VMU-C
VMU-C Instruction manual
51
VMU-O module configuration mask
The system will automatically display the information concerning the source base module
(VMU-C EM or VMU-M EM) and the location of the VMU-O module within the system.
Indicate for each of the two outputs (Output1 and Output2) the function to be applied
(Remote, Alarm, Clock):
VMU-O usage modes
Remote
: Activation and deactivation are performed through a special command
sent by the operator through VMU-C.
Alarm
: The output is associated with an alarm condition coming from local VMU
modules connected by local bus to the target VMU_O (i.e. temperature setpoint
on the VMU-P): in this case the alarm management is made locally by the VMU-
M master This selection also allows to define the initial state of the relay
(Normally closed or Normally open).
Clock
: Activation and deactivation are carried out at the time set in VMU-C.
Global
: The output is associated with an alarm condition coming from VMU-C (i.e.
an Energy meter voltage setpoint): in this case the alarm management is made
remotely by the VMU-C. This selection also allows to define the initial state of the
relay (Normally closed or Normally open).
Clicking on the “Next” button from the “Manual setup” page (Fig. 32) will grant access
to the EM (Energy Meter) configuration page .
Summary of Contents for VMU-C EM
Page 1: ...VMU C EM Web Server system for energy monitoring Instruction manual Version A6...
Page 33: ...VMU C VMU C Instruction manual 33 Commands Change of parameters on Eos Array...
Page 104: ...VMU C VMU C Instruction manual 104...
Page 108: ...VMU C VMU C Instruction manual 108...
Page 116: ...VMU C VMU C Instruction manual 116...