6

 

Accessory description and usage (continued)

 

5.

 

Crankcase Heater

 

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles.  Improves compressor lubrication on
restart and minimizes the chance of liquid slugging. 

Usage Guideline:

Required in low ambient applications.
Required in long line applications.
Suggested in all commercial applications.

 

6.

 

Evaporator Freeze Thermostat

 

An SPST temperature-actuated switch that stops unit operation when evaporator reaches freeze-up conditions.

Usage Guideline:

Required when low ambient kit has been added.

 

7.

 

Filter Drier—Bi-Flow

 

A device for removing contaminants from refrigerant circulating in an air conditioning system: single-direction flow.

Usage Guideline:

Suggested in all field-connected split-system air conditioners.

 

8.

 

High-Pressure Switch 

 

Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 426 ± 10 psig
and resets at 320 ± 20 psig. Provides protection against compressor damage due to loss of outdoor airflow.

Usage Guideline:

Suggested in installations exposed to "very dirty" outdoor air.
Suggested in installations where condenser inlet air temperature exceeds 125°F. (51.7°C)

 

9.

 

Liquid-Line Solenoid Valve (LLS)  

 

This device serves two purposes. It is an electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation.
It maintains a column of refrigerant liquid ready for action at next compressor operation cycle. It also provides system protection against off-cycle refrigerant
migration. 

 

NOTE:

 

 

 

When LLS is used with reciprocating compressors, Compressor Start Assist — Capacitor and Relay is required.

Usage Guideline:

Required in air conditioner long line applications with a piston indoor metering device to prevent off cycle refrigerant migration. A hard shut 
off TXV can be used instead of LLS in single flow air conditioner applications. See Long Line Application Guideline.

 

10.

 

Low-Ambient Pressure Switch 

 

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure
within normal operating limits (approximately 100 psig to 225 psig). The control will maintain working head pressure at low-ambient temperatures down to 0°F
(–17.8°C) when properly installed.

Usage Guideline:

A Low-Ambient Pressure Switch or Motor Master ®—Low-Ambient Controller must be used when cooling operation is used at outdoor tem-
peratures below 55°F (12.8°C). 

 

11.

 

MotorMaster®-Low-Ambient Controller

 

A fan speed control device activated by a temperature sensor, designed to control condenser fan motor speed in response to the saturated, condensing temperature
during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at 100°F ± 10°F (37.8°C ± –
12°C).

Usage Guideline:

A Motor Master ®—Low-Ambient Controller or Low-Ambient Pressure Switch must be used when cooling operation is used at outdoor tem-
peratures below 55°F (12.8°C). 
Suggested for all commercial applications.

 

12.

 

Outdoor Air Temperature Sensor

 

Designed for use with Carrier Thermostats listed in this publication. The device enables the thermostat to display the outdoor temperature. This device also is
required to enable special thermostat features such as auxiliary heat lock out.

Usage Guideline:

Suggested for all Carrier thermostats listed in this publication.

 

13.

 

Sound Hood

 

Wraparound sound reducing cover for the compressor. Reduces the sound level by about 2 dBA.

Usage Guideline:

Suggested when unit is installed closer than 15 ft to quiet areas—bedrooms, etc.
Suggested when unit is installed between two houses less than 10 ft apart.

 

14.

 

Thermostatic Expansion Valve (TXV)  Single-Flow

 

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the
evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB valves are available.  

NOTE: 

When using a hard shut off TXV with single phase reciprocating compressors, a Compressor Start Assist — Capacitor and Relay is required.

Usage Guideline:

Required to achieve ARI ratings in certain equipment combinations. Refer to combination ratings. 
Hard shut off TXV or LLS required in air conditioner long line applications.
Required for use on all zoning systems.

15.

Time-Delay Relay 

An SPST delay relay which briefly continues operation of indoor blower motor to provide additional cooling after the compressor cycles off.

NOTE: 

Most indoor unit controls include this feature.  For those that do not, use the guideline below.

Usage Guideline:

For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

Summary of Contents for 38CKS

Page 1: ...otective coating on the coil Heavy Duty Inlet Grille The WeatherArmor coil protector made of a coated steel wire grid with vertical 3 8 in 9 5 mm spacing is designed to help protect the coil from incl...

Page 2: ...nt seating with provision for field sweat connections Valves are externally located for quick and easy refrigerant tube connections Each valve provides service ports for ease in checking operating ref...

Page 3: ...125 COND COIL Face Area Sq Ft m2 Fins per In Fins per cm Rows Circuits Copper Tube Aluminum Plate Fin 6 8 63 9 1 85 9 9 92 12 4 1 15 14 8 1 37 18 5 1 72 16 1 1 50 20 8 20 8 20 8 20 8 20 8 20 8 20 8 1...

Page 4: ...or and Relay Size 042 KSAHS1601AAA Start Assist Capacitor and Relay Sizes 048 060 KAACS0201PTC Start Assist PTC All Sizes KAACH1001AAA Crankcase Heater Sizes 018 042 KAACH1201AAA Crankcase Heater Size...

Page 5: ...to the compressor motor at each start up Usage Guideline Suggested when compressor power supply is marginal Suggested in reciprocating compressor applications with rapid pressure balance RPB expansion...

Page 6: ...sure at low ambient temperatures down to 0 F 17 8 C when properly installed Usage Guideline A Low Ambient Pressure Switch or Motor Master Low Ambient Controller must be used when cooling operation is...

Page 7: ...path between the unit and service panel for a voltage drop not to exceed 2 Time delay fuse FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps NOTES 1 Control circuit...

