality Assurance

Unit construction will comply with latest edition of ANSI/

ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards 

and will carry the UL label of approval. Unit will have c-UL 
approval.

The condenser coil will be capable of withstanding the 

following test method standards: Salt Spray test, ASTM 
B117 1,000 hrs, and the Prohesion Test ASTM G85-A5 
1,000 hrs.

Air-cooled condenser coils will be leak tested at 150 psig 

(1034 KPa) and pressure tested at 300 psig (2068 KPa).

Unit constructed in ISO 9001 approved facility.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored 

and handled per unit manufacturer’s recommendations.

PRODUCTS

Equipment

Factory-assembled, single-piece, air-cooled air conditioner 

unit. Contained within the unit enclosure is all factory 
wiring, piping, controls, compressor, refrigerant charge 
(R22), and special features required prior to 

fi

eld start-up.

Unit Cabinet

Unit cabinet will be constructed of galvanized steel, 

bonderized, and coated with a powder coat paint.
Fans

Condenser fan will be direct-drive propeller type, 

discharging air upward.

Condenser fan motors will be totally enclosed, 1-phase 

type with class B insulation and permanently lubricated 
bearings.

Air-Cooled, Split-System

Air Conditioner

38CKS

1-1/2 to 5 Tons Nominal

(5.2 to 17.5 kW)

Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with PVC-coated 

steel wire safety guards.
Compressor

Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.
Coil will be constructed of aluminum 

fi

ns with a resin-

based epoxy phenolic thermoset coating, factory applied by 
pre-coating and baking. The 

fi

ns are mechanically bonded to 

copper tubes which are then cleaned, dehydrated, and sealed.
Refrigeration Components

Refrigeration circuit components will include liquid line 

shutoff valve with sweat connections, suction line shutoff 
valves with sweat connections, system charge of R22 
refrigerant, and compressor oil.

Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at 

a suction temperature of _____ °F (°C). The power 
consumption at full load will not exceed _____ kW.

Combination of the unit and the evaporator or fan coil unit 

will have a total net cooling capacity of _____ Btuh (kW) or 
greater at conditions of _____ CFM entering air temperature 
at the evaporator at _____ °F (°C) wet bulb and _____ °F 
(°C) dry bulb, and air entering the unit at _____ °F (°C).

The system will have a SEER of _____ Btuh/watt or greater 

at DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be _____ v, 

single phase, 60 hz. The unit will be capable of satisfactory 
operation within voltage limits of _____ v 
to _____ v.

Unit electrical power will be single point connection.
Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories 

and descriptions for speci

fi

c features and available 

enhancements.

Summary of Contents for 38CKS

Page 1: ...otective coating on the coil Heavy Duty Inlet Grille The WeatherArmor coil protector made of a coated steel wire grid with vertical 3 8 in 9 5 mm spacing is designed to help protect the coil from incl...

Page 2: ...nt seating with provision for field sweat connections Valves are externally located for quick and easy refrigerant tube connections Each valve provides service ports for ease in checking operating ref...

Page 3: ...125 COND COIL Face Area Sq Ft m2 Fins per In Fins per cm Rows Circuits Copper Tube Aluminum Plate Fin 6 8 63 9 1 85 9 9 92 12 4 1 15 14 8 1 37 18 5 1 72 16 1 1 50 20 8 20 8 20 8 20 8 20 8 20 8 20 8 1...

Page 4: ...or and Relay Size 042 KSAHS1601AAA Start Assist Capacitor and Relay Sizes 048 060 KAACS0201PTC Start Assist PTC All Sizes KAACH1001AAA Crankcase Heater Sizes 018 042 KAACH1201AAA Crankcase Heater Size...

Page 5: ...to the compressor motor at each start up Usage Guideline Suggested when compressor power supply is marginal Suggested in reciprocating compressor applications with rapid pressure balance RPB expansion...

Page 6: ...sure at low ambient temperatures down to 0 F 17 8 C when properly installed Usage Guideline A Low Ambient Pressure Switch or Motor Master Low Ambient Controller must be used when cooling operation is...

Page 7: ...path between the unit and service panel for a voltage drop not to exceed 2 Time delay fuse FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps NOTES 1 Control circuit...

Page 8: ...65 2 365 1 496 9 560 4 260 4 241 3 298 5 571 5 X 571 5 036 A 571 5 862 01 81 0 19 1 93 7 460 4 501 7 565 2 365 1 496 9 560 4 260 4 241 3 393 7 571 5 X 571 5 042 A 762 0 709 61 82 6 22 2 165 1 596 9 69...

Page 9: ...0 800 380 23 800 6 97 2 43 9 80 19 500 5 71 2 79 030 3A FB4BNF030 1000 467 28 600 8 38 3 04 9 40 23 200 6 80 3 41 FB4BNF036 1000 467 28 800 8 44 3 06 9 40 23 500 6 89 3 36 FA4CN F C 030 1000 467 29 00...

