Table 2 — LID Display Data (cont)
EXAMPLE 2 — STATUS02 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press STATUS .
3. Scroll down to highlight STATUS02.
4. Press SELECT .
DESCRIPTION
POINT TYPE
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
INPUT
OUTPUT
Hot Gas Bypass Relay
X
OFF/ON
HGBR
*Chilled Water Pump
X
OFF/ON
CHWP
Chilled Water Flow
X
NO/YES
EVFL
*Condenser Water Pump
X
OFF/ON
CDP
Condenser Water Flow
X
NO/YES
CDFL
Compressor Start Relay
X
OFF/ON
CMPR
Compressor Start Contact
X
OPEN/CLOSED
1CR
AUX
Compressor Run Contact
X
OPEN/CLOSED
RUN
AUX
Starter Fault Contact
X
OPEN/CLOSED
STR
FLT
Pressure Trip Contact
X
OPEN/CLOSED
PRS
TRIP
Single Cycle Dropout
X
NORMAL/ALARM
V1
CYCLE
Oil Pump Relay
X
OFF/ON
OILR
Oil Heater Relay
X
OFF/ON
OILH
Motor Cooling Relay†
X
OFF/ON
MTRC
Auxiliary Oil Pump Relay
X
OFF/ON
AUXOILR
*Tower Fan Relay
X
OFF/ON
TFR
Compr. Shunt Trip Relay
X
OFF/ON
TRIPR
Alarm Relay
X
NORMAL/ALARM
ALM
Spare Prot Limit Input
X
ALARM/NORMAL
SPR
PL
†Information is applicable to hermetic machines only.
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
EXAMPLE 3 — STATUS03 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press STATUS .
3. Scroll down to highlight STATUS03.
4. Press SELECT .
DESCRIPTION
RANGE
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
OPTIONS BOARD 1
*Demand Limit 4-20 mA
4-20
mA
DEM
OPT
*Temp Reset 4-20 mA
4-20
mA
RES
OPT
*Common CHWS Sensor
–40-245 (–40-118)
DEG F (DEG C)
CHWS
*Common CHWR Sensor
–40-245 (–40-118)
DEG F (DEG C)
CHWR
*Remote Reset Sensor
–40-245 (–40-118)
DEG F (DEG C)
R
RESET
*Temp Sensor — Spare 1
–40-245 (–40-118)
DEG F (DEG C)
SPARE1
*Temp Sensor — Spare 2
–40-245 (–40-118)
DEG F (DEG C)
SPARE2
*Temp Sensor — Spare 3
–40-245 (–40-118)
DEG F (DEG C)
SPARE3
OPTIONS BOARD 2
*4-20 mA — Spare 1
4-20
mA
SPARE1
M
*4-20 mA — Spare 2
4-20
mA
SPARE2
M
*Temp Sensor — Spare 4
–40-245 (–40-118)
DEG F (DEG C)
SPARE4
*Temp Sensor — Spare 5
–40-245 (–40-118)
DEG F (DEG C)
SPARE5
*Temp Sensor — Spare 6
–40-245 (–40-118)
DEG F (DEG C)
SPARE6
*Temp Sensor — Spare 7
–40-245 (–40-118)
DEG F (DEG C)
SPARE7
*Temp Sensor — Spare 8
–40-245 (–40-118)
DEG F (DEG C)
SPARE8
*Temp Sensor — Spare 9
–40-245 (–40-118)
DEG F (DEG C)
SPARE9
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
24