Table 2 — LID Display Data (cont)
EXAMPLE 8 — SERVICE1 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT .
5. Scroll down to highlight SERVICE1.
6. Press SELECT .
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
Motor Temp Override*
150-200 (66-93)
DEG F (DEG C)
mt
over
200 (93)
Cond Press Override
90-200 (620-1379)
PSI (kPa)
cp
over
125 (862)
Refrig Override Delta T
2-5 (1-3)
DEG F (DEG C)
ref
over
3
D
(1.6
D
)
Chilled Medium
Water/Brine
medium
WATER
Brine Refrig Trippoint
8-40 (–13.3-4)
DEG F (DEG C)
br
trip
33 (1)
Compr Discharge Alert
125-200 (52-93)
DEG F (DEG C)
cd
alert
200 (93)
Bearing Temp Alert
165-210 (74-99)
DEG F (DEG C)
tb
alert
175 (79)
Water Flow Verify Time
0.5-5
MIN
wflow
t
5
Oil Press Verify Time
15-300
SEC
oilpr
t
15
Water/Brine Deadband
0.5-2.0 (0.3-1.1)
DEG F (DEG C)
cw
db
1.0 (0.6)
Recycle Restart Delta T
2.0-10.0 (1.1-5.6)
DEG F (DEG C)
rcycrdt
5 (2.8)
Recycle Shutdown Delta
0.5-4.0 (.27-2.2)
rcycsdt
1.0 (0.6)
Surge Limit/HGBP Option
0/1
srg
hgbp
0
Select: Surge=0, HGBP=1
Surge/HGBP Delta T1
0.5-15 (0.3-8.3)
DEG F (DEG C)
hgb
dt1
1.5 (0.8)
Surge/HGBP Delta P1
30-170 (207-1172)
PSI (kPa)
hgb
dp1
50 (345)
Min. Load Points (T1/P1)
Surge/HGBP Delta T2
0.5-15 (0.3-8.3)
DEG F (DEG C)
hgb
dt2
10 (5.6)
Surge/HGBP Delta P2
30-170 (207-1172)
PSI (kPa)
hgb
dp2
85 (586)
Full Load Points (T2/P2)
Surge/HGBP Deadband
1-3 (0.6-1.6)
DEG F (DEG C)
hgb
dp
1 (0.6)
Surge Delta Percent Amps
10-50
%
surge
a
25
Surge Time Period
1-5
MIN
surge
t
2
Demand Limit Source
0/1
dem
src
0
Select: Amps=0, Load=1
Amps Correction Factor
1-8
corfact
3
Motor Rated Load Amps
1-9999
AMPS
a
fs
200
Motor Rated Line Voltage
1-9999
VOLTS
v
fs
460
Meter Rated Line kW
1-9999
kW
kw
fs
600
Line Frequency
0/1
HZ
freq
0
Select: 0=60 Hz, 1=50 Hz
Compr Starter Type
REDUCE/FULL
starter
REDUCE
Condenser Freeze Point
–20-35 (–28.9-1.7)
DEG F (DEG C)
cdfreeze
34 (1)
Soft Stop Amps Threshold
40-100
%
softstop
100
Stop to Start Timer
3-50
MIN
stopmtr
20
External Gear Option
ENABLE/DSABLE
exg
opt
ENABLE
Mechanical Gear Oil Pump
ENABLE/DSABLE
mech
pmp
DSABLE
Auxiliary Gear Oil Pump
ENABLE/DSABLE
aux
pmp
DSABLE
Gear Oil Pressure Alert
15-20 (103-138)
PSI (kPa)
gearp
al
15 (103)
Gear Oil Temperature Alert
130-145 (54-63)
DEG F (DEG C)
geart
al
130 (54)
*Information is applicable to hermetic machines (19EX) only.
NOTE:
D
= delta degrees.
28