Table 2 — LID Display Data (cont)
EXAMPLE 9 — SERVICE2 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT .
5. Scroll down to highlight SERVICE2.
6. Press SELECT .
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME DEFAULT VALUE
OPTIONS BOARD 1
20 mA POWER CONFIGURATION
External = 0, Internal = 1
RESET 20 mA Power Source
0,1
res
20 ma
0
DEMAND 20 mA Power Source
0,1
dem
20 ma
0
SPARE ALERT ENABLE
Disable = 0, 1 = High Alert, 2 = Low Alert,
3 = High Alarm, 4 = Low Alarm
Temp = Alert Threshold
CHWS Temp Enable
0-4
chws
en
0
CHWS Temp Alert
–40-245 (–40-118)
DEG F (DEG C) chws
al
245 (118)
CHWR Temp Enable
0-4
chwr
en
0
CHWR Temp Alert
–40-245 (–40-118)
DEG F (DEG C) chwr
al
245 (118)
Reset Temp Enable
0-4
rres
en
0
Reset Temp Alert
–40-245 (–40-118)
DEG F (DEG C) rres
al
245 (118)
Spare Temp 1 Enable
0-4
spr1
en
0
Spare Temp 1 Alert
–40-245 (–40-118)
DEG F (DEG C) spr1
al
245 (118)
Spare Temp 2 Enable
0-4
spr2
en
0
Spare Temp 2 Alert
–40-245 (–40-118)
DEG F (DEG C) spr2
al
245 (118)
Spare Temp 3 Enable
0-4
spr3
en
0
Spare Temp 3 Alert
–40-245 (–40-118)
DEG F (DEG C) spr3
al
245 (118)
OPTIONS BOARD 2
20 mA POWER CONFIGURATION
External = 0, Internal = 1
SPARE 1 20 mA Power Source
0,1
sp1
20 ma
0
SPARE 2 20 mA Power Source
0,1
sp2
20 ma
0
SPARE ALERT ENABLE
Disable = 0, 1 = High Alert, 2 = Low Alert,
3 = High Alarm, 4 = Low Alarm
Temp = Alert Threshold
Spare Temp 4 Enable
0-4
spr4
en
0
Spare Temp 4 Alert
–40-245 (–40-118)
DEG F (DEG C) spr4
al
245 (118)
Spare Temp 5 Enable
0-4
spr5
en
0
Spare Temp 5 Alert
–40-245 (–40-118)
DEG F (DEG C) spr5
al
245 (118)
Spare Temp 6 Enable
0-4
spr6
en
0
Spare Temp 6 Alert
–40-245 (–40-118)
DEG F (DEG C) spr6
al
245 (118)
Spare Temp 7 Enable
0-4
spr7
en
0
Spare Temp 7 Alert
–40-245 (–40-118)
DEG F (DEG C) spr7
al
245 (118)
Spare Temp 8 Enable
0-4
spr8
en
0
Spare Temp 8 Alert
–40-245 (–0-118)
DEG F (DEG C) spr8
al
245 (118)
Spare Temp 9 Enable
0-4
spr9
en
0
Spare Temp 9 Alert
–40-245 (–40-118)
DEG F (DEG C) spr9
al
245 (118)
NOTE: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp’’ threshold for each point listed. If the ‘‘Enable’’
is set to 1, a value above the ‘‘Temp’’ threshold generates an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp Alert’’ threshold
generates an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled. If the ‘‘Enable’’ is set to 3, a value above the ‘‘Temp’’ threshold
generates an alarm. If the ‘‘Enable’’ is set to 4, a value below the ‘‘Temp’’ threshold generates an alarm.
EXAMPLE 10 — SERVICE3 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT .
5. Scroll down to highlight SERVICE3.
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
Proportional Inc Band
2-10
gv
inc
6.5
Proportional Dec Band
2-10
gv
de
6.0
Proportional ECW Gain
1-3
gv
ecw
2.0
Guide Vane Travel Limit
30-100
%
gv
lim
50