23XL PIC II ISM_CONF TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Starter Type
(0=Full, 1=Red, 2=SS/VFD)
0 to 2
1
Motor Rated Line Voltage
200 to 13200
VOLTS
460
Volt Transformer Ratio: 1
1 to 35
1
Overvoltage Threshold
105 to 115
%
115
Undervoltage Threshold
85 to 95
%
85
Over/Under Volt Time
1 to 10
SEC
5
Voltage % Imbalance
1 to 10
%
10
Voltage Imbalance Time
1 to 10
SEC
5
Motor Rated Load Amps
10 to 5000
AMPS
200
Motor Locked Rotor Trip
100 to 60000
AMPS
1000
Locked Rotor Start Delay
1 to 10
cycles
5
Starter LRA Rating
100 to 60000
AMPS
2000
Motor Current CT Ratio: 1
3 to 1000
100
Current % Imbalance
5 to 40
%
15
Current Imbalance Time
1 to 10
SEC
5
3 Grnd Fault CT’s? (1=No)
0/1
NO/YES
YES
Ground Fault CT Ratio: 1
150
150
Ground Fault Current
1 to 25
AMPS
15
Ground Fault Start Delay
1 to 20
cycles
10
Ground Fault Persistence
1 to 10
cycles
5
Single Cycle Dropout
0/1
DSABLE/ENABLE
DSABLE
Frequency-60 Hz? (No=50)
0/1
NO/YES
YES
Line Frequency Faulting
0/1
DSABLE/ENABLE
DSABLE