21
V1.0 | NRG EtherCAT User Manual | © 2022 | CARLO GAVAZZI LTD.
EN
TEACH current
reference
0x2
xx
4:02
Holds the reference current to be used for the load
deviation alarm. Can be updated automatically with a
TEACH command or manually
If TEACH is not successful value will reset to 0
This parameter is in steps of 0.01, therefore a value of
1745 = 17.45A
0 – Max. current limit
(RG..N model
dependent)
TEACH % load
deviation
0x2
xx
4:03
Holds the percentage load deviation used for the load
deviation alarm.
4
– 100%
10% (default)
Load running
hours reset
0x2
xx
5:01
Use this index to reset the load running hours reading in
case of load or SSR replacement in hours
0 hrs (default) -
Energy Reading
(low)
(read only)
0x2
xx
6:01
The energy reading is split into 2 indexes. This index
holds the lower value
0 (default) -
Energy Reading
(high)
(read only)
0x2
xx
6:02
This index holds the upper value of the energy reading
0 (default) -
SSR ON time
(read only)
0x2
xx
6:03
Holds the accumulated time in hours that the output of
the RG..N was switched ON
0 (default) -
Control level
feedback
(only for
RGx1P..N)
(read only)
0x2
xx
7:01
Holds the actual control level of the output firing. (0-
100%). In the case of ON/OFF mode it shall give 0 or
100. In the case of the other firing modes, it shall either
reflect the control level. If voltage compensation is
active than it shall contain the result of the voltage
compensation algorithm
0 – 100%
0 (default)
Status
(read only)
0x2
xx
7:02
Holds flags related to general status data of the solid
state relay. Each bit represents a specific flag
Bit 0 – Device reset Flag
Bit 1 – Autoconfiguration
Flag (for internal use)
Bit 2 – Internal Error
Alarm Flag
Bit 3 – Communication
Error Flag
Bits 4:7 – Not used
Bit 8: Alarm Status Flag
Bit 9: TEACH busy Flag
Bit 10: TEACH successful
Flag
Bit 11: Ramping Flag
Bit 12: Voltage
Compensation Active
Flag
Bits 13:15 -
Not used.
(shall be 0)
Note:
Reading the Energy (low) and Energy (high) readings as a uint32 will give the actual energy measurement