background image

Replacement Aluminized Primary Heat Exchanger: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

7

Unit Checkout

6. Set thermostat to “OFF”. 
7. Turn on power at external disconnect, fuse or circuit breaker.
8. Turn on gas at external shut-off or gas meter.
9. Check  for  gas leaks  with a  commercially available  soap  solution

made specifically for the detection of leaks.

10. Manually close blower door switch.

11. Initiate  component  test  through  circuit  board  by  referring  to

“Component Test” on status code label on blower access door for

complete test sequence information.

12. If any  status  codes  are flashed, refer  to status code  label  on  unit

blower door.

13. Turn thermostat fan switch to “ON”, “Continuous” or jumper R to

G terminals at furnace control board.

14. Check  for  air  leakage  around  cell  panel.  It  may  be  necessary  to

remove heat exchanger assembly and top gasket between cell panel

and furnace casing top plate. Re-install and re-check for blower air

leaks.

15. Remove jumper(s) or set thermostat fan to “Auto” or “OFF”.
16. Release blower door switch.
17. Install blower access door.
18. Set thermostat to call for heat.
19. Allow unit to initiate a complete call for heat cycle.
20. Check for air leakage around collector box. A whistling noise may

indicate air leak in collector box seal.

NOTE: 

If there is a severe air leak in the collector box seal, pressure

switch may not close or will re-open, resulting in no ignition or erratic

burner operation.

NOTE: 

Heat Exchanger failure may have been caused by one or more of

the following conditions. As part of the system check-out, verify that the

following conditions are not affecting the operation of the furnace:

• Short Cycling-Defective thermostat: Incorrect thermostat anticipator

setting, dirty filter or over-sized furnace.

• Under firing/low  Btu input: Set  manifold pressure  and verify firing

rate as shown on rating plate by clocking the gas meter.

• Over-firing/high  Btu  input:  Set  manifold  pressure  and  verify  firing

rate as shown on rating plate by clocking the gas meter.

• Low temperature rise: Set unit for correct temperature rise range as

shown on unit rating plate.

• Contaminated  combustion  air:  Remove  contaminates  or  provide

ample fresh air for combustion.

• Excessive amounts of outside ventilation air: Return air temperature

cannot be below 60 degrees F for extended periods of time.

• Incorrect  venting  or  termination:  Recirculation  of  products  of

combustion  into  the  combustion  air  pipe  can  damage  the  furnace.

Verify  proper  venting  and  vent  termination  per  installation

instructions. For additional information, and a complete sequence of

furnace  operation,  refer  to  furnace  Installation,  Start-Up  and

Operating Instructions.

21. After  System  Check-out  is  complete,  set  thermostat  below  room

temperature.

22. Verify that burner  shuts down  and  blower completes  selected  off

delay time. 

23. Verify furnace operates properly and set thermostat to desired room

temperature.

24. Re-install outer door.

WARNING

!

FIRE OR EXPLOSION HAZARD 

Failure  to  follow  this  warning  could  result  in  personal  injury,  death

and/or property damage.

Never purge a gas line into a combustion chamber. Never test for gas

leaks with an open flame. Use a commercially available soap solution

made specifically for the detection of leaks to check all connections. A

fire or explosion may result causing property damage, personal injury

or loss of life.

WARNING

!

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury or death.

Blower  door  opens  115-v  power  to  furnace  control.  No  component

operation can occur unless switch is closed. Exercise caution to avoid

electrical  shock  from  exposed  electrical  components  when  manually

closing this switch for service purposes.

Summary of Contents for 1184802

Page 1: ...r Kit Part No 1186215 1186216 1186217 1186218 1186219 1186220 1184802 and 1184803 in 35 in 889 mm tall condensing gas furnaces see Table 2 for model sizes The low adhesion sealant used on the Coupling...

Page 2: ...Removal NOTE Use a back up wrench on the gas valve to prevent the valve from rotating on the manifold or damaging the mounting to the burner box s see Fig 2 1 Disconnect the gas pipe from gas valve an...

Page 3: ...screws from the tabs on inducer assembly that secures the inducer to the collector box Note there is one mounting tab directly under the vent elbow 5 Remove the inducer assembly and set aside 6 To av...

Page 4: ...Baffles to the Primary Cell Panel and set aside Separate Primary and Condensing Heat Exchangers 1 Remove the screws that attach the condensing heat exchanger assembly to the primary cell outlet panel...

Page 5: ...ion by inserting the sidewall baffle inward from the rear of coupling box to the indexing tab on the primary cell panel then align the baffle with the coupling box cover Insert the slot on the sidewal...

Page 6: ...two types of pressure switches The modulating pressure switch assembly has three pressure switches Two are side by side with the third switch mounted to the back of one of the switches All other furn...

Page 7: ...t anticipator setting dirty filter or over sized furnace Under firing low Btu input Set manifold pressure and verify firing rate as shown on rating plate by clocking the gas meter Over firing high Btu...

Page 8: ...ns Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 8 A160110 Fig 6 Heat Exchanger Removal Installation CELL PANEL 5217 9 2 35 0...

Page 9: ...e right to change at any time specifications and designs without notice and without obligations 9 A11442 Fig 7 Collector Box Gasket Condensate Trap A11438 Fig 8 Heat Exchanger Panel Assembly REMOVE OL...

Page 10: ...443 06 5311 04 Replaces 443 06 5311 03 Replacement Aluminized Primary Heat Exchanger Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without...

Reviews: