background image

16

ENVIRONMENTAL
MANAGEMENT

TROUBLESHOOTING CHART

Below we list a series of possible faults, along with the probable causes and suggested solutions. In the event of a unit
malfunction, it is advisable to disconnect the power supply and ascertain the cause.

SYMPTOMS

CAUSE

REMEDY

Compressor does not run

Compressor stops or cycles rapidly on
low-pressure control

Compressor cycles rapidly on high-
pressure control

Operating cycles too long or continuous
operation

System noises

Compressor loses oil

Frosted or sweating suction line

Hot liquid line

Frosted liquid line

Compressor will not unload

Compressor will not load

Reset circuit breaker
Check control circuit for ground or short; repair and
reset breaker
Reset thermostat
Replace contactor
Check connections
Check wiring and rewire
Check line voltage - determine location of voltage
drop and remedy deficiency
Check motor windings for open or short. Replace
compressor, if necessary
Replace compressor
Check chilled water pump. Check switch.

Raise differential setting. Check capillary for pinches.
Replace control.
Open valve
Add refrigerant
Clean strainer. Clean or replace.

Check capillary tube for pinches. Set control as
required.
Open valve, or replace if defective.
Purge, dehydrate and recharge.
Check motor and wiring. Repair or replace if defective.
Check fan position and security on shaft.

Add refrigerant.
Replace control device concerned
Purge
Clean or replace
Replace or repair
Check valves, replace if necessary.

Support piping as required. Check for loose pipe
connectors.
Add refrigerant. Check for blocked liquid line strainer.
Check valve plates for valve noise. Replace
compressor (worn bearings). Check for loose
compressor hold-down bolts.

Find and repair leak, pump down and recharge.
Replace heaters, check wiring.

Adjust expansion valves.

Repair leak and recharge.
Adjust expansion valve.

Remove restriction or replace filter-drier.

Replace coil.
Replace.
Wire correctly.
Replace.

Replace.
Wire correctly.
Clean.

Power line open
Tripped circuit breaker

Safety thermostat tripped
Contactor stuck open
Loose terminal connection
Improperly wired controls
Low line voltage

Compressor motor defective

Seized compressor
Chilled water flow switch open

Low-pressure control erratic in action

Compressor discharge valve partially closed
Low refrigerant charge
Filter-drier blocked or fouled

High-pressure control erratic in action

Compressor discharge valve partially closed
Air in system
Condenser fan(s) not operating or low air flow

Low refrigerant charge
Control contacts fused
Air in system
Partially blocked or blocked expansion valve or strainer
Defective insulation
Inefficient compressor

Piping vibrations

Expansion valve hissing
Compressor noisy

Leak in system
Crankcase heaters not energizing during shutdown

Expansion valve admitting too much refrigerant

Shortage of refrigerant due to leak
Expansion valve closed too far

Restricted filter-drier

Burnt-out coil
Leaky bypass piston
Miswired solenoid
Weak bypass piston spring

Damaged bypass piston
Miswired solenoid
Blocked bypass port strainer (high side)

Order No. 13811-76, May 1998. Supersedes order No.: 13811-76, September 1996 + 13883-76, April 1995.

Manufactured by: Carrier SA, Montluel, France.

Manufacturer reserves the right to change any product specifications without notice.

Printed on Totally Chlorine-Free Paper.

Printed in the Netherlands.

Summary of Contents for 38AJ 008

Page 1: ...1 QUALITY ASSURANCE SYSTEM 38AJ 008 074 R 22 38AZ 008 074 R 407C Air Cooled Condensing Units 50 Hz Installation Operation and Maintenance Instructions...

Page 2: ...trol systems 11 Pressure operated control valve 11 Control setpoint 11 Setpoint control 11 Pressure differential 12 Modifications 12 Servicing refrigeration components 13 General maintenance 13 Liquid...

Page 3: ...gas pressure kPa Pressure drop air kPa Circuit 2 Suction gas temperature C Discharge air pressure Pa Suction gas pressure kPa Fan speed r s or rpm Fan motor input Ph 1 V Ph 2 V Ph 3 V Ph 1 V Ph 2 V P...

Page 4: ...70 1912 2500 1200 500 1200 062 074 2900 2156 2060 2500 1200 500 1200 Legend All dimensions are given in mm Required clearance space for servicing Power supply Water inlet Water outlet Do not obstruct...

Page 5: ...unit These units are designed for outdoor installation CAUTION Ensure the air flow around the unit is not obstructed At least two sides of the units must be free from obstructions to ensure proper ai...

Page 6: ...n dew point temperature R 407C of 10 C saturated discharge temperature R 22 or discharge dew point temperature of 68 3 C ICF maximum instantaneous current during starting equal to the current value of...

Page 7: ...unit Moving Do not remove skids pallets or protective packaging until the unit is in its final position Move the chiller using tubes or rollers or lift it using slings of the correct capacity Siting B...

Page 8: ...sure Legend 1 Condenser 2 Liquid line valve 3 Filter drier 4 Sight glass 5 Fan cycling pressure switch 6 Suction valve NOTE The typical refrigeration circuit diagram shown does not apply to all contro...

Page 9: ...tions to accomplish this Bypass hot gas if used should be introduced before the evaporator Consult your local Carrier distributor The oil charge must be adjusted to allow for extra line length This is...

Page 10: ...tions use the piping shown for the upper and the middle sections 3 The lower section is always the first section to be activated and the last to be shut off 4 Refer to the Carrier System Design Manual...

Page 11: ...ergized when the unit is switched off to ensure proper lubrication of the compressor Open the compressor suction and discharge line valves and then close them one turn each to stabilise the pressure t...

Page 12: ...Pressure operated control valve Modifications It is possible to convert pressure controlled capacity reductions to electrically controlled reductions or to add capacity reductions in accordance with t...

Page 13: ...es Refrigeration installations must be inspected and maintained regularly and rigorously by specialists Their activities must be overseen and checked by properly trained people To minimise discharge t...

Page 14: ...hen to ON NOTE Damage resulting from failure to follow these instruction is not covered by the product warranty Compressor motor protection Compressor protection devices Circuit breaker Calibrated the...

Page 15: ...y removed through the top of the unit Take care not to damage the propeller Label the wires to facilitate correct reassembly later 38AJ AZ 008 012 fan Maximum clearance 80 mm mm 0 2 Maximum clearance...

Page 16: ...strainer Check valve plates for valve noise Replace compressor worn bearings Check for loose compressor hold down bolts Find and repair leak pump down and recharge Replace heaters check wiring Adjust...

Reviews: