CL-6
23XL PIC II OPTIONS TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Auto Restart Option
0/1
DSABLE/ENABLE
DSABLE
Remote Contacts Option
0/1
DSABLE/ENABLE
DSABLE
Soft Stop Amps Threshold
40 to 100
%
100
Stall/Hot Gas Bypass
Stall Limit/HGBP Option
Select: Stall=0, HGBP=1
0/1
0
Min. Load Point (T1/P1)
Stall/HGBP Delta T1
0.5 to 20
ˆF
1.5
Stall/HGBP Delta P1
30 to 170
PSI
150
Full Load Point (T2/P2)
Stall/HGBP Delta T2
0.5 to 20
ˆF
4
Stall/HGBP Delta P2
30 to 250
PSI
200
Stall/HGBP Deadband
0.5 to 3
ˆF
1
Stall Protection
Stall Delta % Amps
5 to 20
%
10
Stall Time Period
7 to 10
MIN
8
Ice Build Control
Ice Build Option
0/1
DSABLE/ENABLE
DSABLE
Ice Build Termination
0=Temp, 1=Contacts, 2=Both
0 to 2
0
Ice Build Recycle
0/1
DSABLE/ENABLE
DSABLE
Refrigerant Leak Option
0/1
DSABLE/ENABLE
DSABLE
Refrigerant Leak Alarm mA
4 to 20
mA
20
Head Pressure Reference
Delta P @ 0% (4 mA)
20-30
PSI
25
Delta P @ 100% (20 mA)
35-50
PSI
35
Minimum Output
0-100
%
0