System Design Summary
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less
than 0.01-in. wc.
2. Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).
3. Maximum outdoor operating air temperature is 125°F (51.7°C).
4. For reliable operation, unit should be level in all horizontal planes.
5. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft (15.24m), indoor
coil below = 150 ft (45.72m).
6. For interconnecting refrigerant tube lengths between 50 (15.24m) and 175 (53.34m) ft and/or 20 (6.1m) ft vertical dif-
ferential, consult Residential’s Split System Long-Line Application Guideline available from equipment distributor.
7. Crankcase heater required when interconnecting refrigerant tube length exceeds 50 ft (15.24m).
8. If any refrigerant tubing is buried, provide a minimum 6 in. (152mm) vertical rise to the valve connections at the
unit. Refrigerant tubing lengths up to 36 in. (912mm) may be buried without further consideration. For buried lines
longer than 3 ft (912mm), consult your local distributor.
9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of
connector provided.