Page 10: ...90 2 98 7 55 5 51 3 15 6 82 5 13 3 31 6 13 4 78 3 48 22 10 59 5 42 2 67 9 93 5 13 2 87 9 22 4 83 3 07 8 49 4 52 3 27 7 74 4 20 3 48 7 00 3 88 3 68 470 14 8 63 8 63 2 58 8 02 8 02 2 74 7 40 7 40 2 91 6...

Page 11: ...30 4 87 8 68 8 68 5 18 17 12 25 10 96 3 73 11 57 10 62 4 05 10 82 10 23 4 31 10 04 9 80 4 59 9 31 9 31 4 87 8 67 8 67 5 18 19 13 41 9 21 3 83 12 86 9 04 4 17 12 16 8 77 4 51 11 33 8 42 4 82 10 49 8 0...

Page 12: ...15 37 5 05 14 73 14 73 5 45 14 07 14 07 5 91 13 32 13 32 6 39 12 60 12 60 6 93 11 84 11 84 7 53 17 16 37 14 30 5 12 15 66 13 90 5 56 14 80 13 42 6 00 13 86 12 90 6 46 12 92 12 36 6 98 11 98 11 78 7 56...

Page 13: ...42 2 92 72 28 79 14 67 2 01 27 33 14 06 2 21 25 62 13 35 2 42 23 78 12 60 2 64 21 86 11 81 2 87 19 87 10 99 3 10 800 57 23 26 23 26 1 94 21 74 21 74 2 11 20 27 20 27 2 28 18 73 18 73 2 47 17 26 17 26...

Page 14: ...4 97 25 79 4 98 32 14 24 62 5 26 72 48 12 24 41 3 83 46 80 23 94 4 19 44 82 23 19 4 54 42 40 22 28 4 90 39 55 21 15 5 26 36 67 20 07 5 57 1400 57 39 57 39 57 3 68 37 75 37 75 3 97 35 79 35 79 4 26 33...

Page 15: ...52 46 52 46 5 05 50 29 50 29 5 45 48 01 48 01 5 91 45 47 45 47 6 39 42 99 42 99 6 93 40 41 40 41 7 53 62 55 86 48 81 5 12 53 43 47 43 5 56 50 50 45 80 6 00 47 31 44 02 6 46 44 11 42 18 6 98 40 89 40 2...

Page 16: ...88 1 91 1 94 4 TCG 9 00 8 20 7 50 6 70 6 00 5 30 4 60 4 00 SDT 30 00 35 00 40 00 45 00 49 00 53 00 58 00 62 00 KW 1 67 1 76 1 85 1 91 1 96 2 00 2 04 2 09 7 TCG 10 30 9 30 8 50 7 70 7 00 6 20 5 50 4 8...

Page 17: ...7 3 71 4 TCG 15 60 14 20 13 00 11 80 10 70 9 50 8 40 7 30 SDT 29 00 35 00 39 00 44 00 49 00 53 00 58 00 62 00 KW 2 90 3 16 3 39 3 57 3 69 3 82 3 92 3 98 7 TCG 17 80 16 10 14 70 13 40 12 20 10 90 9 70...

Page 18: ...00 35 00 40 00 45 00 50 00 54 00 59 00 64 00 KW 3 73 4 10 4 46 4 81 5 19 5 62 6 07 6 53 4 TCG 19 10 18 60 17 90 17 00 15 90 14 70 13 60 12 30 SDT 30 00 36 00 41 00 46 00 51 00 56 00 61 00 65 00 KW 3 7...

Page 19: ...1 1 94 40 TCG 30 60 27 90 25 40 23 00 20 50 18 10 15 80 13 60 SDT 86 90 95 50 103 80 112 10 120 20 128 00 136 00 144 10 KW 1 67 1 76 1 85 1 91 1 96 2 00 2 04 2 09 45 TCG 35 00 31 80 29 10 26 40 23 80...

Page 20: ...9 3 60 3 67 3 71 40 TCG 53 20 48 40 44 30 40 30 36 40 32 60 28 80 24 90 SDT 85 10 94 30 103 10 111 60 120 00 128 10 136 20 144 10 KW 2 90 3 16 3 39 3 57 3 69 3 82 3 92 3 98 45 TCG 60 80 55 00 50 20 45...

Page 21: ...60 103 70 112 40 121 10 129 80 138 60 147 40 KW 3 73 4 10 4 46 4 81 5 19 5 62 6 07 6 53 40 TCG 65 30 63 40 61 10 58 10 54 40 50 30 46 30 42 00 SDT 86 10 96 80 106 00 115 00 123 80 132 30 141 00 149 8...

Page 22: ...or interconnecting refrigerant tube lengths between 50 15 24m and 175 53 34m ft and or 20 6 1m ft vertical dif ferential consult Residential s Split System Long Line Application Guideline available fr...

Page 23: ...23...

Page 24: ...drive propeller type discharging air upward Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Air Cooled Split System Air Condition...

Reviews: