15
V1.0 | NRG EtherCAT User Manual | © 2022 | CARLO GAVAZZI LTD.
EN
Under current
limit (UCL)
0x2
xx
1:05
This parameter is in steps of 0.01, therefore a value
of 1745 = 17.45A
Check ‘Measurements’ section for more
information
0 – RG..N model
dependent &
< OCL value
Default (0A)
Over frequency
limit (OFL)
0x2
xx
1:06
Set the over and under current limit if desired
which will trigger an alarm if the current reading is
beyond the range
44 – 66Hz & > UFL value
Default (66Hz)
Under frequency
limit (UFL)
0x2
xx
1:07
44 – 66Hz & < OFL value
Default (44Hz)
Over
temperature
pre-warning
0x2
xx
1:08
Δ temperature from max at which the RG..N will
issue an alarm
0 – 50degC
Default (0dC)
Soft start ramping
time
(only for
RGx1P..N)
0x2
xx
2:01
Activate soft start with time whereby ramping will
vary linearly with the set time
0 -> soft start with time is disabled
0.1 – 25.5s -> soft start with time is abled with the
set time
This parameter is in steps of 0.1, therefore a value
of 11 = 1.1s
Note
: soft start with time and soft start with current
limit are mutually exclusive
0 – 255 (0 – 25.5s)
Default (0s)
OFF time to soft
start
(only for
RGx1P..N)
0x2
xx
2:02
Set the non-firing time before soft start is
reactivated.
0
-> soft start with occur on power up only
0.1
– 25.5s-> non firing time for soft start to be
reactivated
This parameter is in steps of 0.1, therefore a value
of 11 = 1.1s
0 – 255 (0 – 25.5s)
Default 50 (5s)
Soft start current
limit
(only for
RGx1P..N)
0x2
xx
2:03
Set the current limit to be utilised with Soft start
with current limit mode
0 -> soft start with current limit is disabled
0.1 – RG..N model dependent -> soft start with
current limit is enabled with the set current limit.
(Recommended 1.2 – 1.5 times the nominal
current)
This parameter is in steps of 0.01, therefore a value
of 6600 = 66A
Note
: soft start with time and soft start with current
limit are mutually exclusive
0 – RG..N model
dependent
Default (0)
Output substitute
mode
0x2
xx
2:04
Set the output mode to be used in case of a
communication timeout
0
Clear Output
1
Hold Output (default)
2
Set Value
Output substitute
value
0x2
xx
2:05
Set the % control level to be used in case of a
communication timeout. (Only applicable for ‘Set
Value option’ for Output substitute mode)
0 (default) – 100%