23XL PIC II SETUP1 TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Comp Motor Temp Override
150 to 200
DEG F
200
Cond Press Override
150 to 260
PSI
230
Comp Discharge Alert
125 to 200
DEG F
200
Chilled Medium
0/1
WATER/BRINE
WATER
Chilled Water Deadband.
5 to 2.0
ˆF
1.0
Evap Refrig Trippoint
0.0 to 40.0
DEG F
33
Refrig Override Delta T
2.0 to 5.0
ˆF
3
Condenser Freeze Point
–20 to 35
DEG F
34
Evap Flow Delta P Cutout
0.5 to 50.0
PSI
5.0
Cond Flow Delta P Cutout
0.5 to 50.0
PSI
5.0
Water Flow Verify Time
0.5 to 5
MIN
5
Oil Filter Pressure Alert
1-15
PSI
3
Recycle Control
Recycle Restart Delta T
2.0 to 10.0
DEG F
5
Recycle Shutdown Delta
0.5 to 4.0
DEG F
1
SPARE ALERT/ALARM ENABLE
Disable=0, Lo=1/3, Hi=2/4
Spare Temp #1 Enable
0 to 4
0
Spare Temp #1 Limit
–40 to 245
DEG F
245
Spare Temp #2 Enable
0 to 4
0
Spare Temp #2 Limit
–40 to 245
DEG F
245
23XL Model TC Comp?
0/1
NO/YES
1