Page 8: ...65 2 365 1 496 9 560 4 260 4 241 3 298 5 571 5 X 571 5 036 A 571 5 862 01 81 0 19 1 93 7 460 4 501 7 565 2 365 1 496 9 560 4 260 4 241 3 393 7 571 5 X 571 5 042 A 762 0 709 61 82 6 22 2 165 1 596 9 69...

Page 9: ...0 800 380 23 800 6 97 2 43 9 80 19 500 5 71 2 79 030 3A FB4BNF030 1000 467 28 600 8 38 3 04 9 40 23 200 6 80 3 41 FB4BNF036 1000 467 28 800 8 44 3 06 9 40 23 500 6 89 3 36 FA4CN F C 030 1000 467 29 00...

Page 10: ...90 2 98 7 55 5 51 3 15 6 82 5 13 3 31 6 13 4 78 3 48 22 10 59 5 42 2 67 9 93 5 13 2 87 9 22 4 83 3 07 8 49 4 52 3 27 7 74 4 20 3 48 7 00 3 88 3 68 470 14 8 63 8 63 2 58 8 02 8 02 2 74 7 40 7 40 2 91 6...

Page 11: ...30 4 87 8 68 8 68 5 18 17 12 25 10 96 3 73 11 57 10 62 4 05 10 82 10 23 4 31 10 04 9 80 4 59 9 31 9 31 4 87 8 67 8 67 5 18 19 13 41 9 21 3 83 12 86 9 04 4 17 12 16 8 77 4 51 11 33 8 42 4 82 10 49 8 0...

Page 12: ...15 37 5 05 14 73 14 73 5 45 14 07 14 07 5 91 13 32 13 32 6 39 12 60 12 60 6 93 11 84 11 84 7 53 17 16 37 14 30 5 12 15 66 13 90 5 56 14 80 13 42 6 00 13 86 12 90 6 46 12 92 12 36 6 98 11 98 11 78 7 56...

Page 13: ...42 2 92 72 28 79 14 67 2 01 27 33 14 06 2 21 25 62 13 35 2 42 23 78 12 60 2 64 21 86 11 81 2 87 19 87 10 99 3 10 800 57 23 26 23 26 1 94 21 74 21 74 2 11 20 27 20 27 2 28 18 73 18 73 2 47 17 26 17 26...

Page 14: ...4 97 25 79 4 98 32 14 24 62 5 26 72 48 12 24 41 3 83 46 80 23 94 4 19 44 82 23 19 4 54 42 40 22 28 4 90 39 55 21 15 5 26 36 67 20 07 5 57 1400 57 39 57 39 57 3 68 37 75 37 75 3 97 35 79 35 79 4 26 33...

Page 15: ...52 46 52 46 5 05 50 29 50 29 5 45 48 01 48 01 5 91 45 47 45 47 6 39 42 99 42 99 6 93 40 41 40 41 7 53 62 55 86 48 81 5 12 53 43 47 43 5 56 50 50 45 80 6 00 47 31 44 02 6 46 44 11 42 18 6 98 40 89 40 2...

Page 16: ...88 1 91 1 94 4 TCG 9 00 8 20 7 50 6 70 6 00 5 30 4 60 4 00 SDT 30 00 35 00 40 00 45 00 49 00 53 00 58 00 62 00 KW 1 67 1 76 1 85 1 91 1 96 2 00 2 04 2 09 7 TCG 10 30 9 30 8 50 7 70 7 00 6 20 5 50 4 8...

Page 17: ...7 3 71 4 TCG 15 60 14 20 13 00 11 80 10 70 9 50 8 40 7 30 SDT 29 00 35 00 39 00 44 00 49 00 53 00 58 00 62 00 KW 2 90 3 16 3 39 3 57 3 69 3 82 3 92 3 98 7 TCG 17 80 16 10 14 70 13 40 12 20 10 90 9 70...

Page 18: ...00 35 00 40 00 45 00 50 00 54 00 59 00 64 00 KW 3 73 4 10 4 46 4 81 5 19 5 62 6 07 6 53 4 TCG 19 10 18 60 17 90 17 00 15 90 14 70 13 60 12 30 SDT 30 00 36 00 41 00 46 00 51 00 56 00 61 00 65 00 KW 3 7...

Page 19: ...1 1 94 40 TCG 30 60 27 90 25 40 23 00 20 50 18 10 15 80 13 60 SDT 86 90 95 50 103 80 112 10 120 20 128 00 136 00 144 10 KW 1 67 1 76 1 85 1 91 1 96 2 00 2 04 2 09 45 TCG 35 00 31 80 29 10 26 40 23 80...

Page 20: ...9 3 60 3 67 3 71 40 TCG 53 20 48 40 44 30 40 30 36 40 32 60 28 80 24 90 SDT 85 10 94 30 103 10 111 60 120 00 128 10 136 20 144 10 KW 2 90 3 16 3 39 3 57 3 69 3 82 3 92 3 98 45 TCG 60 80 55 00 50 20 45...

Page 21: ...60 103 70 112 40 121 10 129 80 138 60 147 40 KW 3 73 4 10 4 46 4 81 5 19 5 62 6 07 6 53 40 TCG 65 30 63 40 61 10 58 10 54 40 50 30 46 30 42 00 SDT 86 10 96 80 106 00 115 00 123 80 132 30 141 00 149 8...

Page 22: ...or interconnecting refrigerant tube lengths between 50 15 24m and 175 53 34m ft and or 20 6 1m ft vertical dif ferential consult Residential s Split System Long Line Application Guideline available fr...

Page 23: ...23...

Page 24: ...drive propeller type discharging air upward Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Air Cooled Split System Air Condition...

Reviews: