
60
attached to the starter frame near the relays. Use
only the dashpot oil supplied with the starter. Do not
substitute.
Solid-state overload relays do not have oil.
4. Reapply starter control power (not main chiller power)
to check the electrical functions.
Ensure the starter (with relay 1CR closed) goes
through a complete and proper start cycle.
BENSHAW, INC. REDISTART MICRO SOLID-STATE
STARTER
1. Ensure all wiring connections are properly terminated
to the starter.
2. Verify the ground wire to the starter is installed prop-
erly and is sufficient size.
3. Verify the motors are properly grounded to the starter.
4. Ensure all of the relays are properly seated in their
sockets.
5. Verify the proper ac input voltage is brought into the
starter according to the certified drawings.
6. Apply power to the starter.
Oil Charge —
The oil charge for the 23XL compressor
holds approximately 8 gal. (30 L) of oil.
The chiller is shipped with oil in the compressor. When the
sump is full, the oil level should be no higher than the middle
of the upper sight glass, and minimum level is the bottom of
the lower sight glass (Fig. 2A and 2B). If oil is added, it must
meet Carrier’s specification for centrifugal compressor use as
described in the Oil Specification section. Charge the oil
through the oil charging valve located near the bottom of the
transmission housing (Fig. 2A and 2B). The oil must be
pumped from the oil container through the charging valve due
to higher refrigerant pressure. The pumping device must be
able to lift from 0 to 200 psig (0 to 1380 kPa) or above unit
pressure. Oil should only be charged or removed when the
chiller is shut down.
Power Up the Controls and Check the Oil
Heater —
Ensure that an oil level is visible in the compres-
sor before energizing the controls. A circuit breaker in the start-
er energizes the oil heater and the control circuit. When first
powered, the CVC should display the default screen within a
short period of time.
The oil heater is energized by powering the control circuit.
This should be done several hours before start-up to minimize
oil-refrigerant migration. The oil heater is controlled by the
PIC II and is powered through a contactor in the power panel.
Starters contain a separate circuit breaker to power the heater
and the control circuit. This arrangement allows the heater to
energize when the main motor circuit breaker is off for service
work or extended shutdowns. The oil heater relay status (OIL
HEATER RELAY) can be viewed on the COMPRESS table on
the CVC. Oil sump temperature can be viewed on the CVC de-
fault screen.
SOFTWARE VERSION — The software part number is la-
beled on the backside of the CVC module. The software ver-
sion also appears on the CVC configuration screen as the last
two digits of the software part number.
Software Configuration
As the 23XL unit is configured, all configuration settings
should be written down. A log, such as the one shown on pages
CL-1 to CL-12, provides a convenient list for configuration
values.
Input the Design Set Points —
Access the CVC set
point screen and view/modify the base demand limit set point,
and either the LCW set point or the ECW set point. The PIC II
can control a set point to either the leaving or entering chilled
water. This control method is set in the EQUIPMENT SER-
VICE (TEMP_CTL) table.
Input the Local Occupied Schedule
(OCCPC01S) —
Access the schedule OCCPC01S screen
on the CVC and set up the occupied time schedule according to
the customer’s requirements. If no schedule is available, the de-
fault is factory set for 24 hours occupied, 7 days per week in-
cluding holidays.
For more information about how to set up a time schedule,
see the Controls section, page 14.
The CCN Occupied Schedule (OCCPC03S) should be con-
figured if a CCN system is being installed or if a secondary
time schedule is needed.
NOTE: The default CCN Occupied Schedule OCCPC03S is
configured to be unoccupied.
Input Service Configurations —
The following con-
figurations require the CVC screen to be in the SERVICE por-
tion of the menu.
•
password
•
input time and date
•
CVC configuration
•
service parameters
•
equipment configuration
•
automated control test
PASSWORD — When accessing the SERVICE tables, a pass-
word must be entered. All CVC are initially set for a password
of 1-1-1-1.
INPUT TIME AND DATE — Access the TIME AND DATE
table on the SERVICE menu. Input the present time of day,
date, and day of the week. The HOLIDAY TODAY parameter
should only be configured to YES if the present day is a
holiday.
NOTE: Because a schedule is integral to the chiller control
sequence, the chiller will not start until the time and date have
been set.
CHANGE CVC CONFIGURATION IF NECESSARY —
From the SERVICE table, access the CVC CONFIGURA-
TION screen. From there, view or modify the CVC CCN ad-
dress, change to English or SI units, and change the password.
If there is more than one chiller at the jobsite, change the CVC
address on each chiller so that each chiller has its own address.
Note and record the new address. Change the screen to SI units
as required, and change the password if desired.
This equipment is at line voltage when AC power is con-
nected. Pressing the STOP button does not remove voltage.
Do not operate the chiller before the control configurations
have been checked and a Control Test has been satisfac-
torily completed. Protection by safety controls cannot
be assumed until all control configurations have been
confirmed.