Electrical data
* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70)
Article 336-26. If other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded
wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
‡ Length shown is as measured 1 way along wire path between the unit and service panel for a voltage drop not to exceed 2%.
** Time-delay fuse.
FLA
— Full Load Amps
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
RLA
— Rated Load Amps
NOTES:
1. Control circuit is 24v on all units and requires external power source.
2. Copper wire must be used from service disconnect to unit.
3. All motors/compressors contain internal overload protection.
UNIT
SIZE-SERIES
V/PH
OPER VOLTS*
COMPRESSOR
FAN
FLA
MCA
60°C
MIN
WIRE
SIZE†
75°C
MIN
WIRE
SIZE†
60°C
MAX
LENGTH
(Ft)‡
75°C
MAX
LENGTH
(Ft)‡
MAX FUSE** OR
CKT BKR AMPS
Max
Min
LRA
RLA
018-3A
208-230-1
253
197
48.0
9.0
0.8
12.1
14
14
65
61
20
024-3A
61.0
12.2
0.5
15.8
14
14
49
47
20
030-3A
73.0
14.0
0.8
18.4
14
14
40
38
25
036-3A
86.0
17.7
1.4
23.5
12
12
58
55
35
042-3A
102.0
19.7
1.4
26.0
10
10
75
70
40
048-3A
140.0
24.4
1.4
31.9
8
10
95
55
50
060-3A
165.0
28.9
1.4
37.5
8
8
80
75
60