background image

13

SERVICING REFRIGERATION COMPONENTS

Any technician attending the machine for any purpose must be
a fully qualified refrigeration engineer.

WARNING: Before doing any work on the machine ensure that
the power is switched and locked off and that all isolators are
tagged. If a refrigerant circuit is opened, it must be evacuated,
and recharged, after ensuring that the refrigerant is clean and
free from impurities, the filter-drier has been changed and the
unit has been tested for leaks. Before any operation on a
refrigerant circuit, it is necessary to remove the complete
charge of refrigerant from the unit with a refrigerant charge
recovery group.

General maintenance

Keep the unit itself and the space around it clean and free of
obstructions. Remove all rubbish such as packing materials, as
soon as the installation is completed.

Regularly clean the exposed pipework to remove all dust and
dirt. This makes detection of water leaks easier, and they can
be repaired before more serious faults develop.

Confirm that all screwed and bolted connections and joints are
secure. Secure connections prevent leaks and vibration from
developing.

Check that all insulation joints are securely closed and that all
insulation is firmly in place. Check all heat exchangers and all
pipework.

Confirm regularly that any phase imbalance in the three-phase
power supply is within acceptable limits.

Lubricate the hinges, locks and latches on the electrical control
box doors sparingly.

Liquid refrigerant charging

Checking the charge
Run the unit at full capacity for some time and then add
refrigerant until there are no bubbles in the sight glass. This
will generally mean adding more refrigerant than would be
needed to prevent bubbles from being seen in the sight glass.

WARNING: To ensure proper operation of these units there
must be at least 5 K of subcooling as the liquid refrigerant
enters the expansion valve (difference between the saturated
pressure at the liquid valve and the liquid temperature).

The 38AJ/AZ units use a liquid refrigerant charge. For your
information, we are reproducing here some extracts from the
official publication dealing with the design, installation,
operation and maintenance of air conditioning and refrigera-
tion systems and the training of people involved in these
activities, agreed by the air conditioning and refrigeration
industry.

Refrigerant guidelines
Refrigeration installations must be inspected and maintained
regularly and rigorously by specialists. Their activities must be
overseen and checked by properly trained people.
To minimise discharge to the atmosphere, refrigerants and
lubricating oil must be transferred using methods which reduce
leaks and losses to a minimum.

Leaks must be repaired immediately

A valve on the condenser liquid refrigerant outlet line
enables the refrigerant charge to be transferred to the
receiver provided specifically for this purpose.

If the residual pressure is too low to make the transfer
alone, a purpose-built refrigerant recovery unit must be
used.

Compressor lubricating oil contains refrigerant. Any oil
drained  from a system during maintenance must therefore
be handled and stored accordingly.

Refrigerant under pressure must never be discharged to
the atmosphere.

CAUTION: 38AZ units are designed to run on refrigerant
HFC-407C. This non-azeotropic refrigerant blend consists of
23% R-32, 25% of R-125 and 52% R-134a, and is character-
ised by the fact that at the time of the change in state the
temperature of the liquid/vapour mixture is not constant, as
with azeotropic refrigerants. All checks must be pressure tests,
and the appropriate pressure/temperature ratio table must be
used for the interpretation of the values.

Leak detection is especially important for units charged with
refrigerant R-407C. Depending on whether the leak occurs in
the liquid or in the vapour phase, the proportion of the
different components in the remaining liquid is not the same.

Undercharge
If there is not enough refrigerant in the system, this is indicated
by gas bubbles in the moisture sight glass. There are two
possiblities:

Small undercharge (bubbles in the sight glass, no
significant change in suction pressure).
-

After detection and repair the unit can be recharged.

-

The replenishment of the charge must always be done
in the liquid phase at the liquid line. The refrigerant
cylinder must contain a minimum of 10% of its initial
charge.

Significant undercharge (large bubbles in the sight glass,
drop in suction pressure).
-

After detection and repair completely drain the
refrigerant charge, using a refrigerant recovery unit,
then recharge completely, following the precautions
given above.

Compressors

Checking the oil charge
Check the oil level and add or remove oil as necessary so that
the level is 1/8 to 3/8 up each sight glass with the compressors
running normally.

WARNING: Use only oils which have been approved for use in
refrigeration compressors. Never use oil which has been
exposed to air.

Summary of Contents for 38AJ 008

Page 1: ...1 QUALITY ASSURANCE SYSTEM 38AJ 008 074 R 22 38AZ 008 074 R 407C Air Cooled Condensing Units 50 Hz Installation Operation and Maintenance Instructions...

Page 2: ...trol systems 11 Pressure operated control valve 11 Control setpoint 11 Setpoint control 11 Pressure differential 12 Modifications 12 Servicing refrigeration components 13 General maintenance 13 Liquid...

Page 3: ...gas pressure kPa Pressure drop air kPa Circuit 2 Suction gas temperature C Discharge air pressure Pa Suction gas pressure kPa Fan speed r s or rpm Fan motor input Ph 1 V Ph 2 V Ph 3 V Ph 1 V Ph 2 V P...

Page 4: ...70 1912 2500 1200 500 1200 062 074 2900 2156 2060 2500 1200 500 1200 Legend All dimensions are given in mm Required clearance space for servicing Power supply Water inlet Water outlet Do not obstruct...

Page 5: ...unit These units are designed for outdoor installation CAUTION Ensure the air flow around the unit is not obstructed At least two sides of the units must be free from obstructions to ensure proper ai...

Page 6: ...n dew point temperature R 407C of 10 C saturated discharge temperature R 22 or discharge dew point temperature of 68 3 C ICF maximum instantaneous current during starting equal to the current value of...

Page 7: ...unit Moving Do not remove skids pallets or protective packaging until the unit is in its final position Move the chiller using tubes or rollers or lift it using slings of the correct capacity Siting B...

Page 8: ...sure Legend 1 Condenser 2 Liquid line valve 3 Filter drier 4 Sight glass 5 Fan cycling pressure switch 6 Suction valve NOTE The typical refrigeration circuit diagram shown does not apply to all contro...

Page 9: ...tions to accomplish this Bypass hot gas if used should be introduced before the evaporator Consult your local Carrier distributor The oil charge must be adjusted to allow for extra line length This is...

Page 10: ...tions use the piping shown for the upper and the middle sections 3 The lower section is always the first section to be activated and the last to be shut off 4 Refer to the Carrier System Design Manual...

Page 11: ...ergized when the unit is switched off to ensure proper lubrication of the compressor Open the compressor suction and discharge line valves and then close them one turn each to stabilise the pressure t...

Page 12: ...Pressure operated control valve Modifications It is possible to convert pressure controlled capacity reductions to electrically controlled reductions or to add capacity reductions in accordance with t...

Page 13: ...es Refrigeration installations must be inspected and maintained regularly and rigorously by specialists Their activities must be overseen and checked by properly trained people To minimise discharge t...

Page 14: ...hen to ON NOTE Damage resulting from failure to follow these instruction is not covered by the product warranty Compressor motor protection Compressor protection devices Circuit breaker Calibrated the...

Page 15: ...y removed through the top of the unit Take care not to damage the propeller Label the wires to facilitate correct reassembly later 38AJ AZ 008 012 fan Maximum clearance 80 mm mm 0 2 Maximum clearance...

Page 16: ...strainer Check valve plates for valve noise Replace compressor worn bearings Check for loose compressor hold down bolts Find and repair leak pump down and recharge Replace heaters check wiring Adjust...

Reviews: