background image

Replacement Aluminized Primary Heat Exchanger: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

2

DESCRIPTION AND USAGE 

Use  this  Primary  Heat  Exchanger  kit  to  replace  a  failed primary  heat

exchanger.  This  Primary  Heat  Exchanger  Kit  contains  the  following

items, see 

Table 1

 for kit contents and 

Table 2

 for where used.

Table 1 – Kit Contents

Table 2 – Where Used

INSTALLATION

Unit Shut Down

1. Set room thermostat to lowest setting or “OFF.”
2. Disconnect power at external disconnect, fuse or circuit breaker.
3. Turn off gas at external shut-off or gas meter.
4. Remove outer doors and set aside.
5. Turn electric switch on gas valve to OFF.

A11361

Fig. 1 – Loosen Vent Pipe Clamp

A11443

Fig. 2 – Burner Assembly / Manifold Assembly / Gas Valve

Vent Pipe Removal

NOTE: 

It will be necessary to remove the vent pipe from the furnace in

order to remove the heat exchanger.

1. Support the vent pipe as close to the furnace as possible to prevent

damage to the vent system.

2. Cut vent pipe with a hacksaw and move the remaining vent pipe out

of the way. Secure the vent pipe if necessary.

3. Loosen both  clamps  at  the  vent  pipe  support  attached  to  furnace

casing.

4. Loosen  clamp  for  the  vent  pipe  at  vent  elbow  on  the  inducer

assembly, see 

Fig. 1

.

5. Remove  remaining  vent  pipe  through  the  furnace  casing  and  set

aside.

Manifold Removal / Burner Box Removal

NOTE: 

Use  a  back-up  wrench  on  the  gas  valve  to  prevent  the  valve

from rotating on the manifold or damaging the mounting to the burner

box, s, see 

Fig. 2

.

1. Disconnect the gas pipe from gas valve and remove pipe from the

furnace casing.

KIT NO

DESCRIPTION

1186215

2 Cell, 14-3/16 inch

1184803

3 Cell, 14-3/16 inch

1186216

3 Cell, 17-1/2 inch

1186219

3 Cell, 21 inch

1186220

4 Cell, 17-1/2 inch & 21 inch

1186217

5 Cell, 21 inch

1186218

6 Cell, 24-1/2 inch

1184802

7 Cell, 24-1/2 inch

Description

Quantity

Hex Head 8A 1/2-in. Screws

43 - 61

Screws

8 - 12

Heat Exchanger & Panel Assembly

1

Gasket

2

Collector Box Gasket

1

Cell Panel Insulation

1

Instructions

1

MODEL

KIT NUMBER

CASING WIDTH 

(in/mm)

0261408

1186215

14-3/16 (360)

0261410

1186215

14-3/16 (360)

0401410

1186215

14-3/16 (360)

040A030

1186215

14-3/16 (360)

0401712

1186215

17-1/2 (445)

0601412

1184803

14-3/16 (360)

0601714

1186216

17-1/2 (445)

0601716

1186216

17-1/2 (445)

060B042

1186216

17-1/2 (445)

0602120

1186219

21 (533)

0801714

1186220

17-1/2 (445)

0801716

1186220

17-1/2 (445)

080B048

1186220

17-1/2 (445)

0802120

1186220

21 (533)

080C060

1186220

21 (533)

1002114

1186217

21 (533)

1002116

1186217

21 (533)

100C042

1186217

21 (533)

100C048

1186217

21 (533)

1002120

1186217

21 (533)

1002122

1186217

21 (533)

100C060

1186217

21 (533)

100C066

1186217

21 (533)

1202420

1186218

24-1/2 (622)

120D060

1186218

24-1/2 (622)

1202422

1186218

24-1/2 (622)

120D066

1186218

24-1/2 (622)

1402420

1184802

24-1/2 (622)

Inducer Mounting Screw

Pressure Switch

Inducer Mounting Screw

Remove Vent Elbow

Vent Elbow Clamp

Remove Tube(s) from 

Standoffs

Inducer Mounting Screw

Inducer Mounting Screw

Pressure Switch
Mounting Screw

Summary of Contents for 1184802

Page 1: ...r Kit Part No 1186215 1186216 1186217 1186218 1186219 1186220 1184802 and 1184803 in 35 in 889 mm tall condensing gas furnaces see Table 2 for model sizes The low adhesion sealant used on the Coupling...

Page 2: ...Removal NOTE Use a back up wrench on the gas valve to prevent the valve from rotating on the manifold or damaging the mounting to the burner box s see Fig 2 1 Disconnect the gas pipe from gas valve an...

Page 3: ...screws from the tabs on inducer assembly that secures the inducer to the collector box Note there is one mounting tab directly under the vent elbow 5 Remove the inducer assembly and set aside 6 To av...

Page 4: ...Baffles to the Primary Cell Panel and set aside Separate Primary and Condensing Heat Exchangers 1 Remove the screws that attach the condensing heat exchanger assembly to the primary cell outlet panel...

Page 5: ...ion by inserting the sidewall baffle inward from the rear of coupling box to the indexing tab on the primary cell panel then align the baffle with the coupling box cover Insert the slot on the sidewal...

Page 6: ...two types of pressure switches The modulating pressure switch assembly has three pressure switches Two are side by side with the third switch mounted to the back of one of the switches All other furn...

Page 7: ...t anticipator setting dirty filter or over sized furnace Under firing low Btu input Set manifold pressure and verify firing rate as shown on rating plate by clocking the gas meter Over firing high Btu...

Page 8: ...ns Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 8 A160110 Fig 6 Heat Exchanger Removal Installation CELL PANEL 5217 9 2 35 0...

Page 9: ...e right to change at any time specifications and designs without notice and without obligations 9 A11442 Fig 7 Collector Box Gasket Condensate Trap A11438 Fig 8 Heat Exchanger Panel Assembly REMOVE OL...

Page 10: ...443 06 5311 04 Replaces 443 06 5311 03 Replacement Aluminized Primary Heat Exchanger Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without...

Reviews: